  • Page 1 Products Solutions Services BA01961F/00/EN/01.22-00 71566680 2022-04-04 Operating Instructions Prosonic M FMU40 HART Ultrasonic measuring technology...
  • Page 2 Prosonic M FMU40 HART Order code: XXXXX-XXXXXX Ser. no.: XXXXXXXXXXXX Ext. ord. cd.: XXX.XXXX.XX Serial number www.endress.com/deviceviewer Endress+Hauser Operations App A0023555 Endress+Hauser...
  • Page 3: Table Of Contents

    Manufacturer address ....8 12.2 Endress+Hauser services ....41 Storage and transport .
  • Page 4: About This Document

    Minimum value for the temperature resistance of the connection cables 1.2.3 Symbols for certain types of information   Permitted Procedures, processes or actions that are permitted.  Forbidden Procedures, processes or actions that are forbidden. Indicates additional information.  Reference to documentation  Series of steps  Result of an individual step Endress+Hauser...
  • Page 5: Supplementary Documentation

    For an overview of the scope of the associated Technical Documentation, refer to the following: • W@M Device Viewer (www.endress.com/deviceviewer): Enter serial number from nameplate • Endress+Hauser Operations app: Enter serial number from nameplate. 1.3.1 Standard documentation Technical Information (TI) Planning aid ‒...
  • Page 6: Basic Safety Instructions

    The device meets the legal requirements of the applicable EU Directives. These are listed in the corresponding EU Declaration of Conformity along with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. Endress+Hauser...
  • Page 7: It Security

    The device meets the legal requirements of the applicable EAC Directives. These are listed in the corresponding EAC Declaration of Conformity along with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the EAC mark. IT security We only provide a warranty if the device is installed and used as described in the Operating Instructions.
  • Page 8: Incoming Acceptance And Product

    ‣ Enter the serial number from the nameplate in the Endress+Hauser Operations app or scan the 2-D matrix code on the nameplate with the camera  All of the information on the measuring device and on the scope of the technical documentation pertaining to the device is displayed.
  • Page 9: Storage And Transport

    Avoid measurements through the filling curtain Do not install point level switches or temperature sensors within the beam angle Symmetrical internal fixtures, e.g. heating coils and baffles, negatively impact the measurement Align the sensor so that it is perpendicular to the product surface Endress+Hauser...
  • Page 10 Strong interference echoes can occur in narrow shafts and in uneven conditions. ‣ Use an ultrasound guide pipe with a minimum diameter of 100 mm (3.94 in), e.g. PE or PVC wastewater pipe Avoid the accumulation of dirt in the pipe. ‣ Clean the pipe regularly. Endress+Hauser...
  • Page 11 1 x b A0038222  7 Khafagi-Venturi flume (example) Khafagi-Venturi flume Upstream side Downstream side BD Blocking distance of the sensor Empty calibration (enter during commissioning) Maximum upstream level Flow Width of Khafagi-Venturi flume Endress+Hauser...
  • Page 12 Mounting Prosonic M FMU40 HART ≥3 H ≥ 2 H A0038223  8 Triangular weir (example) BD Blocking distance of the sensor Empty calibration (enter during commissioning) Full calibration Maximum upstream level Endress+Hauser...
  • Page 13 With screw-in flange 5.1.6 Mounting the device NOTICE The device can be damaged. ‣ Tighten the device at the threaded boss only, with maximum 20 Nm (14.75 lbf ft). A0020386  10 Mounting at threaded boss, width across flats AF60 Endress+Hauser...
  • Page 14: Measuring Range

    If the level enters the safety distance SD, the device generates a warning or alarm. ‣ The measuring span F may not project into the blocking distance BD. Level echoes within the blocking distance cannot be evaluated due to the transient response of the sensor. Endress+Hauser...
  • Page 15 • DN50/2": 80 mm (3.15 in) • DN80/3": 240 mm (9.45 in) • DN100/4": 300 mm (11.8 in) • DN150/6": 400 mm (15.7 in) • DN200/8": 400 mm (15.7 in) • DN250/10": 400 mm (15.7 in) • DN300/12": 400 mm (15.7 in) Endress+Hauser...
  • Page 16: Post-Mounting Check

