A.1 Heavy Duty and Normal Duty Ratings
A.1

Heavy Duty and Normal Duty Ratings

The capacity of the drive is based on two types of load characteristics: Heavy Duty (HD) and
Normal Duty (ND).
Refer to Selecting the Appropriate Load Rating on page 210
HD and ND. Specifications for capacity ratings are listed on the following pages.
Setting
Parameter
Rated Output Current
C6-01
HD Rating
0: Heavy Duty
varies by model
ND Rating
1: Normal Duty
(default)
varies by model
<1>
The following pages list information on rating changes based on drive model.
• HD and ND: HD refers to applications requiring constant torque output,
TERMS
TERMS
while ND refers to applications with variable torque needs. The drive allows
the user to select HD or ND torque depending on the application. Fans,
pumps, and blowers should use ND (C6-01 = 1), and other applications
generally use HD (C6-01 = 0).
• Swing PWM: Swing PWM equivalent to a 2 kHz audible noise. This
function turns the motor noise into a less obtrusive white noise.
Note:
Differences between HD ratings and ND ratings for the drive include rated input and output current,
overload capacity, carrier frequency, and current limit. The default setting is for ND (C6-01 = 1).
210
YASKAWA ELECTRIC TOEP C710606 25D YASKAWA AC Drive J1000 Installation & Start-Up Manual
Table A.1 Selecting the Appropriate Load Rating
150% rated output current for 60 s
<1>
120% rated output current for 60 s
<1>
varies by model
for the differences between
Overload Tolerance
Default Carrier
Frequency
8/10 kHz
varies by model
2 kHz, Swing PWM