Operating Instructions
Prosonic M FMU40/41/42/43/44
Ultrasonic Level Measurement
BA00239F/00/EN/13.12
71164392
Valid as of software version:
V 01.04

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Prosonic M FMU40

  • Page 1 Operating Instructions Prosonic M FMU40/41/42/43/44 Ultrasonic Level Measurement BA00239F/00/EN/13.12 71164392 Valid as of software version: V 01.04...
  • Page 2 You can find an overview of all the device functions in the Appendix. You can find a detailed description of all the device functions in the operating instructions BA00240F/00/EN "Prosonic M - Description of Instrument Functions". This is located on the supplied documentation CD-ROM. Endress+Hauser...
  • Page 3: Table Of Contents

    Software history ......68 Contact addresses of Endress+Hauser ... 68 Design;...
  • Page 4: Safety Instructions

    Operating Manual. Strict compliance with the installation instructions and ratings as stated in this Additional documentation is mandatory. • Ensure that all personnel are suitably qualified. • Observe the specifications in the certificate as well as national and local regulations. Endress+Hauser...
  • Page 5: Notes On Safety Conventions And Symbols

    A connection made to the plant grounding system which may be of type e.g. neutral star or equipotential line according to national or company practice Temperature resistance of the connection cables t >85°C States, that the connection cables must be resistant to a temperature of at least 85 °C (185 °F). Endress+Hauser...
  • Page 6: Identification

    Identification Prosonic M - FOUNDATION Fieldbus Identification Nameplate ENDRESS+HAUSER Made in Germany PROSONIC M D-79689 Maulburg Order Code: Ser.-No.: NEMA 4X/6P / IP68 14 ... 30 V DC 0.8W 2-wire 4 ... 20 mA HART Ta > 70°C if modification see sep.
  • Page 7: Product Structure Fmu40

    C Aluminium T12 housing coated to IP68 NEMA6P; with separate terminal compartment D Aluminium T12 housing coated to IP68 NEMA6P+OVP; with separate terminal compartment; with overvoltage protection Special version Screw union/entry M20x1.5 screw union G 1/2“ entry NPT 1/2“ entry M12 PROFIBUS-PA plug-in connector 7/8" FF plug Special version Endress+Hauser...
  • Page 8 Identification Prosonic M - FOUNDATION Fieldbus Marking Tagging (TAG) Bus address FMU40 - Product designation Endress+Hauser...
  • Page 9: Product Structure Fmu41

    D Aluminium T12 housing coated to IP 68 NEMA 6P; with separate terminal compartment; with overvoltage protection Special version Screw union/entry M20x1.5 screw union G 1/2“ entry NPT 1/2“ entry M12 PROFIBUS-PA plug-in connector 7/8" FF plug Special version Marking Tagging (TAG) Bus address FMU41 - Product designation Endress+Hauser...
  • Page 10: Product Structure Fmu42

    A Aluminium F12 housing coated to IP 68 NEMA 6P C Aluminium T12 housing coated to IP 68 NEMA 6P, with separate terminal compartment D Aluminium T 12 housing coated to IP 68 NEMA 6P, with separate terminal compartment; with overvoltage protection Special version Endress+Hauser...
  • Page 11 G 1/2“ entry NPT 1/2“ entry M12 PROFIBUS-PA plug 7/8" FF plug Special version Sealing Sensor/Flange VITON flat sealing EPDM flat sealing special version Additional options A Additional options not selected Marking Tagging (TAG) Bus address FMU42 - Product designation Endress+Hauser...
  • Page 12: Product Structure Fmu43

    A Aluminium F12 housing coated to IP 68 NEMA 6P Special version Screw union/entry M20x1.5 screw union G 1/2“ entry NPT 1/2“ entry M12 PROFIBUS-PA plug-in connector 7/8" FF plug Special version Marking Tagging (TAG) Bus address FMU43 - Product designation Endress+Hauser...
  • Page 13: Product Structure Fmu44

