installation requirements. The programming options for these supervisory trip outputs can be any
combination of the following:
Always Off: Disables all relay supervisory functions.
ACFC: Trips 2 hours (programmable for up to 24 hours) after loss of AC power. Restores 60 seconds
after AC power is restored.
LBC: Trips within 60 seconds on low battery condition. Restores when battery voltage  12.1 vdc.
LFC: Trips after 60 seconds on Telco line fault condition (delay is programmable). Restores 60
seconds after Telco line restores.
NSC: Trips after a 60 second delay (delay is programmable) on no service condition due to loss of
RF signal strength. Restores after RF signal strength is available.
RFC: Trips on radio failure to communicate with the TCC. Restores after 10 minutes.
Note: When the TG-PEM is used, it can be configured to use STC1. This TG-PEM configuration will limit
Telguard supervisory trip output options to STC2 only.
Optional Trip Input
When the input is tripped, a supervisory message is sent to the central station via the TCC. This allows an
external relay, separate from the alarm panel, to be connected to the Telguard unit in order to provide
independent sensor input for other functions, such as tamper detection.
The message that is sent from the TCC to the central station is configurable in Telguard Online. The TG-7
series unit will automatically be configured with a unit template that allows configuration of the trip input
feature, including the message that is sent to the central station. There is a default event configured for each
alarm format, so that if the unit is configured with the butt-set to send trip input events to the TCC, a default
notification will be sent to the central station. If the Telguard unit is configured to report restorals, the
contact closure will also be reported.
Swinger Function
The swinger function is designed to reduce the incidence of excessive messaging and alarms due to faulty
equipment or installation. If enabled, the swinger function will discontinue sending trip input messages to
the TCC once 10 trip events are detected within a 10-minute period. The Telguard device will resume
sending trip input messages to the TCC after a 10-minute period without trip events.

Step 2: Physically Install the TG-7 Series Device in Desired Location

Identify Location for Placing the TG-7 Series Device and Mount
Do not install the Telguard device in an area where the general public could reasonably be within 20cm (8
inches) of the antenna.
NOTE 1: Optimum RF performance can usually be found at the highest point within a building with the
fewest number of walls between the Telguard unit's antenna and the outside of the premises.
NOTE 2: To avoid interference with other electronic devices operating in the area, avoid mounting the
Telguard unit's antenna near other electronic devices.
NOTE 3: The Telguard unit's dipole antenna is designed for indoor installations only.
Care should be taken to ensure that a large metal object such as a refrigerator or a metal cabinet is not
located on the opposite side of the wall. If moving the Telguard unit to a different location is not practical,
you may need to get an extension cable and remote the antenna in order to receive adequate radio signal
strength. Choose a high, visually secure spot using the guidelines below.
Tips for Improved Radio Signal Reception
The higher the antenna the better. Start in the drop ceiling above the unit and proceed from there, up to
the roof if necessary.