Operating Instructions Prosonic M FMU40/41/42/43/44 Ultrasonic Level Measurement BA239F/00/en/01.09 71089089 Valid as of software version: V 01.04...
Page 2
You can find an overview of all the device functions in the Appendix. You can find a detailed description of all the device functions in the operating instructions BA 240F/00/en "Prosonic M - Description of Instrument Functions". This is located on the supplied documentation CD-ROM. Endress+Hauser...
Operating Manual. Strict compliance with the installation instructions and ratings as stated in this supplementary documentation is mandatory. • Ensure that all personnel are suitably qualified. • Observe the specifications in the certificate as well as national and local standards and regulations. Endress+Hauser...
A connection made to the plant grounding system which may be of type e.g. neutral star or equipotential line according to national or company practice Temperature resistance of the connection cables t >85°C States, that the connection cables must be resistant to a temperature of at least 85 °C. Endress+Hauser...
Identification Prosonic M - FOUNDATION Fieldbus Identification Nameplate ENDRESS+HAUSER Made in Germany PROSONIC-M D-79689 Maulburg Order Code: Ser.-No.: IP68 / NEMA 6P Profibus PA Foundation Fieldbus 90 … 253 V AC 4VA 10,5 …32 V DC 1W 14 … 36 V DC 0,8W 4 …...
D Aluminium T12 housing coated to IP 68; with separate terminal compartment; with overvoltage protection Special version Screw union/entry M20x1.5 screw union G 1/2“ entry NPT 1/2“ entry M12 PROFIBUS-PA plug-in connector 7/8" FF plug Special version FMU 40 - Product designation Endress+Hauser...
D Aluminium T12 housing coated to IP 68; with separate terminal compartment; with overvoltage protection Special version Screw union/entry M20x1.5 screw union G 1/2“ entry NPT 1/2“ entry M12 PROFIBUS-PA plug-in connector 7/8" FF plug Special version FMU 41 - Product designation Endress+Hauser...
C Aluminium T12 housing coated to IP 68, with separate terminal compartment D Aluminium T 12 housing coated to IP 68, with separate terminal compartment; with overvoltage protection Special version Gland/Entry M20x1.5 gland G 1/2“ entry NPT 1/2“ entry M12 PROFIBUS-PA plug 7/8" FF plug Special version Endress+Hauser...
Page 10
Identification Prosonic M - FOUNDATION Fieldbus Sealing Sensor/Flange VITON flat sealing EPDM flat sealing special version Additional options A Additional options not selected FMU 42 - Product designation Endress+Hauser...
Prepared for remote display FHX 40 Special version Housing A Aluminium F12 housing coated to IP 68 Special version Screw union/entry M20x1.5 screw union G 1/2“ entry NPT 1/2“ entry M12 PROFIBUS-PA plug-in connector 7/8" FF plug Special version FMU 43 - Product designation Endress+Hauser...
H 4-wire 10.5-32VDC; 4-20mA HART Special version, to be specified Operation w/o display, via communication 4-line display VU331, Envelope curve display on site Prepared for FHX40, Remote display (accessory) Special version, to be specified FMU 44 - product designation, part 1 Endress+Hauser...
Page 13
Thread NPT 1/2 Plug M12 Plug 7/8“ Special version, to be specified Process Sealing Sensor/ Flange Viton EPDM Special version, to be specified Additional option A Basic version Y Special version, to be specified FMU 44 - complete product designation Endress+Hauser...
The device complies with the applicable standards and regulations as listed in the EC declaration of conformity and thus complies with the statutory requirements of the EC directives. Endress+Hauser confirms the successful testing of the device by affixing to it the CE mark.
Page 16
119 (4.7) (3.9) L00-FMU4xxxx-06-00-00-yy-008 Dimensions in mm (inch) 3.1.4 FMU43 (2.6) (3.1) (3.4) ENDRESS+HAUSER Prosonic M 2 x M8 85 (3.3) ANSI 4” DN 100 * Ø 230 (9.1) L00-FMU4xxxx-06-00-00-yy-009 Abb. 2: Dimensions in mm (inch); A: with slip-on flange; B: with mounting bracket 3.1.5...
