Daikin FXZQ-MVJU9 Engineering Data page 31

4-way ceiling mounted cassette unit
Table of Contents

Advertisement

EDUS391300-F9
The air direction is selectable when an optional sealing-material kit is ordered. With this option,
you can select air to be directed in two, three, or four directions.
(1) Select and installation location matching the customer's conditions:
Nothing blocks air
Drainage is available
Sturdy area to support weight of unit
Wall is not tilted
Length of indoor-outdoor piping is not longer than tolerated length. Refer to outdoor unit Installation
manual for details.
NOTE
Leave 8 in. or more space where marked with the *, on sides where the air outlet is closed.
FXZQ07·09·12·15·18MVJU9
CAUTION
The indoor and outdoor units and the power supply wiring and remote controller wiring must be
installed at least 40 in. away from any televisions or radios. This is to prevent interference with picture
If installing the wireless kit, the distance of the signal sent from the remote controller might be shorter if
(2) Ceiling height
Install this unit where the height of bottom panel is more than 100 in. so that the user cannot easily
touch it.
(3) Air direction
Select the appropriate number of directions according to the shape of the room and the location of
the unit. Field settings have to be made using the remote controller and the outlet vents have to be
separately) installation manual for details.
7
FXZQ-MVJU9
Air
Air
Air
outlet
outlet
inlet
>
>
*
*
60
60
Fig. 1
Model
>
*
>
60
*
60
>
*
60
>
*
60
Fig. 2
H
3P184443-12N
Installation
English
C: 3P184443-12N
29