Object and Diagnostic Data Points

For quick reference, the following tables are listed and sorted two different ways.
through
sorted by Object Name.
N N o o t t e e : : Not all points are available to the user. The available data points are defined and
Table 3. Analog inputs
Object Type
Object Name
Space Temperature Local
AI1
Space Relative Humidity
AI2
Local
Supply Fan Pressure Local
AI3
Circuit 1 Condenser Coil
AI4
Temperature Local
Circuit 2 Condenser Coil
AI5
Temperature Local
Return Air Temperature
AI6
Local
AI7
OAD Position Local
AI8
Zone CO
Local
2
Exhaust Fan Pressure
AI9
Local
AI10
Outdoor Air Flow Local
Discharge Air
AI11
Temperature Local
Return Duct/Space
AI12
Pressure Local
Exhaust Leaving
AI13
Temperature Local
Return Air Humidity Local
AI14
Evaporator Coil Leaving
AI15
Temperature Local
Space Occupancy
AI16
Request Override
ERV Supply Side Leaving
AI17
Temperature Local
Circuit 1 Liquid Line
AI18
Pressure Local
Circuit 2 Liquid Line
AI19
Pressure Local
Space Temperature
AI20
Setpoint Local
Outdoor Air Temperature
AI21
Local
Outdoor Air Relative
AI22
Humidity Local
AI23
Duct Static Pressure Local
Table 4. Analog outputs
Object Type
Object Name
AO1
HGRH Command
AO2
IVFD Command
BAS-SVP18D-EN
Table 9, p. 25
are listed by input/output type and sorted by object type.
dependent on the type of equipment and options.
Min /Max
-25 - 135 °F
0 - 100 %
0 - 25 in(H
O)
2
-50 to 200 °F
-50 to 200 °F
-25 to 135 °F
0 – 100 %
0 – 3000 ppm
0 - 25 in(H
O)
2
0 – 15000 cfm
-25 to 135 °F
0 - 2 in(H
O)
2
-25 to 135 °F
0 - 100%
-25 to 135 °F
-58 to 482
-58 to 482 °F
0 – 500 psi
0 – 500 psi
50 – 86 °F
-50 to 135 °F
0 - 100%
0 - 2 in(H
O)
2
Min / Max
0 – 100 %
0 - 100%
When the Point
Exists
Units with Space
Local space temperature sensor.
Temperature Sensor
Installed.
Units with Space
Local space relative humidity
Humidity Sensor
sensor.
Installed.
Units with Piezo Ring on
Local supply fan piezo ring
Supply Fan.
pressure.
Units with Head Pressure
Local condenser coil
Control or an Air Source
temperature sensor on circuit 1.
Heat Pump.
Units with Head Pressure
Local condenser coil
Control or an Air Source
temperature sensor on circuit 2.
Heat Pump.
Units with Modulating
Local return air temperature
Dampers.
sensor.
Units with Modulating
Local outside air damper
Dampers.
position.
Units with a CO
Sensor
2
Local Space CO
Installed.
Local exhaust fan piezo ring
Units with Piezo Ring on
pressure.
Exhaust Fan.
Units with Outside air
Local outside air flow.
flow Monitoring.
Local discharge air temperature
All Units.
sensor.
Units with Powered
Local return duct or space
Exhaust and Modulating
pressure sensor
Dampers.
Local exhaust leaving
Units with an ERV.
temperature sensor
Units with Modulating
Local return air humidity sensor.
Dampers.
Local evaporator leaving air
Units with Compressors.
temperature sensor.
Local input that overrides
Units with Thumbwheel
Occupancy Request.
Installed.
Units with an ERV and is a
Local temperature sensor
Water Source Heat
located post ERV on the supply
Pump.
air side.
Units with Head Pressure
Local refrigerant pressure
Control and is an Air
sensor on circuit 1.
Source Heat Pump.
Units with Head Pressure
Local refrigerant pressure
Control and is an Air
sensor on circuit 2.
Source Heat Pump.
Units with Thumbwheel
Local thumbwheel input.
Installed.
Local outside air temperature
All Units.
sensor.
Local outside air humidity
All Units.
sensor.
Local supply duct pressure
Unit with Multizone VAV.
sensor.
When the Point Exists
Units with Modulating Hot
Analog HGRH output
Gas Reheat.
command.
Analog supply fan VFD speed.
All Units.
Table 3, p. 19
Table 10, p. 26
Description
concentration
2
Description
is
19