Venting Fireplace - Top - Empire Comfort Systems DVP FP3 4 Series Installation Instructions And Owner's Manual

Direct vent zero clearance gas fireplace heater
Table of Contents

Advertisement

To Use the Vent Graph
1. Determine the height of the center of the horizontal vent
pipe. Using this dimension on the Sidewall Vent Graph,
locate the point it intersects with the slanted graph line.
2. From the point of this intersection, draw a vertical line to
the bottom of the graph.
3. Select the indicated dimension, and position the unit in
accordance with same.
EXAMPLE A:
If the vertical dimension from the floor of the unit is 35 feet,
the horizontal run to the outer wall flange must not exceed
6.5 feet.
EXAMPLE B:
If the vertical dimension from the floor of the unit is 6.5 feet,
the horizontal run to the outer wall flange must not exceed
14.5 feet.
Special Note: For each 45 degree elbow installed in the
horizontal run, the length of the horizontal run MUST be
reduced by 18" (45cm). This does not apply if the 45 degree
elbows are installed on the vertical part of the vent system.
Reduce 3' for every 90° elbow.
Example: according to the chart the maximum horizontal
vent length is 20' and if two 45 degree elbows are required
in the horizontal vent it must be reduced to 17'.
The maximum number of 45 degree elbows permitted per
side wall installation is two. These elbows can be installed
in either the vertical or horizontal run.
NOTE: On vertical venting the first elbow does not get counted.
39359-0-1018

VENTING FIREPLACE - TOP

Venting Graph (Dimensions in Feet)
acceptable vertical and horizontal vent run.
(40' maximum vertical and 20' maximum horizontal)
Unacceptable vertical and horizontal vent run.
Figure 22
Page 17