Technical Data; Technical Specifications/Equipment Ratings; Gas Reading Accuracy - Trane TruSense RMWH Installation, Operation And Maintenance Manual

Refrigerant monitor
Table of Contents

Advertisement

Technical Data

Technical Specifications/
Equipment Ratings
Usage
Overvoltage
Pollution
AC Power
Operating Temperature
Operating Altitude Limit
Operating Humidity
Ingress Protection
Size
Weight
Sensor Type
Sample Line Tubing
Sample Line Length
Gases
Measuring Range
Sensitivity (minimum detection)
Accuracy (linearity)
Sensor Response Time
Relays
Audible Alarm
Communication Outputs

Gas Reading Accuracy

Gas
As factory calibrated:
R-134A, R-404A, R-410A, R-407C, R-123, R1233zd(E)
As factory calibrated extended library:
R-11, R-12, R-1234ze, R-22, R-407F, 
R-401A, R-407A, R-422A, R-422D, R-427A, R-507, R-1234yf, R513A, R-514A
As calibrated after installation:
R-134A, R-404A, R-410A, R-407C, R-123, R1233zd(E), R-11, R-12, R-1234ze, R-22, 
R-407F, R-401A, R-407A, R-422A, R-422D, R-427A, R-507, R-1234yf, R-513A, R-514A
50
Indoor use only
Category II
Degree 2
100–240 Vac, 50/60 Hz, 200 VA maximum
Supply voltage not to fluctuate more than ±10%
32°F–122°F (0°C to 50°C)
9762 ft (2975 m)
0 to 95%, noncondensing
IP54
Height x Width x Depth = 
15.6 in. x 13.6 in. x 7.6 in. 
(39.6 cm x 34.5 cm x 19.3 cm)
4 point unit = 14 lb (6.4 kg)
8 point unit = 15 lb (6.8 kg)
16 point = 17 lb (7.7 kg)
Photoacoustic Infrared
1/4 in. OD x 1/8 in. ID
6 mm OD x 4 mm ID
Up to 400 ft (121 m) for optimum performance, will support up
to 1200 ft (366 m)
R11, R12, R22, R123, R134A, R401A, R404A, R407A, R407C,
R407F, R410A, R422A, R422D, R427A, R507, R1233zd(E),
R1234yf, R1234ze, R-513A, R-514A
0–1000 ppm
1 ppm for all listed gases
0– 50 ppm ±1 ppm, 51–1000 ppm ±10% of reading
90% of gas reading <70 sec
5 Form C, 8A 250 Vac resistive SPDT
95 ±5 dB(A) at 24 in. (61 cm) maximum
4–20 mA sourcing, 250 Ohm load; 0–10 V, 2 K Ohm minimum
load; RS485 Modbus RTU; RS-485 BACnet MS/TP
Polyurethane (ether based) or metal
with tubing
Gas Concentration
Gas Reading Accuracy
1–50 ppm
±1 ppm
51–1000 ppm
±10% of F.S.
1–50 ppm
±3 ppm
51–1000 ppm
±30% of reading
1–50 ppm
±1 ppm
51–1000 ppm
±10% of F.S.
RMWH-SVX001C-EN