Initial Setup; Routine Operation; Starting Calibration - Trane TruSense RMWH Installation, Operation And Maintenance Manual

Refrigerant monitor
Table of Contents

Advertisement

Initial Setup

Following the initial setup, an initial calibration must be
completed to ensure sensor accuracy.
For a description of the dashboard, refer to
Overview," p.
30.
1. On the Initial Calibration screen, select Calibrate
Now.
2. Go to
Step 2
in
"Routine Operation," p.
Note: If Calibrate Later is selected, the dashboard
shows a notification on the Calibration button
until the initial calibration is completed.
Select Calibrate to re-open the Initial Calibration
screen and select Calibrate Now.
RMWH-SVX001C-EN

Routine Operation

"Dashboard
Risk of Asphyxiation!
Failure to follow instructions below could cause
inaccurate readings and improper gas monitoring
which could result in death or serious injury.
Make sure to remove the cap from the exhaust port
25.
before operating the device.

Starting Calibration

1. To start the calibration process, on the dashboard,
select Calibrate.
2. On the bottom of the device, remove the pin from the
calibration port.
3. On the device touchscreen, select Start.
Calibration
WARNING
25