Endress+Hauser Proline Promass F 200 HART Operating Instructions Manual

Endress+Hauser Proline Promass F 200 HART Operating Instructions Manual

Coriolis mass flow measuring system
Table of Contents

Advertisement

Quick Links

Operating Instructions
Proline Promass F 200
HART
Coriolis Mass Flow Measuring System
BA01112D/06/EN/01.12
71187177
Valid as of version
01.02.zz (Device firmware)

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Proline Promass F 200 HART

  • Page 1 Operating Instructions Proline Promass F 200 HART Coriolis Mass Flow Measuring System BA01112D/06/EN/01.12 71187177 Valid as of version 01.02.zz (Device firmware)
  • Page 2 Proline Promass F 200 HART • Make sure the document is stored in a safe place such that it is always available when working on or with the device. • To avoid danger to individuals or the facility, read the "Basic safety instructions" section carefully, as well as all other safety instructions in the document that are specific to working procedures.
  • Page 3: Table Of Contents

    Proline Promass F 200 HART Table of contents Table of contents Document information ....5 Electrical connection ....25 Document function .
  • Page 4 10.4.7 Configuring the partial filled pipe 13.3 Endress+Hauser services ....113 detection ..... . . 73 10.5 Advanced settings .
  • Page 5: Document Information

    Proline Promass F 200 HART Document information Document information Document function These Operating Instructions contain all the information that is required in various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.
  • Page 6: Symbols For Certain Types Of Information

    The following document types are available: • On the CD-ROM supplied with the device • In the Download Area of the Endress+Hauser Internet site: www.endress.com ® Download For a detailed list of the individual documents along with the documentation code (®...
  • Page 7: Standard Documentation

    Proline Promass F 200 HART Document information 1.3.1 Standard documentation Document type Purpose and content of the document Technical Information Planning aid for your device The document contains all the technical data on the device and provides an overview of the accessories and other products that can be ordered for the device.
  • Page 8: Basic Safety Instructions

    Observe the specified maximum process pressure. ► Verification for borderline cases: For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying ► the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability as minute changes in the temperature, concentration or level of contamination in the process can alter the corrosion resistance properties.
  • Page 9: Workplace Safety

    It meets general safety standards and legal requirements. It also complies with the EC directives listed in the device-specific EC Declaration of Conformity. Endress+Hauser confirms this by affixing the CE mark to the device. Endress+Hauser...
  • Page 10: Product Description

    Terminals (spring loaded terminals, pluggable) Connection compartment cover Sensor Registered trademarks Ò HART Registered trademark of the HART Communication Foundation, Austin, USA Ò Ò Ò Applicator , FieldCare , Field Xpert , HistoROM Registered or registration-pending trademarks of the Endress+Hauser Group Endress+Hauser...
  • Page 11: Incoming Acceptance And Product

    A0015502 A0013699 Do the nameplate data match the ordering information on the delivery note? A0015502 A0013697 Is the CD-ROM with the Technical Documentation and documents present? If one of the conditions is not satisfied, contact your Endress+Hauser Sales Center. Endress+Hauser...
  • Page 12: Product Identification

    Incoming acceptance and product identification Proline Promass F 200 HART Product identification The following options are available for identification of the measuring device: • Nameplate specifications • Order code with breakdown of the device features on the delivery note • Enter serial numbers from nameplates in W@M Device Viewer (www.endress.com/deviceviewer): All information about the measuring device is displayed.
  • Page 13: Sensor Nameplate

    Proline Promass F 200 HART Incoming acceptance and product identification 4.2.2 Sensor nameplate Order code: Ser. no.: Ext. ord. cd.: Ptest: Size: Material: Patents Date: A0017923 å 3 Example of a sensor nameplate Name of the sensor Manufacturing location Order code Serial number (Ser.
  • Page 14: Symbols On Measuring Device

    Incoming acceptance and product identification Proline Promass F 200 HART 4.2.3 Symbols on measuring device Symbol Meaning WARNING! This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury. Reference to documentation Refers to the corresponding device documentation.
  • Page 15: Storage And Transport

    Proline Promass F 200 HART Storage and transport Storage and transport Storage conditions Observe the following notes for storage: • Store in the original packaging to ensure protection from shock. • Do not remove protective covers or protective caps installed on process connections. They prevent mechanical damage to the sealing surfaces and fouling in the measuring tube.
  • Page 16: Packaging Disposal

    Storage and transport Proline Promass F 200 HART Packaging disposal All packaging materials are environmentally friendly and 100% recyclable: • Measuring device secondary packaging: polymer stretch film that conforms to EC Directive 2002/95/EC (RoHS). • Packaging: – Wood crate, treated in accordance with ISPM 15 standard, which is confirmed by the affixed IPPC logo.
  • Page 17: Mounting

    Proline Promass F 200 HART Mounting Mounting Mounting requirements No special measures such as supports are necessary. External forces are absorbed by the construction of the device. 6.1.1 Mounting position Mounting location A0015595 To prevent measuring errors arising from accumulation of gas bubbles in the measuring tube, avoid the following mounting locations in the pipe: •...
  • Page 18 Mounting Proline Promass F 200 HART A0015596 å 4 Installation in a down pipe (e.g. for batching applications) Supply tank Sensor Orifice plate, pipe restriction Valve Batching tank Æ Orifice plate, pipe restriction [mm] [in] [mm] [in] 0.24 ½ 0.40 0.55...
  • Page 19: Requirements From Environment And Process

