FIELD SETTING AND TEST RUN

9-1 Press and hold Cancel button for 4 seconds or
longer.
Service settings menu is displayed.
9-2 Select "Field Settings" in the Service Settings
menu, and press Menu/OK button.
Field settings screen is displayed.
9-3 Highlight the mode and select desired "Mode
No." by using
9-4 In the case of setting per unit during group
control (When Mode No. such as "20" , "21" ,
"22" , "23" , "25" are selected), highlight the
unit No. and select "Indoor unit No." to be set by
using
(Up/Down) button.
(In the case of group total setting, this operation
is not needed.)
In the case of individual setting per unit, current set-
tings are displayed. And, SECOND CODE NO. " - "
means no function.
9-5 Highlight SECOND CODE NO. of the FIRST
CODE NO. to be changed and select desired
"SECOND CODE NO." by using
button. Multiple identical mode number settings
are available.
In case of setting for all units in the remote control
group, available SECOND CODE NO. is displayed as
" * " which means it can be changed.
When SECOND CODE NO. is displayed as " - ", there
is no function.
9-6 Press Menu/OK button. Setting confirmation
screen is displayed.
9-7 Select "Yes" and press Menu/OK button. Setting
details are determined and field settings screen
returns.
9-8 In the case of multiple setting changes, repeat
"9-3" to "9-7".
9-9 After all setting changes are completed, press
Cancel button twice.
9-10 Backlight goes out and "Checking the
connection. Please stand by." is displayed for
initialization. After the initialization, the basic
screen returns.
13
28
(Up/Down) button.
(Up/Down)
<Basic screen>
9-1
Vent
AUTO
ERV
Return
Setting
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
<Service Settings menu screen>
9-2
Service Settings
Test Operation
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Buttons
Min Setpoints Differential
Setting
Press Menu/OK button.
<Service Settings menu screen>
In the case of individual
setting per unit
9-3
9-3
Field Settings
9-4
Unit No
Mode
9-5
0
20
0 –
01
1 – 01
2 – 02
3 – 01
9-5
4 –––
5 –––
6 –––
7 –––
8 –––
9 –––
a –––
b –––
Setting
Press Menu/OK button.
<Setting confirmation screen>
9-6
Field Settings
Save the settings?
9-7
Yes
No
Setting
Press Menu/OK button.
Setting confirmation
EDUS711116
1/3
In the case of group total
setting
Field Settings
Unit No
Mode
0
10
0 –
01
4 –––
8 –––
Setting
SECOND CODE NO.
FIRST CODE (SW) NO.
English
3P034928-7Q
VAM-GVJU