    Connect the potential equalization line to the outer ground terminal before applying the supply voltage. ‣ When connecting to the public mains, install a mains switch for the device such that it is within easy reach of the device. Mark the switch as a disconnector for the device (IEC/EN61010). Endress+Hauser...
  • Page 17: Connecting The Measuring Device

    7 → 8 → A0038254 A0038706 A0047499 ‣ ‣ Connect the cable shield to the Tighten the cable gland ground terminal in the connection compartment 10. Close the connection compartment. 11. Switch on the power supply. Endress+Hauser...
  • Page 18: Terminal Assignment

    Terminal assignment for two-wire version Supply voltage Test terminal to test the signal current PAL (potential equalization) 4-20 mA HART ‣ Connect the connecting line to the screw terminals in the connection compartment (conductor cross-section 0.5 to 2.5 mm , 20 to 14 AWG) Endress+Hauser...
  • Page 19: Supply Voltage

    ‣ Use a short potential equalization line for optimum electromagnetic compatibility. ‣ Minimum line cross-section 2.5 mm (14 AWG). Use a ground strap if interference can be expected due to the installation conditions (existing interfering installations). Endress+Hauser...
  • Page 20: Post-Connection Check

    Overview of operation options • Local operation • HART communication • FieldCare operating program • Handheld terminal Structure and function of the operating menu 7.2.1 Function codes Within the function menus, a position is shown on the display for each function. Endress+Hauser...
  • Page 21: Access To The Operating Menu Via The Local Display

    Each completely filled bar represents 10% of the set span. A0047444  17 Group selection Picklist of function groups, e.g. basic setup, safety settings, temperature A0047445  18 Function with free parameter Label, e.g. empty calibration Help text Position in menu, e.g. 005 Endress+Hauser...
  • Page 22 Lock or unlock the hardware. After a hardware lock, it is not possible to operate the device via the display or communication! The hardware can only be unlocked via the display. An access code must be entered to do so. Endress+Hauser...
  • Page 23: Access To The Operating Menu Via The Operating Tool

    The device can be configured and measured values can be viewed using a HART protocol. Two operation options are available: • Field Xpert handheld terminal • FieldCare operating program on PC If operation is locked using the local display, parameter entry via communication is not possible. Endress+Hauser...
  • Page 24: Locking Or Enabling Parameter Configuration

    Operating Instructions BA00060S/04. 8.1.2 Operation with FieldCare FieldCare is an Endress+Hauser asset management tool based on FDT technology. FieldCare configures all Endress+Hauser devices and devices from other manufacturers that support the FDT standard. Hardware and software requirements: www.de.endress.com - Search: FieldCare FieldCare supports the following functions: •...
  • Page 25 • Click the parameter names and call up exact explanations via the help pages Signal analysis with envelope curve The "Envelope curve" view offers convenient ways to analyze the envelope curve:  22 Signal analysis with envelope curve, view in the FieldCare operating program Endress+Hauser...
  • Page 26: Commissioning

     If supply voltage is present, is the device operational and does a screen appear? Switching on the measuring device After the supply voltage has been switched on, the device is first initialized. Then the following information appears for approximately five seconds: • Device type • Software version Endress+Hauser...
  • Page 27: Connecting Via Fieldcare

    Basic setup procedure (example) Function and selection • Tank shape → Dome ceiling • Medium property→ Unknown • Process cond.→ Standard • Empty calibr. • Full calibr. • Mapping Optional functions • Safety settings • Linearization • Extended calibration • ... Endress+Hauser...
  • Page 28 Medium properties function (003) Selection • Unknown (e.g. pasty media such as greases, creams, gels etc.) • Liquid • Bulk solids, grain size < 4 mm, powder • Bulk solids, grain size > 4 mm, coarse Process cond. function (004) Selection Endress+Hauser...
  • Page 29 • Small values are set for the filters → Fast response time → Possibly unstable measured value • Standard solid • For bulk solids applications that do not suit any of the options • Average filter values and output damping Endress+Hauser...
  • Page 30 The blocking distance (BD) of the sensor is displayed. After the basic setup, enter the safety distance (SD) in the Safety distance (015) function When entering the full distance, make sure that the maximum level does not enter the blocking distance. Endress+Hauser...
  • Page 31 Process cond. (004)and in the function group Basic setup (00) → Empty calibration (005) • Dist. unknown → the actual distance is not known Two functions that follow are then skipped. • Manual → you can specify the mapping range yourself in the following function Endress+Hauser...
  • Page 32: Displaying The Envelope Curve