    Proline Promass F 200 HART Mounting If a sensor is installed horizontally with a curved measuring tube, match the position of the sensor to the fluid properties. A0014057 å 5 Orientation of sensor with curved measuring tube Avoid this orientation for fluids with entrained solids: Risk of solids accumulating.
  • Page 20 Mounting Proline Promass F 200 HART For this reason, the following mounting locations are recommended: • At the lowest point in a vertical pipe • Downstream from pumps (no danger of vacuum) A0015594 Thermal insulation In the case of some fluids, it is important that the heat radiated from the sensor to the transmitter is kept to a minimum.
  • Page 21: Special Mounting Instructions

    Proline Promass F 200 HART Mounting Vibrations The high oscillation frequency of the measuring tubes ensures that the correct operation of the measuring system is not influenced by plant vibrations. 6.1.3 Special mounting instructions Outlet run for peripheral device If a pressure and temperature measuring device are installed downstream from the measuring device, make sure there is sufficient distance between the two devices.
  • Page 22: Mounting The Measuring Device

    Mounting Proline Promass F 200 HART [mm] [in] [mm] [in] [in] [in] [mm] [in] [mm] [in] 1½ Approx.42 Approx.1.65 AF 1 ½ NPT 2.64 12.20 Approx.42 Approx.1.65 AF 1 ½ NPT 3.11 17.78 WARNING Limited functional reliability of the rupture disk.
  • Page 23: Turning The Transmitter Housing

    Proline Promass F 200 HART Mounting à A0013964 6.2.4 Turning the transmitter housing To provide easier access to the connection compartment or display module, the transmitter housing can be turned: max. 350° 8 mm 8 mm A0013713 1. Release the fixing screw.
  • Page 24: Post-Mounting Check

    Mounting Proline Promass F 200 HART 7. Reverse the removal procedure to reassemble the transmitter. Post-mounting check Is the device damaged (visual inspection)? Does the measuring device conform to the measuring point specifications? For example: • Process temperature (® ä 126) •...
  • Page 25: Electrical Connection

    Proline Promass F 200 HART Electrical connection Electrical connection Connection conditions 7.1.1 Required tools • For cable entries: Use corresponding tools • For securing clamp: Allen key3 mm • Wire stripper • When using stranded cables: Crimping tool for wire end ferrule •...
  • Page 26: Terminal Assignment

    Electrical connection Proline Promass F 200 HART 7.1.3 Terminal assignment Transmitter 4-20 mA HART connection version with additional outputs A0013570 A0018161 Maximum number of terminals, without integrated overvoltage Maximum number of terminals, with integrated protection overvoltage protection Output 1 (passive): supply voltage and signal transmission...
  • Page 27: Preparing The Measuring Device

    Proline Promass F 200 HART Electrical connection Calculation of the maximum load Depending on the supply voltage of the power supply unit (U ), the maximum load (R ) including line resistance must be observed to ensure adequate terminal voltage at the device. In doing so, observe the minimum terminal voltage (®...
  • Page 28: Connecting The Transmitter

    Electrical connection Proline Promass F 200 HART 7.2.1 Connecting the transmitter 3 mm 20 mm 10 (0.4) mm (in) A0013836 1. Loosen the securing clamp of the connection compartment cover. 2. Unscrew the connection compartment cover. 3. Push the cable through the cable entry . To ensure tight sealing, do not remove the sealing ring from the cable entry.
  • Page 29: Ensuring The Degree Of Protection

    Proline Promass F 200 HART Electrical connection Ensuring the degree of protection The measuring device fulfills all the requirements for the IP66/67 degree of protection, Type 4X enclosure. To guarantee IP66/67 degree of protection, Type 4X enclosure, carry out the following steps after the electrical connection: 1.
  • Page 30: Operation Options

    Operation options Proline Promass F 200 HART Operation options Overview of operation options A0015607 Local operation via display module Computer with operating tool (e.g. FieldCare, AMS Device Manager, SIMATIC PDM) Field Xpert SFX100 Field Communicator 475 Control system (e.g. PLC)
  • Page 31: Structure And Function Of The Operating Menu

    Proline Promass F 200 HART Operation options Structure and function of the operating menu 8.2.1 Structure of the operating menu For an overview of the operating menu with menus and parameters (® ä 133) Operating menu for operators and maintenances Language Display/operat.
  • Page 32: Operating Philosophy

    Operation options Proline Promass F 200 HART 8.2.2 Operating philosophy The individual parts of the operating menu are assigned to certain user roles. Each user role corresponds to typical tasks within the device lifecycle. Menu User role and tasks Content/meaning...
  • Page 33: Access To The Operating Menu Via The Local Display

    Proline Promass F 200 HART Operation options Access to the operating menu via the local display 8.3.1 Operational display X X X X X X X 1120.50 kg/h A0016501 Operational display Device tag (® ä 75) Status area Display area for measured values (4-line) Operating elements (®...
  • Page 34: Navigation View

    Operation options Proline Promass F 200 HART Mass flow A0013710 • Volume flow • Corrected volume flow A0013711 • Density • Reference density A0013946 Temperature A0013947 Totalizer The measurement channel number indicates which of the three totalizers is displayed. A0013943 Output The measurement channel number indicates which of the two current outputs is displayed.
  • Page 35 Proline Promass F 200 HART Operation options Navigation path The navigation path - displayed at the top left in the navigation view - consists of the following elements: • In the submenu: Omission symbol for operating Name of current Display symbol for menu menu levels in between •...
  • Page 36: Editing View

    Operation options Proline Promass F 200 HART Wizard A0013968 Parameters within a wizard No display symbol exists for parameters in submenus. A0013972 Locking Symbol Meaning Parameter locked When displayed in front of a parameter name, indicates that the parameter is locked.
  • Page 37 Proline Promass F 200 HART Operation options Inserts minus sign at the input position. – A0016620 Confirms selection. A0013985 Moves the input position one position to the left. A0016621 Exits the input without applying the changes. A0013986 Clears all entered characters.
  • Page 38: Operating Elements

