START UP
Prior to Start-up Check List
• Is the case connected to its proper nameplate power supply?
• Is there power on at the breaker panel?
• Are the water hand valves open?
• Is the chiller on and circulating water through the condenser(s)?
• Are there any leaks from condenser water connections? Clamps may need to be tightened.
• Do evaporator fans rotate freely? Are they plugged in?
• Is the water strainer clear of debris?
Possible hazardous condition. Follow safety
procedures outlined by store safety management.
Starting up the case
• Ensure the chilled water flow is on, and connect the case to power.
The case(s) will start automatically within 4 minutes. The controller will be activated and the case
will begin to cool down.
NOTE: Compressor startups are staggered to prevent high electrical circuit demand.
Once the cases are running, listen for any unusual sounds or events. Examples include: evaporator
fan blade interference. Compressors should run continuously at startup. Use an amperage meter to
check the current to each compressor. Compressors are hermetic and very quiet.
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
START UP / OPERATION
Due to risk of ignition resulting from
incorrect parts or improper service,
only Hussmann authorized personnel
may service this equipment.
Component parts shall be replaced only
with exact manufacturer and model
number components. FAILURE TO USE
AUTHORIZED TECHNICIANS COULD
RESULT IN AN EXPLOSION, DEATH,
INJURY AND PROPERTY DAMAGE.
Showcases with R-290 Refrigerant
4-1