    • Envelope curve • Envelope curve and FAC • Envelope curve and mapping For information on the FAC and mapping, see the documentation BA "Description of Device Functions". 9.5.2 Recording curve (0E2) function Selection • Single curve • Cyclic Endress+Hauser...
  • Page 33 Active navigation mode: symbol in the top left-hand corner of the display Horizontal zoom mode • Zoom in • Zoom out Move mode • Move left • Move right Vertical zoom mode Zoom in or out in 4 steps 0 to 3 Endress+Hauser...
  • Page 34: Diagnostics And Troubleshooting

    • The error with the highest priority is displayed. • Several errors currently pending: scroll through the error messages with  or . 10.2 Previous error Display Diagnostics (0A) function group, Previous error (0A1) function Clear the display in the Clear last error (0A2) function Endress+Hauser...
  • Page 35: Types Of Error

    E651 = Level in safety distance, risk of overspill • The error disappears as soon as the level is no longer in the safety distance • Acknowledge alarm Safety settings (01) function group → Acknowledge alarm (017) function E661 = Sensor temperature too high Endress+Hauser...
  • Page 36: Application Errors

    1. Check Empty calibration (005) and Full calibration (006) and correct. 2. Check the linearization and correct it: Level/ullage (040), Max. scale (046), Diameter vessel (047), Linearization table. Error: Measured value (000) and measured distance in Distance (008) incorrect. Example: Endress+Hauser...
  • Page 37 4. If very large interference echoes occur simultaneously, select "Off" in the Detection window (0A7) function. Error: If the surface is turbulent, the measured value jumps sporadically to higher levels. Turbulent: e.g. when filling, emptying, or with running agitator Examples: 100% t → A0038461 Expected result Error occurred Endress+Hauser...
  • Page 38 1. Check the tank shape and correct it → "Dome ceiling" or "Horizontal cyl.". 2. If possible, do not select an installation position in the middle 3. If necessary, use a stilling well/ultrasound guide pipe Error: Echo loss (E641) Example: Endress+Hauser...
  • Page 39: Resetting The Measuring Device

    • If you want to use a device with an unknown history • If an incorrect mapping has been recorded Navigation → Extended calibration (05) function group → Selection (050) function → "Extended map." function → Cust. tank map (055) Endress+Hauser...
  • Page 40: Firmware History

    Repair 12.1 General notes Endress+Hauser repair concept • Measuring devices have a modular design • Customers can carry out repairs For more information on service and spare parts, please contact your Endress+Hauser sales representative. Endress+Hauser...
  • Page 41: Endress+Hauser Services

    WARNING Incorrect repair can compromise electrical safety! Explosion Hazard! ‣ Only specialist personnel or the Endress+Hauser service team may carry out repairs on Ex-certified devices. ‣ Relevant standards and national regulations on hazardous areas, safety instructions and certificates must be observed.
  • Page 42: Accessories

