Fire detectors series IQ8Quad with integrated alarm device

Automatic point-type smoke detector with integrated alarm device and zone isolator for connection on the
esserbus
®
-PLus of the FlexES Control and IQ8Control fire alarm system. In case of an event, the alarm,
depending on the alarm device type, can be given via flash, sounder, and/or voice output.
The IQ8Quad smoke detectors with built-in alarm device incorporate up to 4 different functionalities.
fire detection as per EN 54-7
integrated heat sensor as per EN 54-5
optical alarm via flash lamp
acoustic alarm via sounder as per EN 54-3
acoustic alarm speech messages
Detection
The detection of the O²T multisensor detector is carried out via two integrated optical smoke detectors (except
Part No. 802382) with various scattered light angles and additional heat detector sensor evaluation to detect
smouldering fires through to open fires with an equivalent responsiveness. Smoke sensor signal identification to
ensure smoke classification and reduction of false alarms caused, for instance, by water vapor or dust. Each
detector is provided with an integrated isolator.
Alarm signaling
The alarm signaling device is activated from the control panel. No further short address needs to be allocated. It
is programmed with the service and programming software tools 8000.
Alarm tone / speech message programming
For detectors with speech message and/or alarm tone function with up to five language options, up to
4 signals can be programmed. Two signals are reserved for alarm signalling and evacuation in the case of fire.
Two further signals can be programmed for other events. Each signal can consist of up to four signal components,
enabling one signal to be programmed as a DIN tone combined with subsequent speech messages in three
different languages.
Alarm tones can be chosen from a table with various tone types. For application in schools, a break signal to
signify the breaks between class can be activated.
TI 798960.GB0 / 04.20