    M 4-wire 90-250VAC; 4-20mA HART,5-point linearity protocol N 4-wire 10.5-32VDC;4-20mA HART,5-point linearity protocol Special version, to be specified Operation w/o display, via communication 4-line display VU331, Envelope curve display on site Prepared for FHX40, Remote display (accessory) Special version, to be specified Endress+Hauser...
  • Page 14 Plug 7/8“ Special version, to be specified Process Sealing Sensor/ Flange Viton EPDM Special version, to be specified Additional option A Basic version Y Special version, to be specified Marking Tagging (TAG) Bus address FMU44 - complete product designation Endress+Hauser...
  • Page 15: Scope Of Delivery

    The device complies with the applicable standards and regulations as listed in the EC declaration of conformity and thus complies with the statutory requirements of the EC directives. Endress+Hauser confirms the successful testing of the device by affixing to it the CE mark.
  • Page 16: Installation

    Prosonic M - FOUNDATION Fieldbus Installation Design; dimensions 3.1.1 FMU40, FMU41 (2.6) (3.1) 32 (1.3) ( 3.4) (2.6) (3.1) (3.7) (2.7) ENDRESS+HAUSER ENDRESS+HAUSER Prosonic M Prosonic M (3.3) (3.3) FMU40 FMU41 SW (AF) 60 SW (AF) 60 G1½” G2” 1½ NPT 2 NPT ø39 (1.5)
  • Page 17 119 (4.7) (3.9) L00-FMU4xxxx-06-00-00-yy-008 Dimensions in mm (in) 3.1.4 FMU43 (2.6) (3.1) (3.4) ENDRESS+HAUSER Prosonic M 2 x M8 85 (3.3) ANSI 4” DN 100 * ø230 (9.1) L00-FMU4xxxx-06-00-00-yy-009 Dimensions in mm (in) A With slip-on flange B With mounting bracket 3.1.5...
  • Page 18 (9,50") (11,22") (0,91") 8" 150 lbs 298,5 mm 298,5 mm 342,9 mm 22, 5 mm 45° (11,75") (11,75") (13,50") (0,89") DN200 PN16 / 10 K 200 290 mm 295 mm 340 mm 23 mm 30° (11,42") (11,61") (13,39") (0,91") Endress+Hauser...
  • Page 19: Installation Variants

    Prosonic M - FOUNDATION Fieldbus Installation Installation variants 3.2.1 Installation variants FMU40, FMU41 ENDRESS+HAUSER Prosonic M L00-FMU4xxxx-17-00-00-yy-002 A Installation with counter nut 1 Counter nut (PC) supplied for G1½ and G2 instruments B Installation with sleeve 1 Sealing ring (EPDM) supplied...
  • Page 20 A Installation with universal flange (Ex-hazardous, e.g. Zone 20) B Installation with mounting bracket, (Non-Ex-hazardous, Zone 20) 3.2.3 Installation variants FMU43 L00-FMU43xxxx-17-00-00-yy-001 A Installation with universal slip-on flange (option) 1 Sensor 2 Nozzle 3 Slip-on flange B Installation with mounting bracket Endress+Hauser...
  • Page 21: Installation Conditions

    (e.g. PE or PVC wastewater pipe) with a minimum diameter of 100 mm (3.94 in). Make sure that the pipe is not soiled by accumu- lated dirt. If necessary, clean the pipe at regular intervals. L00-FMU4xxxx-17-00-00-yy-010 1 Venting hole Endress+Hauser...
  • Page 22 • You can enter the "Flow to Level" linearisation curve ("Q/h curve") using the operating program or manually via the on-site display. Example: Khafagi-Venturi flume 1 x b L00-FMU4xxxx-17-00-00-xx-003 Khafagi-Venturi flume Inflow C Outflow BD Blocking distance E Empty calibration F Full calibration V Direction of flow Endress+Hauser...
  • Page 23 Prosonic M - FOUNDATION Fieldbus Installation Example: Triangular weir min. 2 H (= F) min. 2 H min. 3 H L00-FMU4xxxx-17-00-00-xx-012 BD Blocking distance E Empty calibration F Full calibration Endress+Hauser...
  • Page 24: Measuring Range