    • Order number G 1½: 71452324 • Material: 316L (1.4404) • Weight: 2.8 kg (6.17 lb) Also suitable for NPT 1½. 13.1.2 Screw-in flange A0019281  31 Screw-in flange FAX50 Screw-in flange Nozzle Sensor EPDM process seal (included in the delivery) Endress+Hauser...
  • Page 43 316L (1.4404) Order number 71452327 13.1.4 Frame, 1 400 mm (55.1 in) 3.2 (0.13) 60 (2.36) ø33.7 (1.3) 4 (0.16) 20 (0.8) 55 (2.17) 109 (4.29) (3.94) 130 (5.12) 150 (5.91) A0037800  33 Dimensions. Unit of measurement mm (in) Endress+Hauser...
  • Page 44 3.2 (0.1) 4 (0.16) ø33.7 (1.3) 6.5 (0.3) 25 (1.0) 88 (3.5) 110 (4.3) 150 (5.9) A0019350  34 Dimensions of the wall bracket. Unit of measurement mm (in) Weight 1.4 kg (3.09 lb) Material 316L (1.4404) Order number 71452323 Endress+Hauser...
  • Page 45 316L (1.4404) Order number 71452318 • 50 mm (2.17 in) openings for all G 1-½" (MNPT 1-½") connections on front • 22 mm (0.87 in) opening can be used for an additional sensor • Retaining screws are included in delivery Endress+Hauser...
  • Page 46 • 22 mm (0.87 in) opening can be used for an additional sensor • Retaining screws are included in delivery Mounting the cantilever A0019523  37 Cantilever with mounting stand or wall bracket Mounting with wall bracket Mounting with mounting stand Cantilever Mounting frame Wall bracket Endress+Hauser...
  • Page 47 • Mounting bracket: 316 Ti (1.4571) or 316 L (1.4435) or 316 (1.4401) • Nut: V4A • Plate: 316 Ti (1.4571) • Screw set (M5) Spring washer: 301 (1.431) or V2A Screw: V4A Nut: V4A • Additional information: Brief Operating Instructions KA00202F Endress+Hauser...
  • Page 48: Communication-Specific Accessories

    The parameters are recorded and transmitted using Fieldgate FXA42, FXA30 and FXA30B gateway types. SupplyCare Hosting is offered as a hosting service (Software as a Service, SaaS). In the Endress+Hauser portal, the user is provided with the data over the Internet.
  • Page 49: Technical Data

    Measured variable Distance D between sensor membrane and product surface Using the linearization function, the device uses D to calculate the following in any unit: • Level L • Volume V • Flow Q over measuring weirs or open flumes Endress+Hauser...
  • Page 50: Output Signal

    • Local display (error symbol, error code and plain text description) • Current output, failure mode can be selected, e.g. according to NAMUR Recommendation NE43 • Digital interface 14.3 Power supply 14.3.1 Supply voltage Two-wire version, HART Terminal voltage directly at the device Endress+Hauser...
  • Page 51: Performance Characteristics

    • Humidity: 50 % • Ideally reflecting surface, e.g. calm, even liquid surface • No interference reflections inside the signal beam • Configured parameters for applications: • Tank shape = Dome ceiling • Medium property = Liquid • Process cond. = Standard liquid Endress+Hauser...
  • Page 52: Environment

    –40 to +80 °C (–40 to +176 °F) The functionality of the LCD display is limited at Tu < –20 °C (–4 °F) and Tu >  60 °C (140 °F) If operating outdoors in strong sunlight, use a weather protection cover. Can be ordered as an accessory. Endress+Hauser...
  • Page 53: Process

    14.6.2 Process pressure range 0.7 to 3 bar abs. (10.15 to 43.5 psi abs.) Appendix 15.1 Overview of the operating menu Function groups and functions Basic setup 00 • Tank shape: 002 • Medium property: 003 • Process cond. 004 Endress+Hauser...
  • Page 54 • Fixed current 064 • Simulation 065 • Simulation value 066 • Output current 067 • 4 mA value 068 • 20 mA value 069 Envelope curve 0E • Plot settings 0E1 • Recording curve 0E2 • Envelope curve display 0E3 Endress+Hauser...
  • Page 55 • Measured dist. 0A5 • Measured level 0A6 • Detection window 0A7 • Application par. 0A8 System parameter 0C • Measuring point 0C0 • Protocol+SW no. 0C2 • Serial number 0C4 • Distance unit 0C5 • Temperature unitOC6 • Download mode 0C8 Endress+Hauser...
  • Page 56: Index

    Product description ......7 Establishing the connection ....27 Endress+Hauser...
  • Page 57 Weather protection cover ..... 48 Workplace safety ......6 Endress+Hauser...