If multiple faults occur simultaneously, the pop-up shows
the faults as line items.
To acknowledge the event and return to the dashboard,
select Acknowledge.
If the fault can be related to a single or multiple points, the
associated point tiles show on the dashboard with a
yellow background.
If the fault cannot be related to a single point or multiple
points, the dashboard shows in a normal state.
To see the details about a specific point, on the dashboard,
select the point tile.
To see the details about the fault itself, go to the Event Log,
Faults tab. Refer to
"Event Log," p.

Critical Faults

WARNING
Risk of Asphyxiation and Explosion!
Failure to follow instruction below could result in death
or serious injury.
When in critical fault mode, the device no longer
monitors for gas. It is critical that the fault be repaired
as quickly as possible in order to re-establish gas
monitoring.
A critical fault causes the following to occur:
The fault relay trips.
RMWH-SVX001C-EN
33.
The device cannot monitor for gas.
The 4–20 mA output decreases to the user-specified
fault level.
All modules except the main board and display shut
down.
All point tiles show on the dashboard with a yellow
background and a black X icon.
Note: If more than four events occur, use the scroll bar to
see the entire list of faults.
To acknowledge the events collectively and return to the
dashboard, select Acknowledge.

Event Log

On the dashboard, select the Event Log button.

All

The All tab shows a list of all types of events for the device.
The last 25 events show in chronological order. When
there are 25 events in the list and a new event occurs, the
oldest event is deleted to make space for the new event to
show.
Use the scroll bar to move through the list of events.