4-Way Ceiling Mounted Cassette Unit (2' × 2')
Model
Power supply
1 3 Cooling Capacity
2 3 Heating Capacity
Casing / Color
Dimensions: (H×W×D)
Rows×Stages×FPI
Coil (Cross
Fin Coil)
Face Area
Model
Type
Fan
Motor Output (High)
Airflow Rate (H/L)
Drive
Temperature Control
Sound absorbing thermal insulation material
Machine Weight (Mass)
Liquid Pipes
Gas Pipes
Piping
Connections
Drain Pipe
4 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Standard Accessories
Model
Color
Decoration
Dimensions: (H×W×D)
Panels
(Option)
Air filter
Weight
Drawing No.
Notes:
1. Nominal cooling capacities are based on the following conditions:
Return air temperature: 80.0°FDB (26.7°CDB), 67.0°FWB (19.4°CWB)
Outdoor temperature: 95.0°FDB (35.0°CDB)
Equivalent ref. piping length: 25ft (7.6m) (Horizontal)
2. Nominal heating capacities are based on the following conditions:
Return air temperature: 70.0°FDB (21.1°CDB).
Outdoor temperature: 47.0°FDB (8.33°CDB), 43.0°FWB (6.11°CWB)
Equivalent ref. piping length: 25ft (7.6m) (Horizontal)
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4. Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
5. Refer to page 8 for Power Input.
FXZQ-MVJU9
FXZQ15MVJU9
1 phase, 208/230V, 60Hz
Btu/h
Btu/h
Galvanized Steel Plate
11-1/4 × 22-5/8 × 22-5/8
in. (mm)
(285 × 575 × 575)
2 × 10 × 17
ft² (m²)
2.9 (0.269)
QTS32C15M
Turbo Fan
W
cfm
388/282
Direct Drive
Microprocessor Thermostat for Cooling and Heating
Foamed polystyrene
Lbs (kg)
φ1/4 (6.4) (Flare Connection)
in. (mm)
φ1/2 (12.7) (Flare Connection)
in. (mm)
in. (mm)
External Dia. 1-1/32 (26)
(
Internal Dia. 25/32 (20)
dB(A)
PC board fuse. Fan motor thermal protector.
Electronic Expansion Valve
R410A VRV Series
Operation manual, Installation manual, Paper pattern for
installation, Drain hose, Metal clamp, Washer fixing plate,
Sealing pads, Clamps, Screws, Washer for hanging bracket,
Insulation for fitting, Sealing material, Conduit mounting
plate.
BYFQ60B8W1U
2-5/32 × 27-9/16 × 27-9/16
in. (mm)
(55 × 700 × 700)
Resin net
(with mold resistance)
Lbs (kg)
15,000
17,500
55
42 (19)
VP20
)
36/30
Operation manual, Installation manual, Paper pattern for
installation, Drain hose, Metal clamp, Washer fixing plate,
Sealing pads, Clamps, Screws, Washer for hanging bracket,
Insulation for fitting, Sealing material, Conduit mounting
plate.
White
6 (2.7)
C: 3D080461A
Specifications
FXZQ18MVJU9
1 phase, 208/230V, 60Hz
18,000
21,000
Galvanized Steel Plate
11-1/4 × 22-5/8 × 22-5/8
(285 × 575 × 575)
2 × 10 × 17
2.9 (0.269)
QTS32C15M
Turbo Fan
55
495/353
Direct Drive
Microprocessor Thermostat for Cooling and Heating
Foamed polystyrene
42 (19)
φ1/4 (6.4) (Flare Connection)
φ1/2 (12.7) (Flare Connection)
VP20
External Dia. 1-1/32 (26)
(
Internal Dia. 25/32 (20)
41/34
PC board fuse. Fan motor thermal protector.
Electronic Expansion Valve
R410A VRV Series
BYFQ60B8W1U
White
2-5/32 × 27-9/16 × 27-9/16
(55 × 700 × 700)
Resin net
(with mold resistance)
6 (2.7)
)
3

Advertisement