Evaporator Screen - York YD Mod D Operation Manual

Table of Contents

Advertisement

Evaporator screen

Figure 7: Evaporator screen
This screen displays a cutaway view of the chiller evaporator. All setpoints relating to the
evaporator side of the chiller are maintained on this screen. Animation of the evaporation process
indicates whether the chiller is presently in a RUN condition. Animation of the liquid flow indicates
chilled liquid flow.
Table 7: Display only fields
Field/LED name
Leaving chilled liquid temperature
Entering chilled liquid temperature
Evaporator small temp difference
Evaporator pressure
Evaporator saturation temperature
Evaporator refrigerant temperature Displays the temperature of the refrigerant in the evaporator, if the sensor is present.
Chilled liquid flow switch (open /
closed)
Chilled liquid pump
Leaving chilled liquid temperature setpoints:
Setpoint
Shutdown
Restart
34
Description
Displays the temperature of the liquid as it leaves the evaporator.
Displays the temperature of the liquid as it enters the evaporator.
Displays the difference between the Leaving Chilled Liquid temperature and the
Evaporator Refrigerant temperature. The Evaporator Refrigerant temperature is
measured by the Refrigerant Temperature sensor input if the sensor is present,
otherwise it is calculated from the Evaporator Saturation temperature.
Displays the present refrigerant pressure in the evaporator.
Displays the present saturation temperature in the evaporator.
Displays whether the liquid flow is present in the evaporator.
Displays the command presently sent by the control center to the Chilled Liquid Pump
(RUN or STOP).
Displays the present setpoint to which the chiller is operating, whether controlled
locally or remotely.
Displays the Leaving Chilled Liquid Temperature at which the chiller will shut down to
avoid overcooling the building. By default this value is 4°F below the Leaving Chilled
Liquid Setpoint, but is adjustable.
Displays the Leaving Chilled Liquid Temperature at which the chiller will restart after
it has shutdown due to over-cooling temperature. By default, the chiller will restart at
the Leaving Chilled Liquid Temperature Setpoint, but is adjustable.
Model YD Mod D with OptiView Control Center