    Operation options Proline Promass F 200 HART 8.3.4 Operating elements Meaning Minus key In a menu, submenu Moves the selection bar upwards in a choose list. With a Wizard Confirms the parameter value and goes to the previous parameter. A0013969 With a text and numeric editor In the input mask, moves the selection bar to the left (backwards).
  • Page 39 Proline Promass F 200 HART Operation options • Setup • Conf. backup disp. • Simulation Calling up and closing the context menu The user is in the operational display. 1. Press F for 2 s. Ã The context menu opens.
  • Page 40: Navigating And Selecting From List

    Operation options Proline Promass F 200 HART 8.3.6 Navigating and selecting from list Different operating elements are used to navigate through the operating menu. The navigation path is displayed on the left in the header. Icons are displayed in front of the individual menus. These icons are also shown in the header during navigation.
  • Page 41: Calling Up Help Text

    Proline Promass F 200 HART Operation options The direct access code consists of a 4-digit number and the channel number, which identifies the channel of a process variable: e.g. 0914-1. In the navigation view, this appears on the right-hand side in the header of the selected parameter.
  • Page 42: Changing The Parameters

    Operation options Proline Promass F 200 HART 8.3.9 Changing the parameters For a description of the editing display - consisting of text editor and numeric editor - with symbols (® ä 36), for a description of the operating elements (® ä 38) Example: Changing the parameter "20 mA value"...
  • Page 43: User Roles And Related Access Authorization

    Proline Promass F 200 HART Operation options A message is displayed if the value entered is outside the permitted value range. Ent. access code Invalid or out of range input value Min:0 Max:9999 A0014049-EN 8.3.10 User roles and related access authorization The two user roles "Operator"...
  • Page 44 Operation options Proline Promass F 200 HART XXXXXXXXXX 20.50 Keylock on kg/h A0014000-EN After disabling the keypad lock: XXXXXXXXXX 20.50 Keylock off kg/h A0014001-EN If the user attempts to access the operating menu while the keylock is enabled, the message Keylock on also appears.
  • Page 45: Access To The Operating Menu Via The Operating Tool

    Proline Promass F 200 HART Operation options Access to the operating menu via the operating tool The structure of the operating menu in the operating tools is the same as for operation via the local display. 8.4.1 Connecting the operating tool...
  • Page 46: Field Xpert Sfx100

    FieldCare Function scope FDT-based plant asset management tool from Endress+Hauser. It can configure all smart field devices in a system and helps you manage them. By using the status information, it is also a simple but effective way of checking their status and condition.
  • Page 47: Ams Device Manager

    Proline Promass F 200 HART Operation options Source for device description files See data (® ä 49) User interface A0017402-EN Header Picture of device Device tag (® ä 75) Status area with status signal (® ä 98) Display area for current measured values (® ä 89)
  • Page 48: Field Communicator 475

    Operation options Proline Promass F 200 HART 8.4.6 Field Communicator 475 Function scope Industrial handheld terminal from Emerson Process Management for remote configuration and measured value display via HART protocol. Source for device description files See data (® ä 49)
  • Page 49: System Integration

    Proline Promass F 200 HART System integration System integration Overview of device description files 9.1.1 Current version data for the device Firmware version 01.02.zz • On the title page of the Operating instructions • On transmitter nameplate (® ä 12) •...
  • Page 50: Other Settings

    System integration Proline Promass F 200 HART The assignment of the measured variables to the dynamic variables can be modified and assigned as desired via local operation and the operating tool using the following parameters: • Expert ® Communication ® HART output ® Assign PV •...
  • Page 51: Commissioning

    Proline Promass F 200 HART Commissioning Commissioning 10.1 Function check Before commissioning the device, make sure that the post-installation and post-connection checks have been performed. • "Post-mounting check" checklist (® ä 24) • "Post-connection check" checklist (® ä 29) 10.2 Switching on the measuring device After a successful function check, switch on the measuring device.
  • Page 52 Commissioning Proline Promass F 200 HART X X X X X X X 20.50 0104-1 Main menu Language English Display/operat. Setup Main menu Display/operat. Setup Diagnostic / ../Setup Medium selection XXXXXXXXX XXXXXXXXX A0014007-EN å 10 Illustrated using the example of the local display Overview of the wizards in the "Setup"...
  • Page 53: Selecting And Setting The Medium

    Proline Promass F 200 HART Commissioning 10.4.1 Selecting and setting the medium The Medium selection wizard guides you systematically through all parameters that have to be configured for selecting and setting the medium. Navigation path "Setup" menu ® Medium selection...
  • Page 54 Commissioning Proline Promass F 200 HART Reference sound velocity Enter the sound velocity of 0 to 99 999 m/s 331.5 m/s the gas at 0°C (32°F). Temperature coefficient Enter the temperature Max. 15-digit, positive 0.61 (m/s)/K sound velocity coefficient of the sound floating-point number velocity of the gas.
  • Page 55: Configuring The Current Output

    Proline Promass F 200 HART Commissioning 10.4.2 Configuring the current output The two wizards Current output 1-2 guide you systematically through all parameters that have to be set in the configuration of the respective current output. Navigation path "Setup" menu ® Current output 1 "Setup"...
  • Page 56 Commissioning Proline Promass F 200 HART Corrected volume Reference density flow Corrected volume Reference density flow unit unit Corrected volume flow calculation Fixed reference Calculated ref. density density Reference density Linear unit expansion coefficient Fixed reference Square density expansion coefficient...
  • Page 57 Proline Promass F 200 HART Commissioning Parameter overview with brief description Parameters Description Selection/ Factory setting User entry Assign current output 1-2 Select process variable for • Off (only for current • Current output 1: mass current output. output 2) flow •...
  • Page 58 Commissioning Proline Promass F 200 HART Reference density unit Select the unit for reference Unit choose list Country-dependent: density. • kg/Nl • lb/Scf Result The selected unit applies for: – Outputs – Low value partial filled pipe detection – High value partial filled pipe detection –...
  • Page 59: Output

