Diagnostics - Siemens 3RS2 Manual

Monitoring and control devices temperature monitoring relay
Table of Contents

Advertisement

Example: K2 alarm value at 20 °C (+ delay time):
• In the closed-circuit principle, a cable break is detected if it occurs, and the output relay is
deactivated; the display turns red
– K1 (11/12) is closed
– K2 (21/22) is closed and relay output 33/34 is open on the 3RS29
• In the open-circuit principle, a cable break is detected if it occurs, and the output relay is
deactivated; the display turns red
– K1 (11/14) is closed
– K2 (21/24) is closed and relay output 33/34 is open on the 3RS29
5.12

Diagnostics

Error
Temperature limit overshoot/undershoot Red display
Short-circuit in a sensor cable (for resist‐
ance sensors only)
Cable break in a sensor cable
Sensor outside of measuring range
Communication error between the basic
unit and the sensor expansion module
Parameter error
3RS2 temperature monitoring relay
Equipment Manual, 02/2022, A5E42462552002A/RS-AB/002
Display
Red display, the "short-circuit" icon ap‐
pears
Red display, the "cable break" icon ap‐
pears
Red display, the "out-of-range" icon ap‐
pears
Red display. "IRDA ERR" is indicated on
the display and the "nil" symbol is re‐
placed by "!".
After resetting to the factory setting or in
the event of a parameter error, the de‐
vice enters the safe state (no tempera‐
ture monitoring). The user is prompted
to check the parameters. Pressing
the "Enter" button for longer than 2 sec‐
onds puts the device into "Set Mode".
Digital devices
5.12 Diagnostics
Icon on the display
-
-
-
47