    8 (26.0) 10 (33.0) 15 (49.0) 20 (66.0) in liquids Max. range [m (ft)] 2 (6.6) 3.5 (11.0) 5 (16.0) 7 (23.0) 10 (33.0) in solids " Caution! If the blocking distance is undershot, it may cause device malfunction. Endress+Hauser...
  • Page 25: Installation Hint For Fmu40, Fmu41

    Use only the screw-in piece to screw in the Prosonic M. Screw the Prosonic M at the screw-in piece using an 60 AF spanner. Maximum torque: 20 Nm (14.75 lbf ft). L00-FMU4xxxx-17-00-00-yy-009 1 Housing F12 or T12 2 60 AF Endress+Hauser...
  • Page 26: Turn Housing

    • If available: Are the measuring point number and labelling correct (visual inspection)? • Is the measuring device sufficiently protected against precipitation and direct sunlight? • Are the cable glands tightened correctly? • After aligning the housing, check the process seal at the nozzle or flange. Endress+Hauser...
  • Page 27: Wiring

    (see below). Re-insert terminal module (4). Tighten cable gland (6). 10. Tighten screws on cover plate (3). 11. Insert display (2) if fitted. 12. Screw on housing cover (1). 13. Switch on power supply. 1 2 3 4 L00-FMU4xxxx-04-00-00-yy-008 Endress+Hauser...
  • Page 28 (4) within the connection room. Make connection according to the terminal assignment (see below). Tighten cable gland (3). Screw on housing cover (1). Switch on power supply. 1 2 3 4 L00-FMU4xxxx-04-00-00-yy-009 4.1.3 Terminal assignment plant ground – L00-FMxxxxxx-04-00-00-en-013 Endress+Hauser...
  • Page 29: Wiring With Foundation Fieldbus Plug

    The following values are the voltages across the terminals directly at the instrument: Type Minimum terminal voltage Maximum terminal voltage standard 32 V Ex ia (FISCO model 17,5 V Ex ia (Entity concept) 24 V The current consumption is approx. 15 mA for the range of voltages given above. Endress+Hauser...
  • Page 30: Recommended Connection

    • Are the terminals correctly assigned? • Is the cable gland tight? • If available: Is the FOUNDATION Fieldbus connector screwed tight? • Is the housing cover fully screwed on? • If power supply available: Does a display appear on the display module? Endress+Hauser...
  • Page 31: Operation

    Mess Meas berei berei uring uring U 16...3 U 16...3 range range max. max. 4...20 4...20 >70° >70° t >85°C t >85°C ENDRESS + HAUSER – L00-FMxxxxxx-07-00-00-yy-001 1 LCD liquid crystal display 2 Snap fit 3 Keys 4 Symbols Endress+Hauser...
  • Page 32 This lock symbol appears when the instrument is locked,i.e. if no input is possible. COM_SYMBOL This communication symbol appears when a data transmission via e.g. HART, PROFIBUS PA or FOUNDATION Fieldbus is in progress. SIMULATION_SWITCH_ENABLE This communication symbol appears when simulation in FOUNDATION Fieldbus is enabled via the DIP switch. Endress+Hauser...
  • Page 33: Function Codes

    The third digit numbers the individual functions within the function group:  • tank shape • basic setup • medium property • process cond..Hereafter the position is always given in brackets (e.g. "tank shape" (002)) after the described function. Endress+Hauser...
  • Page 34: Operating Options

    On-site operation 5.4.1 Options for on-site operation • Display and operating module VU331 • Endress+Hauser operating software "FieldCare" 5.4.2 Parameter access by on-site operation The following parameters can be accessed by on-site operation: • Parameters of the device specific blocks (Sensor Block, Diagnostic Block, Display Block) •...
  • Page 35: Operation Using The On-Site Display Vu331

    Sensorblock AI-Block 1 Input-Selector-Block Diagnoseblock AI-Block 2 Signal-Charact.-Block Display-Block PID Block Integrator-Block Endress+Hauser Service-Parameter L00-FMU4XXXX-02-00-00-YY-005 The highlighted parameters can be edited by on-site operation. Operation using the on-site display VU331 ENDRESS + HAUSER – >3 s Return to basic setup...
  • Page 36: Remote Operation

    FieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare, you can configure all Endress+Hauser devices as well as devices from other manufacturers that support the FDT standard. Hardware and software requirements you can find on the internet: www.endress.com ➝...
  • Page 37 • If you click on a parameter name, the Help pages open with precise explanations of the required input. 5.7.2 Signal analysis via envelope curve: The FieldCare offers easy analysis of the envelope curve via the "Envelope" menu: L00-FMU4xxxx-19-00-00-en-022 Endress+Hauser...
  • Page 38: Operation With A Foundation Fieldbus Configuration Program

    *.cff The directory names have the following meaning: • 452B48: manufacturer ID of Endress+Hauser • 1011: device ID of Prosonic M "Device Revision" (0C3) and "DD Revision" (0C4) can be obtained through the display and operating module VU331. For details refer to section 5.2: "Operation with the display and operating module VU331"...
  • Page 39: Operation Via Field Xpert Sfx100

    • Representation by parameter name Examples: "PAROPERATIONCODE", "PARRESET" • Representation by parameter label (identical to the labels on the display module VU331 and in an Endress+Hauser operation tool) Examples: "unlock parameter", "reset" Operation via Field Xpert SFX100 Compact, flexible and robust industry handheld terminal for remote parametrization and measured value inspection via the HART current output or FOUNDATION Fieldbus.
  • Page 40: Commissioning

    WP = off: parametrization unlocked SIM = on: simulation possible in Analog Input Block by configuration tool SIM = off: simulation not possible in Analog Input Block by configuration tool Parameters affected Locking by the DIP switch affects all parameters. Endress+Hauser...
  • Page 41 Enter "2457". Now parameters can be changed. Parameters affected Locking by the key combination affects the following parameters: • Parameters of the device specific blocks (Sensor Block, Diagnostic Block, Display Block) • Endress+Hauser service parameters 6.2.3 Locking parameter Locking Enter a number other than "2457" into the "unlock parameter" (0A4) function.
  • Page 42: Resetting The Device

    To realize this, the parameter "zero distance" is fine adjusted. After a reset the value for the zero distance has to be re-parameterized in the service menu according to the data on the associated 5- point linearity protocol. Please contact the Endress+Hauser service. 6.3.1...
  • Page 43 – "inactive": deactivates the tank map but does not delete it. It can be re-activated when required. – "active": activates the tank map. Resetting the tank map with an Endress+Hauser operating program In the function group "extended calibr." select the "cust. tank map" (055) function. Select the required option ("reset", "inactive" or "active") Resetting the tank map with a FOUNDATION Fieldbus configuration tool In the Sensor Block select the parameter PARCUSTTANKMAP (cust tank map).
  • Page 44: Commissioning By The Display And Operatig Module Vu331