    Proline Promass F 200 HART Commissioning 10.4.3 Configuring the pulse/frequency/switch output The Pulse/frequency/switch output wizard guides you systematically through all parameters that can be set for the configuration of the selected output type. Navigation path "Setup" menu ® Pulse/frequency/switch output...
  • Page 60 Commissioning Proline Promass F 200 HART Operating mode Specify the output as a pulse, • Pulse Pulse frequency or switch output. • Frequency • Switch The picklist depends on the selected device order (® ä 26). Assign pulse output Select the process variable for •...
  • Page 61 Proline Promass F 200 HART Commissioning Temperature unit Select the unit for Unit choose list Country-dependent: temperature. • °C (Celsius) • °F (Fahrenheit) Result The selected unit applies for: – Outputs – Reference temperature – Simulation process variable Reference temperature Enter the reference Max.
  • Page 62 Commissioning Proline Promass F 200 HART Sequence of the wizard for the frequency output Operating mode Frequency Assign freq. Volume flow Density Temperature Ref.density Mass flow Correct.vol.flow Temperature Volume flow Density unit unit unit Mass flow Corr. vol. unit Ref. dens. unit unit Min.
  • Page 63 Proline Promass F 200 HART Commissioning Assign frequency output Select the process variable for • Off the frequency output. • Mass flow • Volume flow • Corrected volume flow • Density • Reference density • Temperature Mass flow unit Select the unit for mass flow.
  • Page 64 Commissioning Proline Promass F 200 HART Temperature unit Select the unit for Unit choose list Country-dependent: temperature. • °C (Celsius) • °F (Fahrenheit) Result The selected unit applies for: – Outputs – Reference temperature – Simulation process variable Minimum frequency value Enter the minimum 0.0 to 1 000.0...
  • Page 65 Proline Promass F 200 HART Commissioning Operating mode Switch Switch out funct Fl. direct. Limit Status check Assign Assign Assign limit dir.check status Ref. Partial Mass Correct. Totalizer Mass Volume Correct. Low flow density pipe det. flow vol.flow 1/2/3 flow flow vol.flow...
  • Page 66 Commissioning Proline Promass F 200 HART Assign diagnostic behavior Select the diagnostic • Alarm Alarm behavior for the switch • Alarm or warning output. • Warning Assign limit Select the process variable for • Mass flow Mass flow the limit function.
  • Page 67: Configuring The Local Display

    Proline Promass F 200 HART Commissioning Reference density unit Select the unit for reference Unit choose list Country-dependent: density. • kg/Nl • lb/scf Result The selected unit applies for: – Outputs – Low value partial filled pipe detection – High value partial filled pipe detection –...
  • Page 68 Commissioning Proline Promass F 200 HART Sequence of the wizard Format display Value 1 display 0% bargraph value 1 100% bargraph value 1 Value 2 display Value 3 display 0% bargraph value 3 100% bargraph value 3 Value 4 display...
  • Page 69: Configuring The Output Conditioning

    Proline Promass F 200 HART Commissioning 0% bargraph value 1 Enter the 0% value to be Floating point number with Country-dependent: shown on the bargraph sign • 0 kg/h display for the measured • 0 lb/min value 1. 100% bargraph value 1...
  • Page 70 Commissioning Proline Promass F 200 HART Sequence of the wizard Level of flow fluctuation Slight Strong Moderate Display Display Display damping damping damping Damping Damping Damping output 1 output 1 output 1 Damping Damping Damping output 2 output 2 output 2...
  • Page 71 Proline Promass F 200 HART Commissioning Parameter overview with brief description Parameters Description Selection/ Factory setting User entry Level of flow fluctuation Specify the extent measured • Slight Moderate values fluctuate due to • Moderate changes in the process. • Strong...
  • Page 72: Configuring The Low Flow Cut Off

    Commissioning Proline Promass F 200 HART 10.4.6 Configuring the low flow cut off The Low flow cut off wizard guides you systematically through all parameters that have to be set for configuring the low flow cut off. Navigation path "Setup" menu ® Low flow cut off...
  • Page 73: Configuring The Partial Filled Pipe Detection

    Proline Promass F 200 HART Commissioning 10.4.7 Configuring the partial filled pipe detection The Partial filled pipe detection wizard guides you systematically through all parameters that have to be set for configuring the monitoring of the pipe filling. Navigation path "Setup"...
  • Page 74: Advanced Settings

    Commissioning Proline Promass F 200 HART 10.5 Advanced settings The Advanced setup menu with its submenus contains all parameters needed for specific settings. Navigation path "Setup" menu ® Advanced setup Navigation to the "Advanced setup" submenu X X X X X X X 20.50...
  • Page 75: Defining The Tag Name

    Proline Promass F 200 HART Commissioning ® Totalizer 2 (® ä 79) Totalizer 3 ® (® ä 79) ® SIL confirmation (® ä 132) Disable SIL ® (® ä 132) Display ® (® ä 81) ® Conf. backup disp. (® ä 82) order code for "Additional approval", option LA "SIL", see device-dependent supplementary documentation...
  • Page 76: Setting The System Units

