Reprogramming factory installed AdaptiView controls (CTV firmware)

Important: Make sure your laptop is loaded with the most current version of Tracer TU tool
Note: CTV MP firmware is always used in factory installed AdaptiView control systems or in
Table 23. UC800/AdaptiView CTV parameter values with a retrofit AFDH
Tracer TU Service Setpoints View:
Adjustable Frequency Drive Setpoints
AF Control
ReOptimization Sensitivity
Tracer TU Field Startup View:
Adjustable Frequency Drive
Maximum Frequency
Minimum Frequency
AFD Surge Capacity Increase
Tracer TU Configuration View: Main
Unit Type (MODL)
Tracer TU Configuration View: UC800
Starter Type
Impeller Diameter (CPIM)
Tracer TU Configuration View: Starter
Stop Delay Time (Contactor Interrupt Failure)
Unit Voltage
Voltage Transformer Ratio
Rated Load Amps (RLA)
CT Meter Scale
Current Unbalance Trip Point
Current Unbalance Grace Period
Maximum Acceleration Setting
Acceleration Time Out Action
Overload Type
Phase Reversal
Contactor Integrity Test
Phase Reversal Grace Period
Surge Protection
Momentary Power Loss Protection
Restart Inhibit Stop to Start Time
Surge Sensitivity
Power Loss Reset Time
RTD Type
64
software so that you have the most up-to-date version of CTV MP firmware available
to install into the UC800.
AdaptiView display upgrades to factory installed CH530 control systems.
Range
Auto, Fixed
0 - 100%
Range
38 - 60 Hertz
38 - 60 Hertz
0 - 5%
Range
CVHE, CVHF, CVHG, CVGF
Range
Not Applicable
210 - 335
Range
1 - 30 Seconds
180 - 15000 Volts
0 - 700
0 - 2500 Amps
0 - 2000
15 - 100%
10 - 255 Seconds
6 - 64 Seconds
Shutdown, Transition
Exponential, Linear
Enable, Disable
Enable, Disable
20 - 1000 milliseconds
Enable, Disable
Enable, Disable
0 - 255 Seconds
0 - 100%
0 - 255 Seconds
75 Ohm@75F, 100 Ohm@ 0C
Default Setting
Auto
20
Default Setting
60
38
1
Default Setting
Enter Chiller Model from Unit Nameplate
CVHE
(Note: only CVHE or CVHF apply)
Default Setting
Unit Mount Wye-Delta
Remote Mount Non-Comm AFD
275
Enter CPIM from Unit Nameplate
Default Setting
3
460
20
500
Choose Correct CT Meter Scale from
0
30
90
6
Shutdown
Linear
Enable
Disable
700
Enable
Enable
30
20
15
75 ohm
Recommended Setting
Auto
20
Recommended Setting
60
38
1
Recommended Setting
Recommended Setting
Recommended Setting
30
Enter from Unit Nameplate
Enter from Unit Nameplate
Enter from Unit Nameplate
Table 21, p. 62
30
90
6
Shutdown
Linear
Disable
Disable
1000
Enable
Disable
60
20
15
75 ohm
AFDH-SVN01A-EN