A.1 Power Ratings
A.1 Power Ratings
u

Three-Phase 208 Vac Bypass Drive Models D002 to D030

Item
Bypass Model P1Bo
Maximum Applicable
Motor Capacity (HP)
Input Current Range (A)
Rated Voltage
Rated Frequency
Input
Allowable Voltage Fluctuation
Allowable Frequency
Fluctuation
Rated Output Current (A)
Overload Tolerance
Output
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency
(Hz)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance. Refer to the bypass data nameplate affixed to the inside of the enclosure door for actual input current.
<3> Carrier frequency is set to 2 kHz. Current derating is required to raise the carrier frequency.
u

Three-Phase 208 Vac Bypass Drive Models D046 to D211

Item
Bypass Model P1Bo
Maximum Applicable
Motor Capacity (HP)
Input Current Range (A)
Rated Voltage
Rated Frequency
Input
Allowable Voltage Fluctuation
Allowable Frequency
Fluctuation
Rated Output Current (A)
Overload Tolerance
Output
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency
(Hz)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance. Refer to the bypass data nameplate affixed to the inside of the enclosure door for actual input current.
<3> Carrier frequency is set to 2 kHz. Current derating is required to raise the carrier frequency.
240
Table A.1 Power Ratings (Three-Phase 208 Vac)
D002
D003
0.5
<1>
2.7
<2>
to 4.6
to 5.8
2.4
(Derating may be required for applications that start and stop frequently)
<3>
Table A.2 Power Ratings (Three-Phase 208 Vac)
D046
D059
15
<1>
56.1
<2>
to 57.8
to 70.6
46.2
(Derating may be required for applications that start and stop frequently)
<3>
Specification
D004
D007
0.75
1
2
3.9
5.6
8.3
to 7.5
to 10.2
Three-phase 208 Vac 50/60 Hz
-15 to 10%
3.5
4.6
7.5
ND Rating: 120% of rated output current for 60 s
User-adjustable between 2 and 15 kHz
Three-phase 208 Vac
400 Hz (user-set)
Specification
D074
D088
20
25
30
68.9
89.4
89.5
to 90.3
to 92.4
Three-phase 208 Vac 50/60 Hz
-15 to 10%
59.4
74.8
88.0
ND Rating: 120% of rated output current for 60 s
User-adjustable between 2 and 15 kHz
Three-phase 208 Vac
400 Hz (user-set)
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
D010
D016
3
5
12.3
17.7
to 14.2
to 19.6
±5%
10.6
16.7
D114
D143
40
50
113.1
140.2
to 116.0
to 142.4
to 167.6
±5%
114
143
User-adjustable between
D024
D030
7.5
10
29.8
40.0
to 31.5
to 41.7
24.2
30.8
D169
D211
60
75
165.4
201.4
to 203.6
169
211
2 and 10 kHz