7) Note the cooling method when the inverter is installed in an enclosure.
When two or more inverters are installed or a ventilation fan is mounted in an
enclosure, the inverters and ventilation fan must be installed in proper positions with
extreme care taken to keep the ambient temperatures of the inverters with the
permissible values. If they are installed in improper positions, the ambient
temperatures of the inverters will rise and ventilation effect will be reduced.
8) Install the inverter on an installation surface securely and vertically with screws or
bolts.
3) Note on ambient
temperatures
Measurement
position
5cm
FR-E500
5cm
5cm
Measurement position
7) For installation in an enclosure
Ventilation
fan
Inverter
(Correct example)
Position of Ventilation Fan
8) Vertical mounting
4) Clearances around the inverter
1cm or
more*
*5cm or more for 5.5K and 7.5K
These clearances are also necessary for changing the cooling fan.
Inverter
Inverter
Built-in cooling fan
(Incorrect example)
(Correct example)
INSTALLATION AND WIRING
10cm
Leave sufficient
or more
clearances above
and under the
inverter to ensure
adequate ventilation.
1cm or
FR-E500
more*
10cm
or more
Inverter
When more than one inverter is contained
11
Cooling air
Cooling fan
built in the
inverter
Inverter
Inverter
(Incorrect example)
2