Bryant Evolution Connex Control Installation Instructions Manual page 19

Hide thumbs Also See for Evolution Connex Control:
Table of Contents

Advertisement

NOTE: ABCD bus wiring only requires a four- - wire connection; however, it is
good practice to run thermostat cable having more than four wires in the event of a
damaged or broken wire during installation.
Each communicating device in the Evolution Zone System has a four- - pin
connector labeled ABCD. It is recommended that the following color code be used
when wiring each device:
A — Green = Data A+
B — Yellow = Data B- -
C — White = 24VAC (Com)
D — Red = 24VAC (Hot)
A
B
C
D
A03193
It is not mandatory that the above color code be used, but each ABCD connector in
the system MUST be wired consistently.
NOTE: Some outdoor units, typically those with multiple compressor stages,
provide their own low- - voltage power source and do not require the "C" (24VAC
common) and "D" (24VAC power) connections. See the outdoor unit installation
instructions for more information.