Page 17
(9,50") (11,22") (0,91") 8" 150 lbs 298,5 mm 298,5 mm 342,9 mm 22, 5 mm 45° (11,75") (11,75") (13,50") (0,89") DN200 PN16 / 10 K 200 290 mm 295 mm 340 mm 23 mm 30° (11,42") (11,61") (13,39") (0,91") Endress+Hauser...
Sealing ring (EPDM) supplied counter nut (PC) supplied for G 1½” and G 2” instruments Installation with installation bracket Installation with adapter flange ENDRESS+HAUSER Prosonic M Sealing ring (EPDM) adapter flange supplied sensor nozzle L00-FMU4xxxx-17-00-00-en-002 For installation bracket or adapter flange s. chapter "Accessories".
Page 19
Installation variants FMU42, FMU44 Installation with mounting bracket Installation with universal flange e.g. Zone 20 Zone 20 L00-FMU42xxxx-17-00-00-en-001 3.2.3 Installation variants FMU 43 Installation with Installation with universal slip-on flange (option) mounting bracket slip-on flange sensor nozzle e.g.Zone 20 Zone 20 L00-FMU43xxxx-17-00-00-en-001 Endress+Hauser...
15 m 0.79 m FMU44 11 ° 20 m 1.93 m 3.3.2 Installation in narrow shafts In narrow shafts with strong interference ENDRESS+HAUSER ENDRESS+HAUSER ENDRESS+HAUSER ENDRESS+HAUSER Prosonic M Prosonic M Prosonic M Prosonic M echoes, we recommend using an ultrasound guide pipe (e.g.
Page 21
• Keep to the installation distance of the channel or weir. • You can enter the "Flow to Level" linearisation curve ("Q/h curve") using ToF Tool or manually via the on-site display. Example: Khafagi-Venturi flume inflow outflow Khafagi - Venturi - flume direction of flow 1 x b L00-FMU4xxxx-17-00-00-en-003 Endress+Hauser...
Page 22
Installation Prosonic M - FOUNDATION Fieldbus Example: Triangular weir min. 2 H α (= full calibr.) min. 2 H min. 3 H L00-FMU4xxxx-17-00-00-en-012 Endress+Hauser...
DN200/8" DN250/10" DN300/12" Emitting angle α 11° 11° 9° 6° 11° Blocking distance [m] 0,25 0,35 Max. range [m] in liquids Max. range [m] in solids " Caution! If the blocking distance is undershot, it may cause device malfunction. Endress+Hauser...
Page 24
The sensor range is dependent on the measuring conditions. Refer to Technical Information TI 365F/00/en for an estimation. The maximum range is shown in the above diagram (valid for good conditions). Sensor maximum range FMU40 FMU41 FMU42 10 m FMU43 15 m FMU44 20 m Endress+Hauser...
• If available: Are the measuring point number and labelling correct (visual inspection)? • Is the measuring device sufficiently protected against precipitation and direct sunlight? • Are the cable glands tightened correctly? • After aligning the housing, check the process seal at the nozzle or flange. Endress+Hauser...
(see below). Re-insert terminal module (4). Tighten cable gland (6). 10. Tighten screws on cover plate (3). 11. Insert display (2) if fitted. 12. Screw on housing cover (1). 13. Switch on power supply. 1 2 3 4 L00-FMU4xxxx-04-00-00-yy-008 Endress+Hauser...
Page 27
(4) within the connection room. Make connection according to the terminal assignment (see below). Tighten cable gland (3). Screw on housing cover (1). Switch on power supply. 1 2 3 4 L00-FMU4xxxx-04-00-00-yy-009 4.1.3 Terminal assignment plant ground – L00-FMxxxxxx-04-00-00-en-013 Endress+Hauser...
The following values are the voltages across the terminals directly at the instrument: Type minimum terminal maximum terminal voltage voltage standard 32 V EEx ia (FISCO model 17,5 V EEx ia (Entity concept) 24 V The current consumption is approx. 15 mA for the range of voltages given above. Endress+Hauser...
• Are the terminals correctly assigned? • Is the cable gland tight? • If available: Is the Foundation Fieldbus connector screwed tight? • Is the housing cover fully screwed on? • If power supply available: Does a display appear on the display module? Endress+Hauser...
