Trane ComfortLink II XL 1040 Installation & User Manual page 20

Zone sensor
Table of Contents

Advertisement

Installation
Zone Assignment
Z o n e a n d A s s i g n e d S e n s o r s
D o w n s t . . .
S e n s o r N a m e
M o d e l / S e r i a l N o
C o m f o r t l i n k I I
1 0 5 0
1
O n b o a r d S e n s o r
W i r e l e s s
D o n e
S e n s o r
page 19
page 19
A v a i l a b l e S e n s o r s
U p s t a i r s G r e a t R o o m - 0 1
1 0 4 0
1   4 A # C D & ' - O n l i n e
W e i g h t
1 0 0 %
R e f r e s h
A s s i g n
Navigate to Indoor Sensor Setup on the 1050 control
from the Service Menu.
This is the Indoor Sensor Setup screen on the 1050
control. When setting up zoning it will ask you if you
have zone sensors to assign and take you to this menu.
When the 1040 is powered and wired into the zone
system you should see it in the list of available sensors.
Navigate to the selected zone on the top left, then
select the 1040 on the right column and select Assign.
Once assigned, the sensor will move over to the left
column and average with the other sensors assigned in
that zone. You can assign up to 4 sensors per zone.
NOTE: 1050 software version 5.7 or later is required.
Features may differ depending on software version.
TZON1040 Installation and User Guide

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tzon1040

Table of Contents