Empire Comfort Systems Boulevard MULTIFUNCTION REMOTE DVLL60BP90N-2 Installation Instructions Manual page 26

Direct vent zero clearance gas fireplace heater
Hide thumbs Also See for Boulevard MULTIFUNCTION REMOTE DVLL60BP90N-2:
Table of Contents

Advertisement

VENTING FIREPLACE - TOP (CONT'D)
Positioning the Fireplace
Determine the exact position of the fireplace so the direct-vent
termination will be centered (if possible) between two studs.
This will avoid any extra framing. All vent kit pipes should be
assembled on the fireplace after the fireplace is moved into the
final position.
Cutting the Hole
After the fireplace has been positioned in its permanent location,
the hole through the exterior wall can be cut. This hole must be
13-in (330mm) high x 10-5/8-in (270mm) wide with its center line
determined by the amount of vertical rise and horizontal run of
the termination. See Figures 42 and 43. When locating the hole
it must be noted that the bottom of the cap must be minimum of
12-in (305mm) above the ground level, and top of the cap must
be no less than 18-in (457mm) below a combustible projection,
and no closer than 9-in (229mm) to any wall running parallel to
vent termination.
U:\INSTRUCTIONS\Instructions Original Graphics\DVLL60BP\
DVLL Vent Cap Clearance - 061515
Page 26
Figure 42
Below Grade Installation
When it is not possible to meet the required vent termination
clearances of 12 inch (305 mm) above grade level, a snorkel
kit is recommended. It allows installation depth down to 7 inch
(178 mm) below grade level. The 7 inch (178 mm) is measured
from the center of the horizontal vent pipe as it penetrates
through the wall.
Ensure the sidewall venting clearances are observed. If
venting system is installed below ground, we recommend
a window well with adequate and proper drainage to be
installed around the termination area.
TYPICAL BASEMENT INSTALLATION
ATTENTION: Vinyl Soffit, Vinyl Ceiling, Vinyl Overhang
Disclaimer
Clearances are to heat resistant material (i.e. wood, metal).
This does not include vinyl. Empire Comfort Systems Inc.
will not be held responsible for heat damage caused from
terminating under vinyl overhangs, vinyl ceilings or vinyl
ventilated/unventilated soffits.
12" (30.5cm) ABOVE
GRADE OR AVERAGE
EXPECTED SNOW LEVEL
Figure 43
41117-0-0819

Advertisement

Table of Contents
loading

Table of Contents