Test Run - Daikin FXZQ-MVJU9 Engineering Data

4-way ceiling mounted cassette unit
Table of Contents

Advertisement

EDUS391300-F9
When using wireless remote controllers
When using the wireless remote controllers, wireless remote controller address setting is necessary.
Refer to the installation manual attached to the wireless remote controller.
For details, refer to the HOW TO SET IN THE FIELD, in the remote controller manual.
OFF at factory set)

12. TEST RUN

Refer to the installation manual of the outdoor unit.
malfunction codes and the corresponding trouble is provided in CAUTION FOR SERVICING of the
outdoor unit.
If any of the items in Table 5 are displayed, there may be a problem with the wiring or power, so check
the wiring again.
Table 5
Remote control display
[U4] is lit up
[UH] is lit up
No display
If the decoration panel is installed on the indoor unit during the test run, check the operation of the
In order to protect the indoor unit, instruct the customer not to operate the air conditioner until the
If the air conditioner is operated, substances discharged from paint or adhesive can contaminate the
indoor unit, and they may cause splashing or leakage of water.
NOTE
25
FXZQ-MVJU9
Content
The power on the outdoor unit is off.
The outdoor unit has not been wired for power supply.
Incorrect wiring for the transmission wiring and / or FORCED
OFF wiring.
The power on the indoor unit is off.
The indoor unit has not been wired for power supply.
Incorrect wiring for the remote controller wiring, the
transmission wiring and / or the FORCED OFF wiring.
b. Items to be checked at time of delivery.
3P184443-12N
English
Installation
C: 3P184443-12N
47