This chapter contains the following sections: • 5.1 Operating options • 5.2 Operation with the display and operating module VU331 • 5.3 Operation with an Endress+Hauser operating software • 5.4 Operation with a FOUNDATION Fieldbus configuration software • 5.5 Operation with the handheld terminal DXR375/FC375...
Page 31
On-site operation Options for on-site operation • Display and operating module VU331 • Endress+Hauser operating software ("ToF Tool - FieldTool Package" or "FieldCare") Parameter access by on-site operation The following parameters can be accessed by on-site operation: • Parameters of the device specific blocks (Sensor Block, Diagnostic Block, Display Block) •...
L00-FMxxxxxx-07-00-00-en-002 In the measured value display, the bargraph corresponds to the output. The bargraph is segmented in 10 bars. Each completely filled bar represents a change of 10% of the adjusted span. Endress+Hauser...
Page 33
Contrast settings of the LCD Hardware lock / unlock After a hardware lock, an operation of the instrument via display or communication is not possible! The hardware can only be unlocked via the display. An unlock parameter must be entered to do so. Endress+Hauser...
Page 34
The third digit numbers the individual functions within the function group: → • tank shape • basic setup • medium property • process cond..Hereafter the position is always given in brackets (e.g. "tank shape" (002)) after the described function. Endress+Hauser...
Page 35
Press F to select the next function. Press O and S (= Q) once; return to previous function. Press O and S (= Q) twice; return to Group Selection. Press O and S (= Q) to return to Measured value display. Endress+Hauser...
Page 36
ToF Tool – Fieldtool Package The ToF Tool is a graphic and menu-guided operating program for measuring devices from Endress+Hauser. It is used for the commissioning, data storage, signal analysis and documentation of the devices. The following operating systems are supported: WinNT4.0, Win2000 and Windows XP.
Page 37
FieldCare FieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare, you can configure all Endress+Hauser devices as well as devices from other manufacturers that support the FDT standard. The following operating systems are supported: WinNT4.0, Win2000 and Windows XP.
Page 38
Operation Prosonic M - FOUNDATION Fieldbus Menu-guided commissioning MicropilotM-en-305 Signal analysis via envelope curve MicropilotM-en-306 Endress+Hauser...
Page 39
Prosonic M - FOUNDATION Fieldbus Operation Tank linearisation MicropilotM-en-307 Endress+Hauser...
• /452B48/1011/*.sym *.ffo *.cff The directory names have the following meaning: • 452B48: manufacturer ID of Endress+Hauser • 1011: device ID of Prosonic M Source of supply Host System Source of supply for the Device Description and Network Configuration files ABB (Field Controller 800) •...
Page 41
A FOUNDATION Fieldbus configuration tool offers two types of parameter representation: • Representation by parameter name Examples: "PAROPERATIONCODE", "PARRESET" • Representation by parameter label (identical to the labels on the display module VU331 and in an Endress+Hauser operation tool) Examples: "unlock parameter", "reset" Endress+Hauser...
You can navigate within the structure by the arrow keys and the "Enter" key. Alternatively, you can use the touch-screen functionality of the handheld terminal for navigation. (Double-click on a name opens the respective block or parameter). Endress+Hauser...
Page 43
CANCEL HELP Page Delete dsdmdm basic setup df das. asdas fa asas la. Prosonic M E+H_PROSONIC_M_XXXXXX tank shape: dome ceiling Endress+Hauser Device Revision 4 dome ceiling Block Tag Block Type Actual Mode horizontal cyl bypass RESOURCE... RES_BL... Auto stilling well SENSOR_B...
• 6.2 Unlocking the device • 6.3 Parameter reset • 6.4 Commissioning with display and operating module VU331 • 6.5 Commissioning with Endress+Hauser operating software • 6.6 Commissioning with FOUNDATION Fieldbus configuration tool • 6.7 Commissioning with handheld terminal DXR375/FC375...
Page 45
Enter "2457". Now parameters can be changed. Parameters affected Locking by the key combination affects the following parameters: • Parameters of the device specific blocks (Sensor Block, Diagnostic Block, Display Block) • Endress+Hauser service parameters 6.2.3 Locking parameter Locking Enter a number other than "2457" into the "unlock parameter" (0A4) function.
