Installation Of The Decoration Panel - Daikin FXZQ-MVJU9 Engineering Data

4-way ceiling mounted cassette unit
Table of Contents

Advertisement

EDUS391300-F9
9-3
CONTROL BY 2 REMOTE CONTROLLERS (CONTROLLING 1 INDOOR UNIT BY 2
REMOTE CONTROLLERS)
When using 2 remote controllers, one must be set to MAIN and the other to SUB.
Wiring Method
(1)
(2)
EXTERNAL REMOTE CONTROL (FORCED OFF AND ON/OFF OPERATION)
(1)
Connect the input from outside to terminals T1 and T2 of the terminal block for remote controller.
F2
T1
T2
FORCED
OFF
Input A
(2) Actuation
FORCED OFF
Input OFF enables control by remote controller
(3) How to select FORCED OFF and ON/OFF OPERATION
Turn the power on and then use the remote controller to select operation.
9-5
CENTRALIZED CONTROL
For centralized control, it is necessary to designate the group No. For details, refer to the manual of
each optional controller for centralized control.

INSTALLATION OF THE DECORATION PANEL

Caution:
the decoration panel.
<Read 12. TEST RUN before making a test run without attaching the decorated panels.>
Refer to the installation manual attached to the decoration panel.
After installing the decoration panel, ensure that there is no space between the unit body and decoration
panel.
23
FXZQ-MVJU9
8. ELECTRIC WIRING WORK)
and Table 8-3)
Gauge
Length
, P
1
2
AWG 18-16
Contact that can ensure the minimum applicable
load of 15V DC, 1 mA.
ON/OFF OPERATION
Input OFF
ON turns ON unit.
Input ON
OFF turns OFF unit.