• For grounding, use a dedicated ground wire (2 mm
(third class grounding: 100 Ω or less grounding resistance).
• Do not share the Sensor controller's ground with other equipment or ground the Sensor con-
troller to the metal structure of a building. Doing so may worsen operation. Whenever possi-
ble, use an independent ground (with the ground pole separated by a minimum of 10 m from
any other ground pole).
• Ground to 100 Ω or less, and if possible use a separate ground from those of other devices.
(Refer to figure (a) in the diagram below.)
• If using an independent ground is not possible, then use a common ground as shown in fig-
ure (b). Connect to the ground pole of the other device.
Sensor Controller
Ground of
100 Ω or less
(a) Independent grounds:
Best
3
Insert the terminal block connector (male) to the terminal block connector (female) of Sensor
Controller.
4
Tightens and fix the left and right screws for the terminal block connector (male). (Recommend-
ed tightening torque: 0.7 to 0.8 N•m)
FH Series Vision System Hardware Setup Manual (Z366-E1)
Sensor Controller
Other
Other
device
device
(b) Common ground:
Acceptable
Grounding Methods
Terminal block connector (female)
Terminal block connector (male)
2
or larger) and apply Class D grounding
Sensor Controller
Other
device
(c) Common ground:
Incorrect
5 Setup and Wiring
5-7
5