Sensorblock AI-Block 1 Input-Selector-Block Diagnoseblock AI-Block 2 Signal-Charact.-Block Display-Block PID Block Integrator-Block Endress+Hauser Service-Parameter L00-FMU4XXXX-02-00-00-YY-007 Performing the reset Resource Block, parameter RESTART; select the option "defaults". 6.3.2 Resetting the parameters of the transducer blocks " Caution! A reset may lead to impairment of the measurement. As a rule, a basic calibration is required after a reset.
Page 47
– "inactive": deactivates the tank map but does not delete it. It can be re-activated when required. – "active": activates the tank map. Resetting the tank map with an Endress+Hauser operating program In the function group "extended calibr." select the "cust. tank map" (055) function. Select the required option ("reset", "inactive" or "active") Resetting the tank map with a FOUNDATION Fieldbus configuration tool In the Sensor Block select the parameter PARCUSTTANKMAP (cust tank map).
The "Basic setup" (00) function group lists all the functions which are required for a standard measurement task to commission the Prosonic M. When you have completed your input for a function, the next function appears automatically. In this way, you are guided through the complete calibration. Endress+Hauser...
Page 49
6.4.2 Application parameters Function "tank shape" (002) In this function, select one of the following options: dome ceiling horizontal cyl bypass stilling well ENDRESS+HAUSER Prosonic M (ultrasonic guide pipe) no ceiling sphere flat ceiling e.g. dumps, open levels chanels, weirs L00-FMU4xxxx-14-00-06-en-001 Function "medium property"...
Page 50
The averaging filters are set to small The filter and output damping are set signal are set to large values. values. to average values. -> Stable measured value -> Rapid reaction time -> Medium reaction time -> Possibly unstable measured value Endress+Hauser...
Page 51
Test: no filter Dusty bulk solids Bulk solids with rapid level change All the filters can be switched off for purposes of service and diagnosis. ENDRESS+HAUSER Prosonic M L00-FMU4xxxx-14-00-00-xx-007 L00-FMU4xxxx-14-00-00-xx-005 The filters are set to detect even The averaging filters are set to small All filters off relatively weak signals.
Page 52
Prosonic M signals a warning or an alarm, depending on your selection in the "in safety distance" (016) function. Function "full calibration" (006) In this function, enter the span F, i.e. the distance from the minimum level to the maximum level. Endress+Hauser...
Page 53
You can still edit the value. With manual suppression, the default value is 0 m. " Caution! The suppression range must end 0.5 m in front of the echo of the actual level. With an empty tank, do not enter E but E – 0.5 m. Endress+Hauser...
Page 54
Go back to the "check distance" (051) function. • Distance correct – Level incorrect -> Check the value of the "empty calibr." (005) function. Rücksprung zur Gruppenauswahl Nach der Störechoausblendung ist der Grundabgleich beendet und das Gerät springt automatisch in die Gruppenauswahl zurück. Endress+Hauser...
Page 55
If the cyclical envelope curve display is still active on the display, the measured value is updated at a slower cycle time. We therefore advise you to exit the envelope curve display after optimising the measuring point. To do this, press F. (The instrument does not leave the envelope curve display automatically.) Endress+Hauser...
Page 56
Vertical Zoom mode Press once more to switch to Vertical Zoom mode. is displayed. You now have the following options. • increases the vertical scale. • reduces the vertical scale. The display icon shows the current zoom factor ( L00-FMxxxxxx-07-00-00-yy-009 Endress+Hauser...
Page 57
• Press to exit the navigation. The set increases and shifts are retained. Only when you reactivate the "recording curve" (0E2) function the display settings return to their standard values. Endress+Hauser...
Commissioning Prosonic M - FOUNDATION Fieldbus Basic Setup with the Endress+Hauser operating program To carry out the basic setup with the operating program, proceed as follows: • Start the operating program and establish a connection. • Select the "basic setup" function group in the navigation window.
Page 59
– tank shape – medium property – process cond. ProsonicM-en-412 Basic Setup step 3/4: If "dome ceiling", "horizontal cyl", "..." is selected in the "tank shape" function, the following display appears on the screen: • empty calibr. • full calibr. ProsonicM-en-303 Endress+Hauser...
