Vitoligno 300-C Installation/Service
Fault Display
(continued)
Fault codes
Fault code displayed
A6
AA
AB
AC
B4
BD
BE
C8
C9
E0
F9
FA
System characteristics
Burner blocked
Burner blocked
Burner blocked
Burner blocked
Control mode
Burner blocked
Burner blocked
Burner blocked
No fuel transport
Burner blocked
Burner blocked
Burner blocked
Cause
Ash box full or secondary
heating surface cleaning
blocked
Boiler had excess
temperature.
Water pressure is too low.
Water pressure is too high.
Fuel store empty
Maintenance cover/door
of fuel store open
Discharge transfer
contaminated
Changeover unit has not
reached position.
Vacuum module spends too
long in constant operation.
Jumpers are not inserted
in slots 97 and 98.
Grate did not reach limit
position.
Proximity switch in pellet
hopper is constantly
contaminated.
Troubleshooting
Measures
Emptying the ash box
Acknowledging a fault
If the fault recurs:
Check the mechanism for
secondary heating surface
cleaning and the ease of
operation of the
turbulators. See chapters
"Cleaning secondary
heating surfaces" and
"Cleaning the ash chamber
and ash removal parts".
Check set values in
control unit
Check pump
Check valves
Check sensors
Check low water cutoff
connections (see safety
equipment connections
on page 43)
Check jumper cable
connections (see auxiliary
safety equipment
connections page 43)
Check water pressure.
Check fuel store fill level.
Check jumper cable
connections (see system
limit switch page 49)
Clean proximity switch.
Test the changeover unit.
Check suction lines for
blockages and remove if
necessary.
Ensure there is sufficient
fuel in the fuel store.
Notify heating contractor.
Acknowledge a fault
If fault recurs, check grate
Clean grate if required
Clean proximity switch.
101