    Commissioning Proline Promass F 200 HART External reference density Fixed reference density Reference temperature Linear expansion coefficient Square expansion coefficient Parameter overview with brief description Parameter Prerequisites Description Selection/input Factory settings Corrected volume – Select the reference density Calculated • Fixed reference...
  • Page 77 Proline Promass F 200 HART Commissioning Structure of the submenu ® System units Mass flow unit Mass unit Volume flow unit Volume unit Corrected volume flow unit Corrected volume unit Density unit Reference density unit Temperature unit Length unit Pressure unit...
  • Page 78: Carrying Out A Sensor Adjustment

    Commissioning Proline Promass F 200 HART Corrected volume flow unit Select the unit for corrected Unit choose list Country-dependent: volume flow. • Nl/h • Scf/min Result The selected unit applies for: – Output – Low flow cut off – Simulation process...
  • Page 79: Configuring The Totalizer

    Proline Promass F 200 HART Commissioning Navigation path "Setup" menu ® Advanced setup ® Sensor adjustment Structure of the submenu Sensor adjustment ® Installation direction ® Zero point adjustment Zero point adjustment control Adjustment in progress Parameter overview with brief description...
  • Page 80 Commissioning Proline Promass F 200 HART Assign process Select process • Off Mass flow variable variable for totalizer. • Mass flow • Volume flow Result • Corrected The selection volume flow determines the choose list of the Unit parameter. Unit...
  • Page 81: Carrying Out Additional Display Configurations

    Proline Promass F 200 HART Commissioning 10.5.6 Carrying out additional display configurations In the Display submenu, you can set all parameters involved in the configuration of the local display. Navigation path "Setup" menu ® Advanced setup ® Display Structure of the submenu Display ®...
  • Page 82: Configuration Management

    Commissioning Proline Promass F 200 HART Decimal places 2 A measured value is specified in Select the number of • x x.xx the parameter Value 2 decimal places for • x.x the display value. • x.xx display. • x.xxx • x.xxxx...
  • Page 83 Proline Promass F 200 HART Commissioning Navigation path "Setup" menu ® Advanced setup ® Conf. backup disp. Function scope of the "Configuration management" parameter Options Description Execute backup The current device configuration is backed up from the integrated HistoROM to the device's display module.
  • Page 84: Simulation

    Commissioning Proline Promass F 200 HART 10.7 Simulation The Simulation submenu enables you to simulate, without a real flow situation, various process variables in the process and the device alarm mode and to verify downstream signal chains (switching valves or closed-control loops).
  • Page 85: Protecting Settings From Unauthorized Access

    Proline Promass F 200 HART Commissioning Simulation current Switch simulation of • Off output 1-2 the current output • On on and off. Value current The On option is selected in the Enter the current 3.6 to 22.5 mA Current value...
  • Page 86: Write Protection Via Write Protection Switch

    Commissioning Proline Promass F 200 HART Navigation path "Setup" menu ® Advanced setup ® Define access code Structure of the submenu ® Define access code Define access code Confirm access code Defining the access code via local display 1. Navigate to the Define access code parameter.
  • Page 87 Proline Promass F 200 HART Commissioning The parameter values are now read only and cannot be edited any more (exception Contrast display): • Via local display • Via service interface (CDI) • Via HART protocol XXXXXXXXXXXXX 3 mm A0013768 1. Loosen the securing clamp.
  • Page 88 Commissioning Proline Promass F 200 HART X X X X X X X 4.00 A0015870 If hardware write protection is disabled, no option is displayed in the Locking status parameter (® ä 89). On the local display, the -symbol disappears from in front of the parameters in the header of the operational display and in the navigation view.
  • Page 89: Operation

    Proline Promass F 200 HART Operation Operation 11.1 Read device locking status The write protection types that are currently active can be determined using the Locking status parameter. Navigation path "Expert" menu ® Locking status Function scope of "Locking status" parameter...
  • Page 90: Totalizer

    Operation Proline Promass F 200 HART Density Reference density Temperature Pressure value Parameter overview with brief description Parameter overview with brief description Parameter Prerequisite Description Display Mass flow – Displays the mass flow Floating-point number currently measured with sign Volume flow –...
  • Page 91: Output Values

    Proline Promass F 200 HART Operation Parameter overview with brief description Parameters Prerequisite Description Display Totalizer value 1-3 One of the following options is selected Displays the current Floating point number in the Assign process variable totalizer counter value. with sign...
  • Page 92: Adapting The Measuring Device To The Process Conditions

    Operation Proline Promass F 200 HART Pulse output Displays the value Positive floating-point currently measured for number the pulse output. Output frequency Displays the value 0 to 1 250 Hz currently measured for the frequency output. Switch status Displays the current •...
  • Page 93: Showing Data Logging

    Proline Promass F 200 HART Operation Preset value 3 Reset all totalizers Parameter overview with brief description Parameters Prerequisite Description Selection/ Factory setting User entry Control totalizer 1-3 One of the following options is Control totalizer • Totalize Totalize selected in the Assign process value.
  • Page 94 Operation Proline Promass F 200 HART If the length of the logging interval or the assignment of the process variables to the channels is changed, the content of the data logging is deleted. "Data logging" submenu Data logging ® Assign channel 1...
  • Page 95 Proline Promass F 200 HART Operation Display channel 1-4 One of the following options is Displays the selected in the Assign channel measured value trend for the logging 1-4 parameter: channel in the form • Mass flow of a chart.
  • Page 96: Diagnostics And Troubleshooting

    Diagnostics and troubleshooting Proline Promass F 200 HART Diagnostics and troubleshooting 12.1 General troubleshooting For local display Problem Possible cause Remedy Local display dark and no output signals Supply voltage does not match that Apply the correct supply voltage specified on the nameplate.
  • Page 97 Proline Promass F 200 HART Diagnostics and troubleshooting No write access to parameters Current user role has limited access 1. Check user role (® ä 43). authorization 2. Enter correct customer-specific access code (® ä 43). No connection via HART protocol...
  • Page 98: Diagnostic Information On Local Display