Page 60
• This step starts the tank mapping • The measured distance and the current measured value are always displayed in the header ProsonicM-en-304 6.5.1 Signal analysis via envelope curve After the basic setup, an evaluation of the measurement using the envelope curve is recommended. MicropilotM-en-306 Endress+Hauser...
Page 61
Prosonic M - FOUNDATION Fieldbus Commissioning 6.5.2 User-specific applications (operation) For details of setting the parameters of user-specific applications, see separate documentation BA240F/00/en "Prosonic M - Description of Instrument Functions" on the enclosed CD-ROM. Endress+Hauser...
For commissioning of the device with a FOUNDATION Fieldbus configuration tool you need to know the DEVICE_ID, which consists of the following parts: Device_ID = 452B481011-XXXXXXXX whereby: 452B48 ID code for Endress+Hauser 1011 ID code for Prosonic M XXXXXXXX Device serial number, as printed on the nameplate 6.6.1 Fist setup Open the configuration tool and load the Device Descriptions (*.ffo, *.sym and - if required by...
Page 63
• You can open one of the FOUNDATION Fieldbus methods. Each method guides you automatically through a number of parameters which are required for a specific configuration task. The following sections describe the parametrization by the "basic setup" method. Open the FOUNDATION Fieldbus method "basic setup": Endress+Hauser...
Page 64
– by the display and operating module VU331 (see section 6.4.5) – by an Endress+Hauser operating program (see section 6.5.1) In the FOUNDATION Fieldbus configuration tool you can select from two types of parameter display: - parameter names (e.g. "PARTANKSHAPE") - label texts (e.g.
Page 65
– HI_LIM -> Limit value for the upper warning – LO_LIM -> Limit value for the lower warning – LO_LO_LIM -> Limit value for the lower alarm The limit values entered must be within the value range specified in the parameter group OUT_SCALE. Endress+Hauser...
Page 66
TARGET). However, this is only possible under the following conditions: – The function blocks are correctly connected with each other. – The parametrization of the AI Block is correct (see 6.6.4, steps 5 and 6). – The Resource Block is in operating mode AUTO. Endress+Hauser...
(→ Page 62 ff.). The blocks should be parametrized in the following order: • the RESOURCE BLOCK • the SENSOR BLOCK (the "basic setup" method can be used for this, see page → ä 43) • the ANALOG INPUT BLOCKS Endress+Hauser...
• VU331: error symbol in the "measured value" (000) function • VU331 or Endress+Hauser operating program: in the "diagnostics" (0A) function group in the "present error" (0A0) function Only the highest priority error is displayed; in the case of multiple errors, you can scroll between the different error messages by pressing O or S.
Page 69
Error disappears when the level leaves the safety distance. Possibly reset the risk of overspill lock. ["safety settings" (01) function group, "ackn. alarm" (017) function]] A661 Sensor overtemperature A671 Linearisation incomplete Activate linearisation table W681 current out of range Carry out basic calibration; check linearisation Endress+Hauser...
Page 70
Device Failure Device needs maintenance now Unspecified Err W601 Uncertain configuration error GOOD Non specific Other Configuration Error W611 Uncertain configuration error GOOD Non specific Other Configuration Error W621 Uncertain Non specific GOOD Non specific simulation active No Error Endress+Hauser...
Page 71
Device needs maintenance now Unspecified Err (Alarm) E661 Uncertain Non specific GOOD Non specific Device needs maintenacne soon Unspecified Err (Warning) A671 Device Failure GOOD Non specific Configuration Error No Error W691 Uncertain Non specific GOOD Non specific Other Unspecified Err Endress+Hauser...
FF: Sensor Block, PARPROCESSCONDITION) measured value actual 3. Increase output damping (058). may jump sporadically to (FF: Sensor Block, PAROUTPUTDAMPING) higher expected levels 4. If necessary, select a different installation position and/or a larger sensor L00-FMR2xxxx-19-00-00-en-015 100% actual expected L00-FMR2xxxx-19-00-00-en-016 Endress+Hauser...
