Checking The Fan Belt - Shindaiwa DGK125F Owner's And Operator's Manual

Diesel engine generator
Table of Contents

Advertisement

 Change the LLC every 1,000 hours or every year.
 LLC is a toxic substance. Wear rubber gloves and other protective wear when handling.
 If someone mistakenly ingests LLC, induce vomiting immediately and seek medical care.
 If LLC gets on skin or clothing, wash with water immediately.
 LLC is flammable. Store in a location where flame is prohibited and it cannot be accessed by
children.
 Engine coolant could leak if the radiator is not completely tightened or there is a gap in the
seating face. Always be sure to securely tighten the radiator cap.
 Do not add engine coolant past the FULL level line of the coolant sub-tank.
(3) Coolant Capacity

8-3. Checking the Fan Belt

(1) Fan Belt Tension
Press the middle of the fan belt with a force of approx.98N
and check whether the amount of deflection is within the
range of standard values.
Standard value
[amount of deflection]
0.2 - 0.3 in
(2) Fan Belt Condition
Check the fan belt for damage and replace if any damage
or other fault is found.
(3) Fan Belt Adjustment
Remove the fan guard.
1
Loosen the Lock nut and Mounting Bolt of the
2
alternator.
Turn the Adjusting bolt until the belt tension falls
3
within the standard value range.
Securely tighten the Lock nut and Mounting Bolt
4
of the alternator to the specified torque.
Attach the fan guard.
5
Lock Nut tightening torque
76 N・m
Mounting Bolt tightening torque
127 N・m
(4) Replacing the Fan Belt
Request the authorized distributor where the generator
was purchased to replace the fan belt.
< Note >
 Use of a loose or damaged fan belt could result in overheating or insufficient charging.
 Do not operate the generator if fan guard has been removed.
Total Coolant Capacity
8.2 gal.
Value in parenthesis is the sub-tank capacity.
Adjusting Bolt
Alternator
33
98N
Bolt
Fan Guard
Bolt
Lock Nut
Mounting Bolt