(2) Input signals (inverter → → → → master module)
The input signals from the inverter to the master unit are indicated.
(Output signals from inverter)
Device No.
RX0
Forward running
RX1
Reverse running
RX2
Running (RUN)
RX3
Up to frequency (SU)
RX4
Overload (OL)
RX5
Unused
RX6
Frequency detection (FU)
RX7
Normal (A, B, C)
RX8
RX9
Unused
RXA
RXB
RXC
Monitoring
Frequency setting command
RXD
(RAM)
Frequency setting command
RXE
2
(E
PROM)
Instruction code execution
RXF
completion
RX10
RX11
RX12
RX13
RX14
Reserved
RX15
RX16
RX17
RX18
RX19
RX1A
Error status flag
Remote station ready
RX1B
(Note 2)
Note:
1.
Using Pr. 190 to Pr. 192 (output terminal function selection), you can set the output signals of device No.s
RX2, RX6, RX7.
For details, refer to page 132.
2.
Since operation differs with the condition setting switch (SW4) position of the master unit, use SW4 in the
OFF position. If you use SW4 in the ON position, the remote station ready signal remains ON if a
communication error occurs.
Signal
OFF : Other than forward running (during stop or reverse rotation)
ON
OFF : Other than reverse running (during stop or forward rotation)
ON
On while the inverter is running. (Note 1)
Switched on when the output frequency reaches the set frequency ±
Pr. 41.
Switched on when stall prevention operation is performed, switched
off when stall prevention is canceled.
Reserved for the system.
Switched on when the output frequency reaches set frequency.
(Note 1)
Switched on when the inverter's protective function is activated to
stop the output. (Note 1)
Reserved for the system.
Switched on when the monitored value is set to RWr
command (RYC) switching on. Switched off when the monitor
command (RYC) is switched off.
Switched on when the set frequency is written to the inverter by the
frequency setting command (RYD) switching on. Switched off when
the frequency setting command (RYD) is switched off.
Switched on when the set frequency is written to the inverter by the
frequency setting command (RYE) switching on. Switched off when
the frequency setting command (RYE) is switched off.
Switched on on-completion of the processing corresponding to the
instruction code (RW
execution request (RYF) switches on. Switched off when the
instruction code execution completion (RXF) is switched off.
Reserved for the system.
Switched on when an inverter error occurs (protective function is
activated).
Switched on when the inverter goes into the ready status on
completion of initial setting after power-on or hardware reset.
(Used as an interlock for read/write from/to the master station.)
Switched off when an inverter error occurs (protectiove function is
activated).
Description
: Forward running
: Reverse running
) which is executed when the instruction code
W2
55
by the monitor
0