9-5. Protective Functions

WARNING : INJURY
 Do not open the check door when the starter switch is in the AUTO or START position.
It will cause injury by rotating parts such as cooling fans and fan belt.
 Always turn the starter switch to the STOP position and stop the engine, then close
and lock OPERATION PANEL DOOR before checking or maintaining the engine or
any equipment.
CAUTION : BURNS
 Do not touch the engine and surrounding components immediately after stopping the
engine as they are still extremely hot.
 Hot steam gushes out from the coolant sub-tank if the generator overheats. Do not
touch the coolant sub-tank.
This generator is equipped with functions to automatically stop operation when there is a
fault/malfunction during operation, and one to warn the operator of the fault location by use of
indicator lamps. Check the fault location when the engine is automatically stopped or an
indicator lamp illuminates to stop the engine.
Protection Feature List
No.
Abnormality
High Water
1
Temperature
Low Oil
2
Pressure
Insufficient
3
Battery Charge
Engine
4
Overspeed
5
Air Filter Clogging Up
Spill Containment
6
Fluid Level
Check
Spill Containment
7
Fluid Overflow
Engine Malfunction
8
DEF Empty
SCR system error
9
and DEF quality
abnormality
10
Overload
*  indicates the automatic activation.
Engine
Action
Breaker
Automatic
Trip
Shutdown
()
Warning
Lamp
Flash
Activates due to high water temperature in
the engine
Default : 212°F (100°C)
Activate due to low oil pressure in the engine
Default 7 psi (0.48 x 100 kPa)
Activates in battery charge Impossible
Engine speed is too fast
(2,070 rpm or more)
The element is clogged making it necessary
to clean or replace the element.
Spill containment accumulated fluid has
exceeded the specified level making it
necessary to flush the fluid.
Spill containment accumulated fluid has
exceeded the specified level making it near
the fill.
Some other engine fault occurs during
operation
DEF remaining amount 0%
An abnormality occurs in the SCR system
during operation
If anything other than DEF is added or the
DEF is diluted with water or other liquids
Activates in overload
42