    A measured value is displayed. This is NOT equivalent to the level in your tank. Firstly carry out a basic calibration. L00-fmrxf000-20-00-00-en-001 Press F to switch to the group selection. Press F again to start the basic calibration. L00-fmrxfg00-20-00-00-en-001 Endress+Hauser...
  • Page 45 Interference echo suppression (tank mapping) L00-FMU4xxx-19-00-00-en-000 D Distance (distance from the sensor membrane (= reference point of the measurement) / product) E Empty calibr. (= zero point F Full calibr. (= span) L Level BD Block distance SD Safety distance Endress+Hauser...
  • Page 46 Commissioning Prosonic M - FOUNDATION Fieldbus 6.4.3 Application parameters Function "tank shape" (002) In this function, select one of the following options: ENDRESS+HAUSER Prosonic M L00-FMU4xxxx-14-00-06-en-001 A Dome ceiling B Horizontal cyl C Bypass, stilling well/ultrasonic guide pipe D No ceiling, e.g. dumps, open levels, chanels, weirs...
  • Page 47 The averaging filters are set to small The filter and output damping are set signal are set to large values. values. to average values. -> Stable measured value -> Rapid reaction time -> Medium reaction time -> Possibly unstable measured value Endress+Hauser...
  • Page 48 Test: no filter Dusty bulk solids Bulk solids with rapid level change All the filters can be switched off for purposes of service and diagnosis. ENDRESS+HAUSER Prosonic M L00-FMU4xxxx-14-00-00-xx-007 L00-FMU4xxxx-14-00-00-xx-005 The filters are set to detect even The averaging filters are set to small All filters off relatively weak signals.
  • Page 49 Prosonic M signals a warning or an alarm, depending on your selection in the "in safety distance" (016) function. Function "full calibration" (006) In this function, enter the span F, i.e. the distance from the minimum level to the maximum level. Endress+Hauser...
  • Page 50 You can still edit the value. With manual suppression, the default value is 0 m. " Caution! The suppression range must end 0.5 m (1.6 ft) in front of the echo of the actual level. With an empty tank, do not enter E but E – 0.5 m. Endress+Hauser...
  • Page 51 • Distance correct – Level incorrect -> Check the value of the "empty calibr." (005) function. Return to group selection After the mapping has been recorded the basic calibration is completed and the device automatically returns to the group selection. Endress+Hauser...
  • Page 52 If the cyclical envelope curve display is still active on the display, the measured value is updated at a slower cycle time. We therefore advise you to exit the envelope curve display after optimising the measuring point. To do this, press F. (The instrument does not leave the envelope curve display automatically.) Endress+Hauser...
  • Page 53 Vertical Zoom mode Press once more to switch to Vertical Zoom mode. is displayed. You now have the following options. • increases the vertical scale. • reduces the vertical scale. The display icon shows the current zoom factor ( L00-FMxxxxxx-07-00-00-yy-009 Endress+Hauser...
  • Page 54 • Press to exit the navigation. The set increases and shifts are retained. Only when you reactivate the "recording curve" (0E2) function the display settings return to their standard values. Endress+Hauser...
  • Page 55: Commissioning With A Foundation Fieldbus Configuration Tool

    For commissioning of the device with a FOUNDATION Fieldbus configuration tool you need to know the DEVICE_ID, which consists of the following parts: Device_ID = 452B481011-XXXXXXXX whereby: 452B48 ID code for Endress+Hauser 1011 ID code for Prosonic M XXXXXXXX Device serial number, as printed on the nameplate 6.5.1 First setup Open the configuration tool and load the Device Descriptions (*.ffo, *.sym and - if required by...
  • Page 56 • You can open one of the FOUNDATION Fieldbus methods. Each method guides you automatically through a number of parameters which are required for a specific configuration task. The following sections describe the parametrization by the "basic setup" method. Endress+Hauser...
  • Page 57 – by the display and operating module VU331 ( Chap. 6.4.1) – by an Endress+Hauser operating program ( Chap. 6.5.1) In the FOUNDATION Fieldbus configuration tool you can select from two types of parameter display: - parameter names (e.g. "PARTANKSHAPE") - label texts (e.g.
  • Page 58 – HI_LIM -> Limit value for the upper warning – LO_LIM -> Limit value for the lower warning – LO_LO_LIM -> Limit value for the lower alarm The limit values entered must be within the value range specified in the parameter group OUT_SCALE. Endress+Hauser...
  • Page 59 TARGET). However, this is only possible under the following conditions: – The function blocks are correctly connected with each other. – The parametrization of the AI Block is correct ( Kap. 6.5.4, steps 5 and 6). – The Resource Block is in operating mode AUTO. Endress+Hauser...
  • Page 60: Troubleshooting

    • VU331: error symbol in the "measured value" (000) function • VU331 or Endress+Hauser operating program: in the "diagnostics" (0A) function group in the "present error" (0A0) function Only the highest priority error is displayed; in the case of multiple errors, you can scroll between the different error messages by pressing O or S.
  • Page 61 Error disappears when the level leaves the safety distance. Possibly reset the risk of overspill lock. ["safety settings" (01) function group, "ackn. alarm" (017) function]] A661 Sensor overtemperature A671 Linearisation incomplete Activate linearisation table W681 current out of range Carry out basic calibration; check linearisation Endress+Hauser...
  • Page 62 Device Failure Device needs maintenance now Unspecified Err W601 Uncertain configuration error GOOD Non specific Other Configuration Error W611 Uncertain configuration error GOOD Non specific Other Configuration Error W621 Uncertain Non specific GOOD Non specific simulation active No Error Endress+Hauser...
  • Page 63 Device needs maintenance now Unspecified Err (Alarm) E661 Uncertain Non specific GOOD Non specific Device needs maintenacne soon Unspecified Err (Warning) A671 Device Failure GOOD Non specific Configuration Error No Error W691 Uncertain Non specific GOOD Non specific Other Unspecified Err Endress+Hauser...
  • Page 64: Application Errors