    Diagnostics and troubleshooting Proline Promass F 200 HART 12.2 Diagnostic information on local display 12.2.1 Diagnostic message Faults detected by the self-monitoring system of the measuring device are displayed as a diagnostic message in alternation with the operational display. Operational display in alarm condition...
  • Page 99 Proline Promass F 200 HART Diagnostics and troubleshooting Diagnostic behavior Symbol Meaning Alarm • Measurement is interrupted. • Signal outputs and totalizers assume the defined alarm condition. • A diagnostic message is generated. A0013961 • For local display with touch control: the background lighting changes to red.
  • Page 100: Calling Up Remedy Information

    Diagnostics and troubleshooting Proline Promass F 200 HART 12.2.2 Calling up remedy information X X X X X X X X X X X X X X 20.50 S441 Curr. output 1 Curr. output 1 (ID:153) S441 2d11h05m55s 1. Check process 2.
  • Page 101: Diagnostic Information In Fieldcare

    Proline Promass F 200 HART Diagnostics and troubleshooting 12.3 Diagnostic information in FieldCare 12.3.1 Diagnostic options Any faults detected by the measuring device are displayed on the home page of the operating tool once the connection has been established. XXXXXXX...
  • Page 102: Overview Of Diagnostic Information

    Diagnostics and troubleshooting Proline Promass F 200 HART Navigation path "Expert" menu ® System ® Diagnostic handling ® Diagnostic behavior ® Assign behavior of diagnostic no. xxx A0014048-EN å 26 Illustrated using the example of the local display You can assign the following options to the diagnostic number as the diagnostic behavior:...
  • Page 103 Proline Promass F 200 HART Diagnostics and troubleshooting Status Diagnostic signal Diagnostic behavior Short text Remedy information number from the from the factory factory Diagnostics for the electronics Software incompatible 1. Check software. Alarm 2. Flash or change main electronic module.
  • Page 104 Diagnostics and troubleshooting Proline Promass F 200 HART Up-/download active Up-/download active, please wait Warning Trim Carry out trim. Warning Incompatible 1. Restart device. Alarm configuration 2. Contact service. Dataset 1. Check data set file. Warning 2. Check device configuration.
  • Page 105: Pending Diagnostic Events

    Proline Promass F 200 HART Diagnostics and troubleshooting Process temperature Increase process temperature. Warning Process limit Low flow cut off active! Logbook entry only 1. Check low flow cut off configuration. Partly filled pipe 1. Check for gas in process.
  • Page 106: Diagnostic List

    Diagnostics and troubleshooting Proline Promass F 200 HART Previous diagnostics 2 diagnostic events have Displays the diagnostic event Symbol for diagnostic already occurred that occurred prior to the behavior, diagnostic code current diagnostic event and short message along with the diagnostic information.
  • Page 107: Filtering The Event Logbook

    Proline Promass F 200 HART Diagnostics and troubleshooting The event history includes entries for: • Diagnostic events (® ä 102) • Information events (® ä 107) In addition to the operation time of its occurrence, each event is also assigned a symbol that indicates whether the event has occurred or is ended: •...
  • Page 108: Resetting The Measuring Device

    Diagnostics and troubleshooting Proline Promass F 200 HART I1156 Memory error trend I1157 Memory error event list I1185 Display backup done I1186 Restore via display done I1187 Settings downloaded with display I1188 Display data cleared I1189 Backup compared I1209 Density adjustment OK...
  • Page 109 Proline Promass F 200 HART Diagnostics and troubleshooting Navigation path "Diagnostics" menu ® Device information Structure of the submenu ® Device info Device tag (® ä 75) Serial number Firmware version Device name Order code Extended order code 1 Extended order code 2...
  • Page 110: 12.11 Disposal

    Diagnostics and troubleshooting Proline Promass F 200 HART Extended order code 1-3 Depending on the length of Displays the 1st, 2nd or 3rd Character string the extended order code, the part of the extended order code is divided into a code.
  • Page 111: 12.12 Firmware History

    "Manufacturer's information" document. The manufacturer's information is available: • In the Download Area of the Endress+Hauser Internet site: www.endress.com ® Download • Specify the following details: – Product root, e.g. 8E2B –...
  • Page 112: Repair

    • Spare parts are grouped into logical kits with the associated Installation Instructions. • Repairs are carried out by Endress+Hauser Service or by correspondingly trained customers. • Certified devices can be converted into other certified devices by Endress+Hauser Service or at the factory only.
  • Page 113: Endress+Hauser Services

    • Is located on the device nameplate and the spare part overview sign. • Can be read out via the Serial number parameter in the Device information submenu (® ä 108). 13.3 Endress+Hauser services Contact your Endress+Hauser Sales Center for information on services and spare parts. Endress+Hauser...
  • Page 114: Maintenance

    • Observe the maximum permitted fluid temperature for the measuring device (® ä 126). 14.2 Measuring and test equipment Endress+Hauser offers a wide variety of measuring and test equipment, such as W@M or device tests. Your Endress+Hauser Sales Center can provide detailed information on the services.
  • Page 115: Return

    The measuring device must be returned if repairs or a factory calibration are required, or if the wrong measuring device has been ordered or delivered. According to legal regulations, Endress+Hauser, as an ISO-certified company, is required to follow certain procedures when handling returned products that are in contact with medium.
  • Page 116: Disposal

    Disposal Proline Promass F 200 HART Disposal 16.1 Removing the measuring device 1. Switch off the device. 2. WARNING! Danger to persons from process conditions. Beware of hazardous process conditions such as pressure in the measuring device, high temperatures or aggressive fluids.
  • Page 117: Technical Data

