(3) Pr. 502 "error-time stop mode selection"
You can choose inverter operation to be performed if a communication line fault or CC-
Link microcomputer fault occurs.
Parameter
Setting Range
Number
502
(About the settings)
At Occurrence of Fault
Pr. 502
Fault
Setting Operating
status
0
Continued
1
Continued
2
Continued
Coasting
0
to stop
Decele-
1
ration to
stop
Decele-
2
ration to
stop
Note: 1. A communication error [E.OPT (fault data: A0
line, and a communication error [E.3 (fault data: F3
inside the inverter.
2. The alarm output is the ABC contact output or alarm bit output.
3. If the Pr. 502 setting is 1 or 2, the deceleration time is the ordinary
deceleration time setting (Pr. 8, Pr. 44, Pr. 45).
4. The acceleration time at restart is the ordinary acceleration time setting (Pr. 7,
Pr. 44).
5. If the Pr. 502 setting is 2, the operation command/speed command at restart
follows the command before occurrence of a fault.
6. For the setting of alarm output, the fault definition is stored in the alarm history.
(Write to the alarm history is performed when the alarm output is provided.)
If the alarm output is not provided, the fault definition overwrites the alarm
indication of the alarm history temporarily but is not stored.
After the fault is cleared, the alarm indication is reset and returns to the
ordinary monitor and the alarm history returns to the original alarm history.
7. When a communication line fault, which occurred at the Pr. 502 setting of 2, is
cleared during deceleration, acceleration restarts at that point. (Acceleration
does not restart at occurrence of a CC-Link microcomputer fault.)
Minimum Setting
Increment
0, 1, 2
Indi-
Alarm
Operating
cation
output
status
Not
Coasting
No
provided
to stop
Decele-
Not
No
ration to
provided
stop
Decele-
Not
No
ration to
provided
stop
Coasting
E.3 lit
Provided
to stop
Provided
E.3 lit
Decele-
after
after
ration to
stop
stop
stop
Provided
E.3 lit
Decele-
after
after
ration to
stop
stop
stop
Factory Setting
1
Error Recognition after
Pr. 500 Time
Indi-
Alarm
cation
output
E.OPT lit
Provided
E.OPT lit
Provided
after
after
stop
stop
E.OPT lit
Not
after
provided
stop
E.3 lit
Provided
E.3 lit
Provided
after
after
stop
stop
E.3 lit
Provided
after
after
stop
stop
)] is a fault on the communication
H
)] is a communication error
H
139
PARAMETERS
0
At Resolution of Fault
Operating
Indi-
Alarm
status
cation
output
Stop
E.OPT
Provided
held
kept lit
Stop
E.OPT
Provided
held
kept lit
E.OPT
Not
Restart
kept lit
provided
Stop
E.3 kept
Provided
held
lit
Stop
E.3 kept
Provided
held
lit
Stop
E.3 kept
Provided
held
lit
4