Object And Diagnostic Data Points; Analog Inputs; Analog Outputs - Trane Tracer UC600 Installation Manual

For modular self contained
Table of Contents

Advertisement

Object and Diagnostic Data Points

For quick reference, the following tables are listed and sorted two different ways.
through
sorted by Object Name.
N N o o t t e e : : Not all points are available to the user. The available data points are defined and
Table 2. Analog Inputs
Object
Object Name
Identifi-
er
Space Temperature
AI1
Local
Duct Static Pressure
AI12
Local
Return Air
AI32
Temperature Local
Condenser Water
AI46
Entering Temperature
Condenser Water
AI47
Leaving Temperature
Condenser Tee
AI48
Strainer High Pressure
Condenser Tee
AI49
Strainer Low Pressure
Air Filter Differential
AI58
Pressure
Compressor 1
AI93
Discharge Pressure
Sensor
Compressor 1 Suction
AI94
Pressure Sensor
Compressor 1 Suction
AI95
Temperature
Compressor 2
AI96
Discharge Pressure
Sensor
Compressor 2 Suction
AI97
Pressure Sensor
Compressor 2 Suction
AI98
Temperature
Compressor 3
AI99
Discharge Pressure
Sensor
Compressor 3 Suction
AI100
Pressure Sensor
Compressor 3 Suction
AI101
Temperature
Compressor 4
AI102
Discharge Pressure
Sensor
Compressor 4 Suction
AI103
Pressure Sensor
Compressor 4 Suction
AI104
Temperature
Table 3. Analog Outputs
Object
Object Name
Identifi-
er
Compressor 1
AO81
Condenser Regulating
Valve
Compressor 2
AO82
Condenser Regulating
Valve
18
Table 8, p. 29
are listed by input/output type and sorted by object name.
dependent on the type of equipment and options.
Units of
Minimum
Measure
Maximum
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
Pressure
-0.25 to 5.2 in
in(H2O)
(H2O)
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
Pressure
-500 to 550 PSI
(PSI)
Pressure
-500 to 550 PSI
(PSI)
Pressure
-10 to 10 in
in(H2O)
(H2O)
Pressure
0 to 750 PSI
(PSI)
Pressure
0 to 750 PSI
(PSI)
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
Pressure
0 to 750 PSI
(PSI)
Pressure
0 to 750 PSI
(PSI)
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
Pressure
0 to 750 PSI
(PSI)
Pressure
0 to 750 PSI
(PSI)
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
Pressure
0 to 750 PSI
(PSI)
Pressure
0 to 750 PSI
(PSI)
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
Units of
Minimum
Measure
Maximum
0% to 100%
Percent
Open
0% to 100%
Percent
Open
When the Object
Exists
Units with Space
Local Space Temperature Sensor.
Temperature Option.
All Units
Local Duct Static Pressure Sensor.
Local Return Air Tempreature Sensor
All Units
Water Cooled
Local Condenser Water Entering
Condenser Units
Only
Water Cooled
Local condenser Water Leaving
Condenser Units
Only
Water Cooled
Local Condenser Tee Strainger High
Condenser Units
Only
Water Cooled
Local Condenser Tee Strainger Low
Condenser Units
Only
Local Air Filter Differentil Pressure
All Units
Units with at least 1
Local Compressor Refrigerant
Compressor
Discharge (High) Pressure Sensor
Units with at least 1
Local Compressor Refrigerant Suction
Compressor
(Low) Pressure Sensor
Units with at least 1
Local Compressor Refrigerant Suction
Compressor
(Low) Temperature Sensor
Units with at least 2
Local Compressor Refrigerant
Compressors
Discharge (High) Pressure Sensor
Units with at least 2
Local Compressor Refrigerant Suction
Compressors
(Low) Pressure Sensor
Units with at least 2
Local Compressor Refrigerant Suction
Compressors
(Low) Temperature Sensor
Units with at least 3
Local Compressor Refrigerant
Compressors
Discharge (High) Pressure Sensor
Units with at least 3
Local Compressor Refrigerant Suction
Compressors
(Low) Pressure Sensor
Units with at least 3
Local Compressor Refrigerant Suction
Compressors
(Low) Temperature Sensor
Units with at least 4
Local Compressor Refrigerant
Compressors
Discharge (High) Pressure Sensor
Units with at least 4
Local Compressor Refrigerant Suction
Compressors
(Low) Pressure Sensor
Units with at least 4
Local Compressor Refrigerant Suction
Compressors
(Low) Temperature Sensor
When the Object
Exists
Unit that Circuit 1
Analog Control that regulates water
has a Water
throught the water cooled condenser
Regulating Valve
installed
Unit that Circuit 2
Analog Control that regulates water
has a Water
throught the water cooled condenser
Regulating Valve
installed
Table 2, p. 18
Table 9, p. 32
Description
Temperature Sensor
Temperature Sensor
Pressure Sensor
Pressure Sensor
Sensor
Description
of the compressor
of the compressor
BAS-SVP042A-EN
is
Read/
Write
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read/
Write
Read Only
Read Only