Digital devices with IO-Link

6.7 Module replacement

5. Load the configuration into the IO-Link master before parameterizing the monitoring relay.
6. Start by parameterizing the SIRIUS IO-Link monitoring relay (IO‑Link device). Additional
information is available in the S7-PCT online help.
Note
Online access to the IO‑Link master or to an IO-Link device
To be able to access the IO‑Link master or an IO-Link device online, communication between
the ET 200 and the higher-level controller must be active (BF-LED on ET 200 interface module
is off).
6.7
Module replacement
6.7.1
Module replacement (replacement of an IO‑Link device)
Parameter data and configuration data specially optimized for a specific application are stored in
an IO‑Link Device. This data deviates in many cases from the default values stored in the
IO‑Link Device.
In the event of replacement of an IO-Link Device (referred to below as "module"), the optimized
data must be transferred to the new module.
Data can be transferred via two channels:

• Module replacement with PG/PC

• Module replacement without PG/PC

6.7.2
Module replacement with PG/PC
In the event of a replacement, a PG/PC is available with the SIMATIC project of the plant.
With the data stored in the SIMATIC project, and the S7-PCT, you transfer the parameters
belonging to the replaced Device to the new Device.
6.7.3
Module replacement without PG/PC
Requirements
Install the demo project "IOL-CALL". You can download the "IOL-CALL" and the description from
the Internet (https://support.automation.siemens.com/WW/view/en/33102519/133100) .
• Copy the IO-Link Call function block FB1 (including data block DB10) to a STEP 7 project.
• Use the IO-Link Call function block FB1 as described in the demo project.