    3. Increase output damping (058). may jump sporadically to (FF: Sensor Block, PAROUTPUTDAMPING) higher expected levels 4. If necessary, select a different installation position and/or a larger sensor t → L00-FMR2xxxx-19-00-00-en-015 100% actual expected t → L00-FMR2xxxx-19-00-00-en-016 Endress+Hauser...
  • Page 65 (FF: Sensor Block, PARTANKSHAPE, PARMEDIUMCONDITION, PARPROCESSCONDITION) 100% 2. If necessary, select a different installation position and/or a larger sensor eingetreten 3. Align the sensor parallel to the product surface (particularly for bulk solids applications) E 641 erwartet t → L00-FMR2xxxx-19-00-00-en-018 Endress+Hauser...
  • Page 66: Maintenance And Repairs

    Repairs The Endress+Hauser repair concept assumes that the measuring devices have a modular design and that customers are able to undertake repairs themselves  ä 67, "Spare Parts". For more information on service and spare parts, contact the Service Department at Endress+Hauser.
  • Page 67: Spare Parts

    Select the required spare parts (You may also use the overview drawing on the right side of the screen.) When ordering spare parts, always quote the serial number indicated on the nameplate. As far as necessary, the spare parts also include replacement instructions. Endress+Hauser...
  • Page 68: Return

    The measuring device must be returned if repairs or a factory calibration are required, or if the wrong measuring device has been ordered or delivered. According to legal regulations, Endress+Hauser, as an ISO-certified company, is required to follow certain procedures when handling returned products that are in contact with medium.
  • Page 69: Accessories

    1 F12 / T12 housing Installation bracket for FMU40, FMU41 ø16 L00-FMU4x-00-00-00-de-001 Dimensions in mm • for FMU 40, G1½: Order No. 942669-0000 • for FMU 41, G2: Order No. 942669-0001 suited for NPT 1½" and 2" as well Endress+Hauser...
  • Page 70: Screw In Flange

    020 Sensor Connection: Thread ISO228 G3/4 Thread ISO228 G1 Thread ISO228 G1-1/2 Thread ISO228 G2 Thread ANSI NPT3/4 Thread ANSI NPT1 Thread ANSI NPT1-1/2 Thread ANSI NPT2 Special version The filled in options result in the complete order code. FAX50 - Endress+Hauser...
  • Page 71: Cantilever

    • The 50 mm (2.17 in) or 62 mm (2.44 in) orifices serve for the mounting of the FMU40 or FMU41 sensor, respecitvely. • The 22 mm (0.87 in) orifice may be used for an additional sensor. For the mounting of the cantilever can be used: • mounting frame  ä 72 • wall bracket  ä 72 Endress+Hauser...
  • Page 72: Mounting Frame

    700 (27.6) galv. steel 919791-0000 700 (27.6) 316Ti (1.4571) 919791-0001 1400 (55.1) galv. steel 919791-0002 1400 (55.1) 316Ti (1.4571) 919791-0003 mm (in) Wall Bracket ø 33.7 L00-FMU4x-00-00-00-yy-006 Dimensions in mm Material Order Code galv. steel 919792-0000 316Ti (1.4571) 919792-0001 Endress+Hauser...
  • Page 73: Mounting Bracket For Fmu 42/43/44

    For details refer to TI00404F/00/EN. Commubox FXA291 The Commubox FXA291 connects Endress+Hauser field instruments with CDI interface (= Endress+Hauser Common Data Interface) to the USB interface of a personal computer or a notebook. For details refer to TI00405C/07/EN. Note! For the instrument you need the "ToF Adapter FXA291" as an additional accessory.
  • Page 74: Remote Display Fhx40

