and the reversing valve slides back to its normal heat
position.
Cooling
1. Thermostat calls for cooling.
2. When the thermostat call is for cooling, the
compressor and outdoor fan are energized .
3. The indoor blower will energize approximately 6
seconds later.
4. The unit delivers cooling to the conditioned space
until the thermostat is satisfied.
5. The compressor and outdoor fan will be de-energized
when the thermostat opens.
6. The indoor blower continues to run at low cool speed
for approximately 60 seconds after the thermostat
is satisfied. This allows additional cooling from the
indoor coil to be transferred to the conditioned space.
Then, the indoor blower is de-energized.
NOTE: A 180-second anti-short cycle is integral to
the control and prevents recycling of the compressor.
Cooling Operation
NOTE: Mechanical cooling cannot be reliably provided at
ambient temperatures below 50° F.
1. Turn on the electrical power supply to the unit.
2. Place the room thermostat selector switch in
the COOL position (or AUTO if available, and if
automatic changeover from cooling to heating is
desired).
3. Set the room thermostat to the desired temperature.
Fan Only
1. Thermostat calls for FAN ONLY by energizing "G".
2. The indoor blower is immediately energized at the
low heat speed.
3. The indoor blower is immediately de-energized once
thermostat call for FAN is removed.

Air flow Measurement and Adjustment

Please review the Duct Work section before proceeding
with the airflow measurements and adjustments in this
section.
Unit blower curves (see Specification Sheets) are based
on external static pressure (ESP per in/W.C.). The
duct openings on the unit are considered internal static
pressure. As long as ESP is maintained, the unit will deliver
the proper air up to the maximum static pressure listed for
the CFM required by the application (i.e. home, building,
etc.)
In general, 400 CFM per ton of cooling capacity is a rule
of thumb. Some applications depending on the sensible
and latent capacity requirements may need only 350 CFM
or up to 425 CFM per ton. Check condition space load
requirements (from load calculations) and equipment
expanded ratings data to match CFM and capacity.
After unit is set and duct work completed, verify the ESP
with a 1-inch inclined manometer with pilot tubes or a
Magnahelic gauge and confirm CFM to blower curves in the
Specification Sheets.
NOTE: Never run CFM below 350 CFM per ton, evaporator
freezing or poor unit performance is possible.
Air Flow Adjustments For Indoor Blower Motor
EEM Motor
Adjust the CFM by changing the 24V low voltage lead at
the speed terminal block on the motor. (T1, T2, T3, T4,
T5). See Blower Performance Data in the appendix for
airflow delivered at each speed tap.
NOTE: Factory set T1 (G, fan and low stage gas heat), T2
(high stage gas heat, T4 (nominal heat pump / cooling).
T3 is for optional low speed cooling and heat pump. T5 is
for optional high speed cooling and heat pump.

START-UP, ADJUSTMENTS, AND CHECKS

Heating Start-up ( Natural Gas / LP)
This unit is equipped with an electronic ignition device to
automatically light the main burners. It also has a power
vent blower to exhaust combustion products.
On new installations, or if a major component has been
replaced, the operation of the unit must be checked.
Check unit operation as outlined in the following
instructions. If any sparking, odors, or unusual sounds are
encountered, shut off electrical power and check for wiring
errors, or obstructions in or near the blower motors.
Rollout Protection Control
The rollout protection device opens, cutting power to the
gas valve, if the flames from the burners are not properly
drawn into the heat exchanger. The rollout protection
device is located on the burner bracket. The reason for
elevated temperatures at the control must be determined
and repaired prior to resetting this manual reset control.
Rollout Protection on Burner Bracket
14
Rollout Protection