TROUBLESHOOTING ERROR CODES

Logic 3.0 operators incorporate a self diagnostic feature built into
the MAS LED. In addition to indicating when routing maintenance
is due, the MAS LED can be used to troubleshoot some problems
with the operator.
If the MAS LED is flashing on and off rapidly, the Maintenance
Alert System has been triggered and the schedule operator
service is due. If the MAS LED flashes 2 or more pulses in a row
ERROR
CODE
DESCRIPTION
E1
MAS triggered (cycles or
months).
E2
No RPM input during
opening or closing.
E3
(MRT) Maximum Run
Time timed out.
E4
Obstruction sensed on
closing.
E5
Stuck key button pressed
for greater than 2 minutes.
E6
Rotary dial in invalid
position for greater than
30 seconds.
E7
Failsafe Safety device
faulted or not connected
for greater than 2 minutes.
E8
Brownout Detected.
E9
Motor movement at invalid
time.
NOTES: Error codes take priority over normal MAS LED operation. Error codes will repeat on the MAS every 1.5 seconds until cleared.
There may be more than one error present, but only the highest priority will flash. If the highest error is cleared, the next highest will
flash. All errors self-correct when the corrective action is taken and a reset is not needed.
followed by a pause, an operator error has occurred. To view how
many errors currently exist, turn the selector dial to DIAGNOSTIC
and press the OPEN button. To read out each individual error
code (if more than one exists) press CLOSE. It is possible to have
more than one error at a time.
The chart below can assist with identifying the flashes on the
MAS LED.
EFFECT
None normal operation.
The door only responds to
constant pressure commands.
The door stops before
reaching the desired time.
Operator will be in the OPEN
position.
Stuck key on 3-button station
will not respond.
The door will not respond to
the 3-button station or any
other input.
Normal operation (5 second
constant pressure override
required to close).
Operator will run as long as
enough power is present.
Operator will continue to
function normally for 5
operations and then default to
a constant pressure mode.
28
DISPLAY
1 blink
Reset MAS.
2 blinks
Clutch is slipping, adjust clutch, or
verify RPM sensor connection or
replace RPM sensor. NOTE: To relearn
the RPM sensor, move the door with a
constant pressure command. The door
will stop once relearned and normal
operation will resume.
3 blinks
First check Operator for any faults (i.e.,
Bad Limit switch), manually learn Max
Run Timer (page 23)
OR reset factory defaults (page 24).
4 blinks
Cleared by removing obstruction or
realigning photo eyes and giving a close
command.
5 blinks
Stuck key must be unstuck before it will
be recognized as an input.
6 blinks
Rotary dial must be set to a valid
position.
7 blinks
Cleared when safety device is cleared or
connected.
8 blinks
1. Check AC line for voltage.
2. Check transformer secondary for low
voltage. To many accessories may be
connected to the transformer.
Flash on start
Check relays and the drive circuitry to
of movement
insure that they are turning off. Operator
must run correctly for two starts for the
error to be cleared.
CORRECTION