    Technical data (cable and housing) and product structure: Max. cable length 20 m (65 ft) Temperature range -40 °C to +60 °C (-40 °F to 140 °F) Degree of protection IP65/67 (housing); IP68 (cable) acc. to IEC 60529 Dimensions mm/in (HxWxD) 122x150x80 / 4.8x5.9x3.2 Endress+Hauser...
  • Page 75 A Basic version Mounting bracket, pipe 1"/ 2" Special version, TSP-Nr. to be spec. Marking: Tagging (TAG) FHX40 - Complete product designation For connection of the remote display FHX40 use the cable which fits the communication version of the respective instrument. Endress+Hauser...
  • Page 76: Technical Data

    Device Revision 04 (hex) DD Revision 01 (hex) CFF Revision 01 (hex) ITK Version 4.61 ITK-Certification Driver-No. IT035900 Link Master (LAS) cabable Link Master / Basic Device yes; Default: Basic Device selectable Number VCRs Number of Link-Objects in VFD 24 Endress+Hauser...
  • Page 77 The signal characterizer block has two sections, each 40 ms standard rizer Block with an output that is a non-linear function of the respec- tive input. The non-linear function is determined by a sin- gle look-up table with 21 arbitrary x-y pairs. Endress+Hauser...
  • Page 78 Lift-off voltage Basic current 15 mA  15 mA In-rush current Error current 0 mA FISCO 17,5 V 500 mA; with surge arrester 273 mA 5,5 W; with surge arrester1, 2 W 5 mF 0,01 mH FNICO compliant Polarity sensitive Endress+Hauser...
  • Page 79 (hydrochloric acid, sulfuric acid, ...), dilute bases (caustic soda, ...), oils, greases, slurries, pastes, ... High vapor pressures or outgassing media (ethanol, acetone, ammonia, ...) can influence the accuracy. If conditions like these are present, please contact the Endress+Hauser support. Endress+Hauser...
  • Page 80 A temperature sensor is integrated in the sensor for correction of the temperature-dependent time- of-flight. Process pressure • FMU40, FMU41: 0.7 bar to 3bar abs. (10.15 psi to 43.5 psi abs.) • FMU42, FMU43, FMU44: 0.7 bar to 2.5bar abs. (10.15 psi to 36.25 psi abs.) Endress+Hauser...
  • Page 81 Prosonic M - FOUNDATION Fieldbus Technical Data Endress+Hauser...
  • Page 82: Appendix

    + sw-no. device id system parameters Note! The Default values of the parameters are typed in bold face. L00-FMU4xxxx-19-00-01-en-017 Endress+Hauser...
  • Page 83 . period , comma measured dist. measured level application par. detection window not modified modified reset distance unit temperature unit download mode parameter only param. + cust. map mapping only L00-FMU4xxxx-19-00-02-en-017 Endress+Hauser...
  • Page 84: Block Model Of The Prosonic M

    Primary value describe the e.g. scaling, status (main value) device (calibration, linearisation etc.) Secondary value (distance) Analog Input Function Block 2 parameters that are important to the process control system, Third value e.g. scaling, status (temperature) L00-FMU4XXXX-02-00-00-en-003 Endress+Hauser...
  • Page 85: Resource Block

    Shows any configuration, hardware, connection and system problems in the lock. The cause of the alert is to be seen in the subcode field. The function of the resource block parameters not described here can can be taken from the FOUNDATION Fieldbus specification, see "www.fieldbus.org". Endress+Hauser...
  • Page 86: Sensor Block