Page 73
1. Check application parameters (002), (003) and (004) (FF: Sensor Block, PARTANKSHAPE, PARMEDIUMCONDITION, PARPROCESSCONDITION) 100% 2. If necessary, select a different installation position and/or a larger sensor eingetreten 3. Align the sensor parallel to the product surface (particularly for bulk solids applications) E 641 erwartet L00-FMR2xxxx-19-00-00-en-018 Endress+Hauser...
Spare parts are contained in suitable kits. They contain the related replacement instructions. All the spare parts kits which you can order from Endress+Hauser for repairs are listed with their order numbers in the section "Spare parts".
Maintenance and repairs Return The following procedures must be carried out before a transmitter is sent to Endress+Hauser e.g. for repair or calibration: • Remove all residue which may be present. Pay special attention to the gasket grooves and crevices where fluid may be present.
Maintenance and repairs Prosonic M - FOUNDATION Fieldbus 8.10 Contact addresses of Endress+Hauser Contact addresses can be found on our homepage: www.endress.com/worldwide. If you have any questions, please do not hesitate to contact your Endress+Hauser representative. Endress+Hauser...
>8 t >8 5° C 5° C L00-FMR2xxxx-00-00-06-en-001 Installation bracket for FMU 40/41 ø16 L00-FMU4x-00-00-00-de-001 • for FMU 40, G1½: Order No. 942669-0000 • for FMU 41, G2: Order No. 942669-0001 suited for NPT 1½" and 2" as well Endress+Hauser...
FMU 41 316Ti/1.4571 52014138 galv. steel 52014137 • The 50 mm or 62 mm orifices serve for the mounting of the FMU 40 or FMU 41 sensor, respecitvely. • The 22 mm orifice may be used for an additional sensor. Endress+Hauser...
Height Material Order Code 700 mm galv. steel 919791-0000 700 mm 1.4301 (AISI 304) 919791-0001 1400 mm galv. steel 919791-0002 1400 mm 1.4301 (AISI 304) 919791-0003 Wall Bracket ø 33.7 L00-FMU4x-00-00-00-yy-006 Material Order Code galv. steel 919792-0000 316Ti/1.4571 919792-0001 Endress+Hauser...
L00-FMU4x-00-00-00-en-003.eps Commubox FXA291 The Commubox FXA291 connects Endress+Hauser field instruments with CDI interface (= Endress+Hauser Common Data Interface) to the USB interface of a personal computer or a notebook. For details refer to TI405C/07/en. Note! For the following Endress+Hauser instruments you need the "ToF Adapter FXA291" as an additional accessory: •...
20m/65ft; for HART 20m/65ft; for PROFIBUS PA/FOUNDATION Fieldbus Additional option: Basic version Mounting bracket, pipe 1"/ 2" FHX40 - Complete product designation For connection of the remote display FHX40 use the cable which fits the communication version of the respective instrument. Endress+Hauser...
Device Revision 04 (hex) DD Revision 01 (hex) CFF Revision 01 (hex) ITK Version 4.61 ITK-Certification Driver-No. IT035900 Link Master (LAS) cabable Link Master / Basic Device yes; Default: Basic Device selectable Number VCRs Number of Link-Objects in VFD 24 Endress+Hauser...
Page 90
The signal characterizer block has two sections, each 40 ms standard rizer Block with an output that is a non-linear function of the respec- tive input. The non-linear function is determined by a sin- gle look-up table with 21 arbitrary x-y pairs. Endress+Hauser...
Page 91
The reaction time depends on the parameter settings. The minimum values are: • FMU40/41/42/43: min. 2 s • FMU44: min. 3 s Reference operating • Temperature = +20 °C conditions • Pressure = 1013 mbar abs. • Humidity = 50 % • Ideal reflective surface (e.g. calm, smooth fluid surface) Endress+Hauser...
Page 92
(hydrochloric acid, sulfuric acid, ...), dilute bases (caustic soda, ...), oils, greases, slurries, pastes, ... High vapor pressures or outgassing media (ethanol, acetone, ammonia, ...) can influence the accuracy. If conditions like these are present, please contact the Endress+Hauser support. 10.1.6 Ambient conditions Ambient temperature -40 °C ...
