ID2000 Series Operating Manual

4.9.1 Individual Device

To disable or enable an individual device:
1 From the Top Level display, press pushbutton '1'. The
DISABLE/ENABLEMENT menu is displayed:
DISABLE/ENABLEMENT: 0=Individual/
1=Entire Zone/2=Outputs:
2 Press the '0' pushbutton. If there are already some
devices disabled on the system, the panel displays
the prompt shown below:
Select only from devices ALREADY
DISABLED (
Answering
that are currently disabled.
3 The following is then displayed:
DISABLE/ENABLEMENT: Please select:-
0 = Sensor / 1 = Module:
Press the '0' or '1' pushbutton as required. Subsequent
steps are identical for both sensors and modules. The
following is displayed:
Choose from ZONE no. (0 = ALL)?n
Note: Step 3 is omitted if the answer to step 2 was
and all disabled devices are in the same zone.
4 Select a device using the same procedure as
described for the Control Output Test in
Section 4.8.2.1. When you have found the device you
want press
Note: If the device selected is in a zone which has
previously been disabled by means of a remote
switch, the system displays this warning message:
ZONE n already disabled by remote action:
to continue: Passcode?
Enter a passcode to override the remote switch
action (if you have already entered a passcode
for a previous operation you are simply asked to
confirm your action).
5 One of the prompts shown below is then displayed,
depending upon whether the device is currently
disabled or enabled. In either case, press
the current status: i.e. change from disabled to
enabled or from enabled to disabled.
DISABLE (
ENABLE (
25
/X)?
! ! ! ! !
enables you to quickly find the device(s)
.
! ! ! ! !
/X)?
/X)?
! ! ! ! !
997-434-000-4, Issue 4
to invert
May 2010