• Smart Recovery: On or Off. Default = On
NOTE: The "Temperature Units Display" set-up section has been moved
to the Homeowner Screens. See the Owner's Manual for more
information.

6.3.2. Fan Coil

First touch SETUP, then touch FAN COIL to set up the parameters for
the fan coil unit.

6.3.2.1. Airflow

This option allows the installer to select the appropriate air flow based on
the needs of the installation. The QUIET airflow means the minimum
cooling airflow that the system can safely run (typically 300 CFM/ton).
Use this setting if duct noise is a severe problem. Note that duct sweating
in high humidity environments could become an issue at low airflows.
The COMFORT airflow means airflow is varied depending on humidity
and temperature demand settings. This selection enables the full
dehumidify and comfort capabilities of the system. The EFF325 airflow
is a fixed airflow used to achieve specified ratings – no dehumidification
airflow reduction is performed. This is nominally 325 CFM/ton, but will
vary if a 2-stage outdoor unit is used. The EFF350 airflow is a fixed
airflow used to achieve specified ratings – no dehumidification airflow
reduction is performed. This is nominally 350 CFM/ton, but will vary if a
2-stage outdoor unit is used. The MAX airflow is a fixed 400 CFM/ton.
No dehumidification airflow reduction is performed.
NOTE: For Geothermal Heat Pumps, the airflow labels have been
changed from EFF325 and EFF350 to EFF1 and EFF2, respectively.
Nominal geothermal system airflows for these settings tend to be
different than the typical 325 and 350 CFM/ton values.
The dehumidify airflow, when set to NORMAL, is allowed to adjust to a
minimum to satisfy the dehumidification call. When set to HIGH, the
35