AFDH drive program parameters used with all Trane controls

Important: Any AFDH drive module menu parameter numbers not listed in this manual are non-
Note: Please refer to the TR1-SVX10A-EN TR1™ Series Variable Frequency Drive Installation and
Table 18. Trane specific AFDH program parameters and settings
Parameter
(a)
Number
Parameter Name
007
Large Readout
008
Small Readout 1
009
Small Readout 2
010
Small Readout 3
012
Hand Start on LCP (Hand start button)
013
Off/Stop on LCP (Stop button)
101
Torque Characteristics
102
Motor Power
103
Motor Voltage
104
Motor Frequency
105
Motor Current
106
Rated Motor Speed
201
Output Frequency Low Limit
202
Output Frequency High Limit
204
Minimum Reference
205
Maximum Reference
206
Ramp-Up Time
207
Ramp-Down Time
215
Current Limit
304
Coast Inverse
308
Terminal 53 Analog Input Voltage
309
Terminal 53 Minimum Scaling
314
Terminal 60 Analog Input Current
323
Relay 1 Function
(a) Note: Highlighted parameter rows indicate values that must be programmed in the field. Non-highlighted parameter rows should have been factory
set to the recommended value to use - review these parameters and change to recommended value if necessary.
AFDH-SVN01A-EN
Trane specific program parameters. All non-Trane specific program parameter
values have been set by the manufacturer before shipment, to provide optimum
drive performance. Under no circumstances should any of the pre-set values in
these menu parameters be changed unless specifically directed to do so by a factory
engineer or a factory technical support person.
Operation manual for full program parameter details and descriptions, and the instructions
necessary to operate the Local Control Panel (LCP) and program the necessary drive
parameters.
Please refer to the table below for the Trane specific menu parameters that must be reviewed
and/or programmed into the AFDH drive module before doing the initial machine start-up.
0 (Automatic Energy Optimization)
Default Value
(Value Description)
4 (Frequency %)
1 (Reference %)
5 (Motor Current A)
7 (Power HP)
1 (Enable)
1 (Enable)
None - Read Motor Nameplate
None - Read Motor Nameplate
None - Read Motor Nameplate
None - Read Motor Nameplate
None - Read Motor Nameplate
0.0 (Hz)
60 (Hz)
0.0 (Hz)
60 (Hz)
None
None
None - Read Drive Nameplate
3 (Safety Interlock)
0 (No Operation)
0.0 (Volts)
0 (No Operation)
0 (No Alarm)
Installation
Recommended Value to Use
(Value Description)
3 (Frequency Hz)
5 (Motor Current)
6 (Power KW)
27 (Heat Sink Temp)
0 (Disable)
0 (Disable)
1 (Multiple Motors)
Enter Nameplate Motor CPKW
Enter Motor Voltage from Nameplate
60 (Hz)
Enter RLA from Motor Nameplate
Enter RPM from Motor Nameplate
38 (Hz)
60 (Hz)
Enter 38 (Hz)
60 (Hz)
10 (Seconds)
20 (Seconds)
Enter Maximum Rated Drive Amps
0 (Coasting Stop, Inverse)
1 (Reference)
2 (Volts)
0 (No Operation)
8 (Alarm)
57