11. FIELD SETTINGS

CAUTION
the drain pump. This may cause electric shock.
Check that the outdoor unit has been wired properly.
(1) Make sure the control box cover is closed on the indoor and outdoor units.
(2) Field settings must be made from the remote controller and in accordance with installation
conditions.
Settings can be made by changing the MODE NO., FIRST CODE NO. and SECOND CODE NO..
operation.
Setting is made in all units in a group. To set for individual indoor units or to check the setting, use
11-1 SETTING AIR OUTLET DIRECTION
See the installation manual included with the sealing material of air discharge outlet kit, sold separately
and technical guide, for ceiling height settings for two and three-direction air discharge.
11-2 SETTING FOR OPTIONS
For settings for options, see the installation manual provided with the option.
11-3 SETTING AIR FILTER SIGN
Change the SECOND CODE NO. according to
room.
Table 4
3P184443-12N
46
Field settings
0 –
01
4 –––
8 –––
Return
FIRST CODE NO.
Spacing time of display air
Setting
English
FIELD SET MODE
Mode
MODE NO.
10
Setting
SECOND CODE NO.
Fig. 32
depending on the amount of dirt or dust in the
MODE NO.
EDUS391300-F9
FIRST
SECOND
CODE NO.
CODE NO.
01
0
02
24
C: 3P184443-12N
FXZQ-MVJU9