Use flue restrictor for vertically terminated fireplaces only.
Do not use for horizontally terminated fireplaces.
Figures 37 to 40 show the location and recommended opening
for the flue restrictor.
Installation of restrictor before venting is attached. See Figure 37.
NOTICE: When installing flue restrictor, install with screw pointing
downward.
For installation of the restrictor after the venting is installed,
remove (2) screws from each end of the flue baffle and set aside.
Insert the restrictor up into the flue collar and position it as shown
in Figures 38 and 39. Then, re-install the flue baffle.
41117-0-0819

VENTING FIREPLACE - TOP

WARNING
Figure 37
FLUE RESTRICTOR
REMOVE BAFFLE
TO INSTALL
FLUE RESTRICTOR
Figure 38
FLUE RESTRICTOR
REMOVE BAFFLE
TO INSTALL
FLUE RESTRICTOR
Figure 39
HARD ELBOW DIMENSIONS
FIREPLACE
SERIES
A1
DVLL60
54-3/4-in
FLEX PIPE 90 DEGREE BEND
FIREPLACE
SERIES
A2
DVLL60
54-3/4-in
MINIMUM HOLE LOCATION DIMENSIONS FOR THROUGH-
THE-WALL HORIZONTAL INSTALLATIONS WITH 90 DEGREE
ELBOW AND 12-in RISE OFF TOP OF FIREPLACE
SEE FIGURE 44 ON PAGE 27 FOR PERMISSIBLE
HORIZONTAL AND VERTICAL RUN DIMENSIONS.
Figure 40
B
C
5-3/8-in
7-5/8-in
10-5/8-in
B
C
5-3/5-in
7-5/8-in
10-5/8-in
Figure 41
D
D
Page 25