6.3.2.

Fan Coil

First touch SETUP, then touch FAN COIL to set up the parameters for the fan coil
unit.
A14223
6.3.2.1.
Airflow
This option allows the installer to select the appropriate air flow based on the needs
of the installation. The QUIET airflow means the minimum cooling airflow that the
system can safely run (typically 300 CFM/ton). Use this setting if duct noise is a
severe problem. Note that duct sweating in high humidity environments could
become an issue at low airflows. The COMFORT airflow means airflow is varied
depending on humidity and temperature demand settings. This selection enables the
full dehumidify and comfort capabilities of the system. The EFF325 airflow is a
fixed airflow used to achieve specified ratings – no dehumidification airflow
reduction is performed. This is nominally 325 CFM/ton, but will vary if a 2- - stage
outdoor unit is used. The EFF350 airflow is a fixed airflow used to achieve
specified ratings – no dehumidification airflow reduction is performed. This is
nominally 350 CFM/ton, but will vary if a 2- - stage outdoor unit is used. The MAX
airflow is a fixed 400 CFM/ton. No dehumidification airflow reduction is
performed.