    A complete list of the configuration parameters can be found in the "Description of Instrument Functions", BA00240F/00/EN. If MODE_BLK refuses to be changed to AUTO, an error is present. Control all parameters, perform the required changes and try again to change MODE_BLK to AUTO. Endress+Hauser...
  • Page 87 Unsigned8 dynamic Auto, OOS measured temp. PARMEASUREDTEMPERATURE FloatingPoint dynamic Auto, OOS max. temp. limit PARMAXTEMPLIMIT FloatingPoint dynamic Auto, OOS max. meas. temp PARMAXMEASUREDTEMPERATURE FloatingPoint non-vol. Auto, OOS react. high temp PARONHIGHTEMPERATURE Unsigned8 static defect temp sens PARDEFECTTEMPERATURESENSOR Unsigned8 static Endress+Hauser...
  • Page 88 PARDISTANCEUNIT Unsigned16 static temperature unit PARTEMPERATUREUNIT Unsigned16 static download mode PARDOWNLOADMODE Unsigned8 static max meas dist 0D84 PARABSMAXMESSDIST FloatingPoint dynamic Auto, OOS max sample dist. 0D88 PAREDITRANGEMAXSAMPLEDIST FloatingPoint dynamic Auto, OOS present error PARACTUALERROR Unsigned16 dynamic Auto, OOS Endress+Hauser...
  • Page 89: Diagnostic Block

    PAROPERATIONCODE Unsigned16 non-vol. protocol+sw-no. PARPROTSOFTVERSIONSTRING VisibleString const Auto, OOS If MODE_BLK refuses to be changed to AUTO, an error is present. Control all parameters, perform the required changes and try again to change MODE_BLK to AUTO. Endress+Hauser...
  • Page 90: Display Block

    PARSEPARATIONCHARACTER Unsigned8 non-vol. Auto, OOS unlock parameter PAROPERATIONCODE Unsigned16 non-vol. If MODE_BLK refuses to be changed to AUTO, an error is present. Control all parameters, perform the required changes and try again to change MODE_BLK to AUTO. Endress+Hauser...
  • Page 91: Analog Input Block

    User description of the intended application of the block. BLOCK_ERROR Shows error status of software and hardware components – Out-of-Service: the block is in OOS mode – Simulation active: shows the setting of DIP-switch SIM. Input failure/process variable has BAD status. – configuration error Endress+Hauser...
  • Page 92 XD_SCALE_MAX - XD_SCALE_MIN The L_TYPE parameter influences the signal conversion: • Direct: PV = CHANNEL_VALUE • Indirect: FIELD_VALUE PV = x (OUT_SCALE_MAX - OUT_SCALE_MIN) + OUT_SCALE_MIN • Indirect square root: FIELD_VALUE PV = x (OUT_SCALE_MAX - OUT_SCALE_MIN) + OUT_SCALE_MIN Endress+Hauser...
  • Page 93 8 - 15 Critical alarms of increasing priority 11.7.8 Alarm status Parameter Description HI_HI_ALM The status of the HI_HI alarm HI_ALM The status of the HI alarm LO_ALM The status of the LO alarm LO_LO_ALM The status of the LO_LO alarm Endress+Hauser...
  • Page 94 A simulation is also possible by switching MODE_BLK to "MAN" and entering a value for OUT. Parameter Description SIMULATE Enables, sets and displays a simulated value, options: – enable/disable – simulated value – output value Endress+Hauser...
  • Page 95: List Of Start Indices

    View Objects Arithmetic Function Block 3040 View Objects Input Selector Function Block 3050 View Objects Signal Characterizer Function Block 3060 View Objects Integrator Function Block 3070 View Objects Sensor Block 4000 View Object Diagnostic Block 4100 View Object Display Block 4200 Endress+Hauser...
  • Page 96: Measuring Principle

    The interference echo suppression feature on the Prosonic M ensures that interference echos (e.g. from edges, welded joints and installations) are not interpreted as a level echo. 11.9.3 Calibration Enter the empty distance E and the span F to calibrate the device. Endress+Hauser...
  • Page 97 Prosonic M - FOUNDATION Fieldbus Appendix 11.9.4 Blocking distance Span F may not extend into the blocking distance BD. Level echos within the blocking distance cannot be evaluated due to the transient characteristics of the sensor. Endress+Hauser...
  • Page 98: Index

    ........25 Endress+Hauser...
  • Page 99 Prosonic M - FOUNDATION Fieldbus Index Endress+Hauser...
  • Page 100 www.endress.com/worldwide BA00239F/00/EN/13.12 71164392 FM+SGML 9.0 71164392...