    Proline Promass F 200 HART Technical data Technical data 17.1 Application The measuring device is suitable for flow measurement of liquids and gases only. Depending on the version ordered, the measuring device can also measure potentially explosive, flammable, poisonous and oxidizing media.
  • Page 118: Output

    Technical data Proline Promass F 200 HART Maximum full scale value for gas [kg/h] max(G) Maximum full scale value for liquid [kg/h] max(F) < g can never be greater than g max(G) max(F) max(G) max(F) Gas density in [kg/m ] at operating conditions...
  • Page 119 Proline Promass F 200 HART Technical data Maximum input values • DC35 V • 50 mA For information on the Ex connection values Voltage drop • For £ 2 mA: 2 V • For 10 mA: 8 V Residual current £...
  • Page 120 Technical data Proline Promass F 200 HART HART Device diagnostics Device condition can be read out via HART Command 48 Pulse/frequency/switch output Pulse output Failure mode Choose from: • Actual value • No pulses Frequency output Failure mode Choose from: •...
  • Page 121: Power Supply

    Proline Promass F 200 HART Technical data 17.5 Power supply Terminal assignment (® ä 26) Supply voltage An external power supply is required for each output. The following supply voltage values apply for the 4-20 mA and 4-20 mA HART current output:...
  • Page 122: Performance Characteristics

    Technical data Proline Promass F 200 HART Cable specification (® ä 25) Overvoltage protection The device can be ordered with integrated overvoltage protection for ATEX/IECEx approvals: Order code for "Accessory mounted", option NA "overvoltage protection" Input voltage range Values correspond to supply voltage specifications (® ä 26) 2 ×...
  • Page 123 Proline Promass F 200 HART Technical data Zero point stability Zero point stability [mm] [in] [kg/h] [lb/min] 0.180 0.007 0.585 0.021 1.620 0.059 1½ 4.050 0.149 6.300 0.231 Example for max. measured error E [%] Q [%] A0018211 Error: Maximum measured error as % o.r. (example) Flow rate as % Design fundamentals (®...
  • Page 124 Technical data Proline Promass F 200 HART 1:10 1:20 1:50 1:100 1:500 [inch] [lb/min] [lb/min] [lb/min] [lb/min] [lb/min] [lb/min] 1½ 1 650 82.5 16.5 2 570 128.5 51.4 25.7 5.14 Accuracy of outputs o.r. = of reading; o.f.s. = of full scale value...
  • Page 125: Installation

    Proline Promass F 200 HART Technical data Mass flow and volume flow Influence of medium temperature When there is a difference between the temperature for zero point adjustment and the process temperature, the typical measured error of the sensor is ±0.0002 % of the full scale value/°C (±0.0001 % of the full scale value/°F).
  • Page 126: Process

    Technical data Proline Promass F 200 HART –40 to +80 °C (–40 to +176 °F), preferably at +20 °C (+68 °F) Storage temperature Climate class DIN EN 60068-2-38 (test Z/AD) Transmitter Degree of protection • As standard: IP66/67, type 4X enclosure •...
  • Page 127: 17.10 Mechanical Construction

    Proline Promass F 200 HART Technical data • The minimum recommended full scale value is approx. 1/20 of the maximum full scale value • In most applications, 20 to 50 % of the maximum full scale value can be considered ideal •...
  • Page 128 Technical data Proline Promass F 200 HART Transmitter cable entries Order code for "Housing", option B "GT18 two-chamber, 316L" Electrical connection Type of protection Material Cable gland M20 × 1.5 • Non-Ex Stainless steel 1.4404 • Ex ia • Ex ic •...
  • Page 129: 17.11 Operability

    Proline Promass F 200 HART Technical data Accessories Weather protection cover Stainless steel 1.4301 Process connections • Flanges: – EN 1092-1 (DIN 2501) – Namur lengths in accordance with NE 132 – ASME B16.5 – JIS B2220 • VCO connections •...
  • Page 130: 17.12 Certificates And Approvals

    Directives. These are listed in the corresponding EC Declaration of Conformity along with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. C-Tick symbol The measuring system meets the EMC requirements of the "Australian Communications and Media Authority (ACMA)".
  • Page 131: 17.13 Application Packages

    Proline Promass F 200 HART Technical data Pressure Equipment Directive • With the identification PED/G1/x (x = category) on the sensor nameplate, Endress+Hauser confirms conformity with the "Basic Safety Requirements" specified of Appendix I of the Pressure Equipment Directive 97/23/EC.
  • Page 132: 17.15 Documentation

    Proline Promass F 200 HART 17.15 Documentation The following document types are available: • On the CD-ROM supplied with the device • In the Download Area of the Endress+Hauser Internet site: www.endress.com ® Download Standard documentation Device type: 8F2B**- Communication...
  • Page 133: Appendix

