TOP VENT - VERTICAL TERMINATION
No Elbows
DIMENSIONS (in inches)
MINIMUM
120 (10ft)
Two 90° Elbows
EXAMPLE VENT RUNS
INITIAL PIPE
A (Vertical)
LENGTH
(Dimensions in inches)
12
24
36
48
*Maximum horizontal run is 100% of vertical, but cannot exceed
20 feet.
41117-0-0819
MAXIMUM
480 (40ft)
Figure 49
B (Horizontal)
MINIMUM
MAXIMUM
120 (10ft)
222 (18ft, 6in)
120 (10ft)
222 (18ft, 6in)
120 (10ft)
222 (18ft, 6in)
120 (10ft)
222 (18ft, 6in)
Figure 50
Three 90° Elbows
NOTE: Subtract 3 feet from the total horizontal measurement for
each 90° elbow installed horizontally. Subtract 1-1/2 feet from
the total horizontal measurement for each 45° elbow installed
horizontally.
EXAMPLE VENT RUNS
INITIAL PIPE
A (Vertical)
LENGTH
(Dimensions in inches)
12
24
36
48
*Maximum horizontal run is 100% of vertical, but cannot exceed
17 feet.
B (Horizontal)
MINIMUM
MAXIMUM
120 (10ft)
186 (15ft, 6in)
120 (10ft)
186 (15ft, 6in)
120 (10ft)
186 (15ft, 6in)
120 (10ft)
186 (15ft, 6in)
Figure 51
Page 29