<Setting>
To make communication between the personal computer and inverter, the
communication specifications must be set to the inverter initially. If initial setting is not
made or there is a setting fault, data transfer cannot be made.
Note: After making the initial setting of the parameters, always reset the inverter. After
you have changed the communication-related parameters, communication
cannot be made if the inverter is not reset.
Parameter
Name
Number
Station
117
number
Communica-
118
tion speed
Stop bit
119
length/data
length
Parity check
120
presence/
absence
Number of
121
communication
retries
Communica-
122
tion check
time interval
Waiting time
123
setting
CR, LF
instruction
124
presence/
absence
Setting
Station number specified for communication from the
PU connector.
0 to 31
Set the inverter station numbers when two or more
inverters are connected to one personal computer.
48
4800 baud
96
9600 baud
192
19200 baud
8 data
0
Stop bit length 1 bit
bits
1
Stop bit length 2 bits
10 Stop bit length 1 bit
7 bits
11 Stop bit length 2 bits
0
Absent
1
Odd parity present
2
Even parity present
Set the permissible number of retries at occurrence
of a data receive error.
0 to 10
If the number of consecutive errors exceeds the
permissible value, the inverter will come to an alarm stop.
If a communication error occurs, the inverter will not
come to an alarm stop. At this time, the inverter can
be coasted to a stop by MRS or RES input.
9999
During an error, the light fault signal (LF) is given to
(65535)
the open collector output. Allocate the used terminal
with any of Pr. 190 to Pr. 192 (Output (remote input)
function selection).
0
No communication
Set the communication check time [seconds]
interval.
0.1 to 999.8
If a no-communication state persists for longer than
the permissible time, the inverter will come to an
alarm stop.
9999
Communication check suspension
Set the waiting time between data transmission to
0 to 150
the inverter and response.
9999
Set with communication data.
0
Without CR/LF
1
With CR
2
With CR/LF
115
PARAMETERS
Description
4