Delta Electronics ASDA-AB Series User Manual page 218

Advanced ac servo drive for general purpose applications
Table of Contents

Advertisement

If P2-35 is set to 1000, and value B is set to 0, the position excessive error warning pulse is
1000 pulses.
If P2-35 is set to 1000, and value B is set to 1, the position excessive error warning pulse is
100,000 pulses.
P2 - 64
TLMOD Torque Limit Mixed Mode
Default: 0
Applicable Control Mode: PT, PR, S
Unit: N/A
Range: 0 ~ 3
Settings:
0: Disabled
1: Torque limit mixed mode (No polarity)
If |Tref|<PL, Tpl = |Tref|
If |Tref|>PL, Tpl = PL
If |Tref|<NL, Tnl = |Tref|
If |Tref|>NL, Tnl = NL
2: Torque limit mixed mode (Positive)
If 0<Tref<PL, Tpl = Tref
If Tref>PL, Tpl = PL
If Tref<0, Tpl,Tnl = 0
3: Torque limit mixed mode (Negative)
If Tref>0, Tpl,Tnl = 0
If -NL<Tref<0, Tnl = -Tref
If Tref<-NL, Tnl = NL
This parameter can allow the users to set two different kinds of torque limit command sources
when limiting torque. We call it is "Torque Limit Mixed Mode".
The torque limit function is activated by parameter P1-02 or via digital input TRQLM, TLLM or
TRLM.
If the users use TRQLM or P1-02 to activate torque limit function, the torque limit command
source can be analog input or internal parameters (P1-12 to P1-14) depending on which way
you use to activate torque limit function. At this time, the limit of PL and NL in the figure below
are specified as the torque limit that determined by the torque limit command source.
Revision November 2014
Chapter 7 Servo ParametersASDA-AB Series
Related Section: N/A
PL: Positive Limit
NL: Negative Limit
Tref: Torque Analog Input Voltage
Tpl: Actual PL value in "Torque Limit Mixed Mode"
Tnl: Actual NL value in "Torque Limit Mixed Mode"
Address: 0240H
7-59