Page 93
Process conditions Process temperature -40°C ... +80°C A temperature sensor is integrated in the sensor for correction of the temperature-dependent time- of-flight. Process pressure • FMU 40/41: 0.7 bar ... 3bar abs. • FMU 42/43/44: 0.7 bar ... 2.5bar abs. Endress+Hauser...
+ sw-no. device id system parameters Note! The Default values of the parameters are typed in bold face. L00-FMU4xxxx-19-00-01-en-017 Endress+Hauser...
Page 95
. period , comma measured dist. measured level application par. detection window not modified modified reset distance unit temperature unit download mode parameter only param. + cust. map mapping only L00-FMU4xxxx-19-00-02-en-017 Endress+Hauser...
Primary value describe the e.g. scaling, status (main value) device (calibration, linearisation etc.) Secondary value (distance) Analog Input Function Block 2 parameters that are important to the process control system, Third value e.g. scaling, status (temperature) L00-FMU4XXXX-02-00-00-en-003 Endress+Hauser...
Shows any configuration, hardware, connection and system problems in the lock. The cause of the alert is to be seen in the subcode field. The function of the resource block parameters not described here can can be taken from the FOUNDATION Fieldbus specification, see "www.fieldbus.org". Endress+Hauser...
A complete list of the configuration parameters can be found in the "Description of Instrument Functions", BA240F/00/en. If MODE_BLK refuses to be changed to AUTO, an error is present. Control all parameters, perform the required changes and try again to change MODE_BLK to AUTO. Endress+Hauser...
PAROPERATIONCODE Unsigned16 non-vol. protocol+sw-no. PARPROTSOFTVERSIONSTRING VisibleString const Auto, OOS If MODE_BLK refuses to be changed to AUTO, an error is present. Control all parameters, perform the required changes and try again to change MODE_BLK to AUTO. Endress+Hauser...
PARSEPARATIONCHARACTER Unsigned8 non-vol. Auto, OOS unlock parameter PAROPERATIONCODE Unsigned16 non-vol. If MODE_BLK refuses to be changed to AUTO, an error is present. Control all parameters, perform the required changes and try again to change MODE_BLK to AUTO. Endress+Hauser...
User description of the intended application of the block. BLOCK_ERROR Shows error status of software and hardware components – Out-of-Service: the block is in OOS mode – Simulation active: shows the setting of DIP-switch SIM. Input failure/process variable has BAD status. – configuration error Endress+Hauser...
Page 104
XD_SCALE_MAX - XD_SCALE_MIN The L_TYPE parameter influences the signal conversion: • Direct: PV = CHANNEL_VALUE • Indirect: FIELD_VALUE PV = x (OUT_SCALE_MAX - OUT_SCALE_MIN) + OUT_SCALE_MIN • Indirect square root: FIELD_VALUE PV = x (OUT_SCALE_MAX - OUT_SCALE_MIN) + OUT_SCALE_MIN Endress+Hauser...
Page 105
8 - 15 Critical alarms of increasing priority 11.7.8 Alarm status Parameter Description HI_HI_ALM The status of the HI_HI alarm HI_ALM The status of the HI alarm LO_ALM The status of the LO alarm LO_LO_ALM The status of the LO_LO alarm Endress+Hauser...
Page 106
A simulation is also possible by switching MODE_BLK to "MAN" and entering a value for OUT. Parameter Description SIMULATE Enables, sets and displays a simulated value, options: – enable/disable – simulated value – output value Endress+Hauser...
The interference echo suppression feature on the Prosonic M ensures that interference echos (e.g. from edges, welded joints and installations) are not interpreted as a level echo. 11.9.3 Calibration Enter the empty distance E and the span F to calibrate the device. Endress+Hauser...
Page 109
Prosonic M - FOUNDATION Fieldbus Appendix 11.9.4 Blocking distance Span F may not extend into the blocking distance BD. Level echos from the blocking distance cannot be evaluated due to the transient characteristics of the sensor. Endress+Hauser...
....... . . 35 operating menu ....... . 94 Endress+Hauser...
Page 111
Erklärung zur Kontamination und Reinigung Please reference the Return Authorization Number (RA#), obtained from Endress+Hauser, on all paperwork and mark the RA# clearly on the outside of the box. If this procedure is not followed, it may result in the refusal of the package at our facility.