6. Operation and Configuration of S3M UPS Models
and Battery Cabinets
Step 3: Setting Single Battery (Ah) Capability
Change the Single Battery (Ah) Capability to the individual Ah capacity for one individual battery as follows for the specific
battery cabinet models:
• BP240V09/BP240V09K: the Single Battery (Ah) Capacity is 9
• BP240V40/BP240V40L: the Single Battery (Ah) Capacity is 40
• BP240V65/BP240V65L: the Single Battery (Ah) Capacity is 65
• BP240V100/BP240100L: the Single Battery (Ah) Capacity is 100
The values can be 7~2000.
Scroll to the next display screen by pressing the down arrow.
Step 4: Setting Max Charge Current
Max Charge Current is the estimated charge current that the UPS will use to charge the batteries. Obtain the recommended
estimated Max Charge Current based on the specific S3M UPS and battery cabinet model combination from the chart in
Section 6.4.
Float and Boost Voltage: The UPS is factory-set for proper float (2.27V/cell, 13.62V/battery) and boost (2.35V/cell, 14.1V/
battery) voltages.
Cell float voltage: The float voltage value can be 2.23~2.30 V/cell. The default value is 2.27 V/cell.
Cell boost voltage: The battery equalized voltage value can be 2.30~2.40 V/cell. The default value is 2.35 V/cell.