10.2 Configuration list and customer settings
Configuration list
There are separate two levels #1 and #2. Both levels contain the functions F01 to F13 with
the specified default settings and meanings.
The functions F01 to F13 have the following listed functions.
F = Function
F
Function
01 Control mode
02 Selecting the reference variable
(only effective when F01 - 1)
03 Direction of stem action
04 Delayed outdoor temperature
(only effective when F01 - 1 and
F02 - 0)
05 Potentiometer input
06 Resistance range of potentiometer
(only effective when F05 - 1)
07 Function of potentiometer (only ef-
fective when F02 - 0 and F05 - 1)
08 Function of binary input BI1 (only
effective when F05 - 0)
09 Function of switching output
10 Anti-block protection of pumps
(only effective when F09 - 0)
11 Return flow temperature sensor
12 Function of binary input BI2 (only
effective when F11 - 0)
EB 5757-7 EN
WE = Default setting
WE
1
0
0
0
0
0
0
0
0
1
1
0
0 = OFF, 1 = ON
Meaning
0 – Fixed set point control
1 – Control with reference variable
0 – Outdoor sensor
1 – Room sensor
0 – Increasing/increasing >>
1 – Increasing/decreasing <>
0 – Without delay
1 – With delay
0 – Not active (binary input)
1 – Active
0 – Type 5257-7 Room Panel (1000 to 1100 ohm)
1 – Remote adjuster (1000 to 2000 ohm)
0 – Heating characteristic level shift
1
Gradient shift
0
BI1 short-circuited: OFF with frost protection
1
BI1 short-circuited: Reduced operation
0 – BO as circulation pump control
1 – BO as heat demand (ON in rated operation)
0 – No anti-block protection
1 – When pumps are deactivated: switched on
every 24 h for 1 min
0 – Inactive, binary input 2 active
1 – Active, with return flow temperature limitation
0 – BI2 short-circuited: OFF with frost protection
1 – BI2 short-circuited: Reduced operation
Appendix
27