    Proline Promass F 200 HART Appendix Appendix 18.1 Overview of the Operator/Maintenance operating menu The following table provides an overview of the entire operating menu structure with menus and parameters. The direct access code to the parameter is given in brackets. The page reference indicates where a description of the parameter can be found in the manual.
  • Page 134 Appendix Proline Promass F 200 HART Density unit (® ä 57) Corrected volume flow unit (® ä 57) Corrected volume flow (® ä 57) Reference density unit (® ä 58) Fixed reference density (® ä 58) Linear expansion coefficient (® ä 58) Square expansion (®...
  • Page 135 Proline Promass F 200 HART Appendix Square expansion (® ä 58) coefficient Temperature unit (® ä 67) Reference temperature (® ä 61) Pulse value (® ä 61) Pulse width (® ä 61) Failure mode (® ä 61) Minimum frequency value (®...
  • Page 136 Appendix Proline Promass F 200 HART 100% bargraph value 3 (® ä 69) Value 4 display (® ä 69) Output conduct ® (® ä 69) Fluctuat. level (® ä 71) Display damping (® ä 71) Output damping 1 to 2 (®...
  • Page 137 Proline Promass F 200 HART Appendix Volume flow unit (® ä 77) Volume unit (® ä 77) Corrected volume flow unit (® ä 78) Corrected volume unit (® ä 78) Density unit (® ä 78) Reference density unit (® ä 78) Temperature unit (®...
  • Page 138 Appendix Proline Promass F 200 HART Medium (® ä 74) Gas type (® ä 74) Reference sound velocity (® ä 74) Temperature coefficient (® ä 74) sound velocity Partial filled pipe detection (® ä 74) Low value (® ä 74) High value (®...
  • Page 139 Proline Promass F 200 HART Appendix Header (® ä 82) Header text (® ä 82) Separator (® ä 82) Backlight (® ä 82) Conf. backup disp. ® (® ä 82) Operating time (0652) (® ä 83) Last backup (0102) (® ä 83) Configuration management (®...
  • Page 140 Appendix Proline Promass F 200 HART ® Measured values (® ä 89) Process variables ® (® ä 89) Mass flow (® ä 90) Volume flow (® ä 90) Corrected volume flow (® ä 90) Density (® ä 90) Reference density (®...
  • Page 141 Proline Promass F 200 HART Appendix Frequency simulation (® ä 85) Frequency value (® ä 85) Pulse simulation (® ä 85) Pulse value (® ä 85) Switch output simulation (® ä 85) Switch status (® ä 85) Simulation current output 2 (®...
  • Page 142 Appendix Proline Promass F 200 HART 100% bargraph value 3 (® ä 69) (0126) Decimal places 3 (0118) (® ä 82) Value 4 display (0109) (® ä 69) Decimal places 4 (0119) (® ä 82) Display interval (0096) (® ä 82) Display damping (0094) (®...
  • Page 143 Proline Promass F 200 HART Appendix Assign behavior of (® ä 104) diagnostic no. 831 (0716) Assign behavior of (® ä 104) diagnostic no. 832 (0675) Assign behavior of (® ä 104) diagnostic no. 833 (0676) Assign behavior of (® ä 104) diagnostic no.
  • Page 144 Appendix Proline Promass F 200 HART Totalizer overflow 1 to 3 (® ä 91) (0910) Output values ® (® ä 91) Output current 1 (0361) (® ä 91) Measured current 1 (0366) (® ä 91) Terminal voltage 1 (0662) (® ä 91) Output current 2 (0361) (®...
  • Page 145 Proline Promass F 200 HART Appendix Density offset (0571) Density factor (0572) ® Process param. (® ä 51) Flow damping (1801) (® ä 51) Density damping (1808) (® ä 51) Flow override (1839) (® ä 51) Temperature damping (® ä 51)
  • Page 146 Appendix Proline Promass F 200 HART ® Calculated value (® ä 89) Corrected volume flow ® (® ä 90) Corrected volume flow (® ä 90) (1812) Reference values ® Fixed reference density (® ä 58) (1814) Reference temperature (® ä 58)
  • Page 147 Proline Promass F 200 HART Appendix Calibration ® Calibration factor (2431) Zero point (2437) Nominal diameter (2807) C0 (2469) C1 (2574) C2 (2575) C3 (2576) C4 (2577) C5 (2578) Output ® Current output 1 to 2 ® (® ä 55) Assign current output (®...
  • Page 148 Appendix Proline Promass F 200 HART Pulse width (0452) (® ä 61) Measuring mode (0457) (® ä 71) Failure mode (0480) (® ä 61) Pulse output (0456) (® ä 92) Assign frequency output (® ä 63) (0478) Minimum frequency value (®...
  • Page 149 Proline Promass F 200 HART Appendix Communication ® HART output ® (® ä 49) Configuration ® (® ä 50) Burst mode (0208) (® ä 50) Burst command (0207) (® ä 50) HART address (0219) (® ä 50) No. of preambles (0217) (®...
  • Page 150 Appendix Proline Promass F 200 HART ® Totalizer 1 to 3 (® ä 79) Assign process variable (® ä 80) (0914) Unit (0915) (® ä 80) Totalizer operation mode (® ä 80) (0908) Control totalizer 1 (0912) (® ä 93) Preset value 1 (0913) (®...
  • Page 151 Proline Promass F 200 HART Appendix Logging interval (0856) (® ä 94) Clear logging data (0855) (® ä 94) Display channel 1-4 (® ä 95) ® Min/max values Reset min/max values (2504) Terminal voltage ® Minimum value (0689) Maximum value (0663)
  • Page 152 Appendix Proline Promass F 200 HART ® Signal asymmetry Minimum value (2551) Maximum value (2476) ® Simulation (® ä 84) Assign simulation process (® ä 84) variable (1810) Value process variable (® ä 84) (1811) Simulation current output 1 (® ä 85)
  • Page 153: Index

    Proline Promass F 200 HART Index Index Define access code ......86 Degree of protection ..... . . 29, 126...
  • Page 154 Index Proline Promass F 200 HART Electrical connection Hardware write protection ..... . 86 Commubox FXA195 ..... . . 45 HART protocol .
  • Page 155 Proline Promass F 200 HART Index Materials ....... . . 127 Operating keys Maximum measured error .
  • Page 156 Index Proline Promass F 200 HART Calculated ......117 Setting the operating language ....51 Measured .
  • Page 157 Proline Promass F 200 HART Index Write access ....... . 43 Write protection Technical data, overview .
  • Page 158 www.endress.com/worldwide BA01112D/06/EN/01.12 71187177 EH-COSIMA ProMoDo...

Table of Contents