2.8 Function of switching output

NOTICE
!
The switching output function is available for electric actuators with firmware 2.x and higher.
The switching output can be configured as either a pump output (circulation pump for the
DHW circuit or heating circuit), a fault alarm output or an output to report when hot water is
tapped.
− Passive function:
− Function of the fault alarm:
− Function of the circulation pump
(DHW):
− Function of the circulation pump
(heating):
− Function of the tapping:
− Function of the circulation pump
(heating) reversed:
Functions
F16: Function of switching output
KH 5757 EN
The switching output is inactive.
The switching output is active when a fault has
occurred.
The switching output is active while hot water is
being tapped, when the function to maintain the hot
water at a constant temperature or the frost
protection function is active.
The switching output is active after a demand for
heat (valve position > 0 %).
The switching output is active while hot water is
being tapped.
The switching output is switched off when the
actuator stem reaches the top end position.
WE
Configuration
1
F16 - 1: Not active
F16 - 2: Fault alarm
F16 - 3: Circulation pump (DHW)
F16 - 4: Circulation pump (heating)
F16 - 5: Tapping
F16 - 6: Circulation pump (heating) reversed
Functions and parameters
11