Trane Tracer AdaptiView Operation Manual

For water-cooled centravac chillers
Hide thumbs Also See for Tracer AdaptiView:
Table of Contents

Advertisement

Quick Links

Operations Guide
Tracer AdaptiView
Display
for Water-Cooled CenTraVac
Chillers
X39641071-020
CTV-SVU01B-EN
March 2008

Advertisement

Table of Contents
loading

Summary of Contents for Trane Tracer AdaptiView

  • Page 1 Operations Guide Tracer AdaptiView Display ™ for Water-Cooled CenTraVac Chillers ™ X39641071-020 CTV-SVU01B-EN March 2008...
  • Page 2 © 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be used or reproduced in whole or in part, without the written permission of Trane. Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change.
  • Page 3: Table Of Contents

    Editing Custom Data Graphs ........33 CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 4 Data Points Used in Default Data Graphs ......69 Data Points Available to Include in Custom Data Graphs ....72 CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 5: Introduction

    CenTraVac™ chiller models CVHE, CVHF, and CVHG. The purpose of this guide is to assist you in using the Tracer AdaptiView display. The guide describes how to access the screens and the types of information that appear on the screens.
  • Page 6: Touchscreen Guidelines

    Animated color graphics indicate the status of the chiller and its components. AC power The Tracer AdaptiView display receives AC power through its power cable, which is connected to the Tracer UC800 controller. The Tracer UC800 controller must be powered...
  • Page 7: Screen Overview

    Introduction Screen Overview The touch-sensitive areas of the Tracer AdaptiView display screen are described in detail in this section. Figure 1, three areas are identified, which correspond to the following subsections: “Chiller Status Area, ” p. 8 “Main Display Area/Home Screen, ” p. 9 “Main Menu Area, ”...
  • Page 8: Chiller Status Area

    Figure 1, p. 7) remains visible from every screen on the Tracer AdaptiView display. Basic information about chiller status and control appears on the face of the buttons and touch targets. When touched, the buttons and touch targets open other screens that provide more information and control access.
  • Page 9: Main Display Area/Home Screen

    • Active chilled water setpoint (if chilled water control is available) • Evaporator water flow (animation in graphic indicates if evaporator is running) Touch anywhere within the white rectangular area to view the evaporator component screen. CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 10 For more information, see “Viewing Unit Information (About This Chiller),” p. Log Sheet Touch the Log Sheet button to view the Log Sheet. Note: For more information, see “Viewing the Log Sheet,” p. Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 11 The screen saver also appears if you touch the animated graphic on the home screen. Alternately, if you touch the screen saver, the home screen appears. Figure 2. Screen saver Better graphic to come CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 12: Component Screens

    (See, for example, the buttons on the evaporator component screen in Figure 3, which show the Active Chilled Water Setpoint and the Evaporator Water Pump Override). Note: For more information about changing settings, see “Equipment Settings, ” p. Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 13: Main Menu Area

    Touch the Settings button to view the Settings screen, which is separated into the following three categories: • “Equipment Settings,” p. 34 • “Display Settings,” p. 47 • “Security Settings,” p. 54 Note: Refer to the page numbers for detailed information about each category. CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 14: Stopping/Restarting Chiller Operation

    To stop the chiller in either of these ways: 1. Touch the Stop button to initiate the chiller shutdown process. A confirmation screen appears (Figure Figure 4. Stop the Chiller confirmation screen Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 15: Restarting The Chiller

    Touch the Auto button to initiate the chiller restart process. You can observe the mode change to Auto. The chiller will wait until cooling is needed before starting the compressor. When the chiller is running normally, it automatically starts and stops as needed to reach its setpoints. CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 16: Alarms

    Alarms You can use the Tracer AdaptiView display to view alarms and to reset them. Alarms are communicated to the display immediately upon detection. Viewing the Alarms Screen Touch the Alarms button in the main menu area (Figure 1, p.
  • Page 17: Understanding Alarm Icons

    Description: Alarms are sorted alphanumerically by name, followed by the most recent. • Status: Alarms are sorted according to active/historic status (if you are viewing both active and historic alarms), followed by the most recent. CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 18: Resetting Alarms

    If an active alarm is present, the alarm indicator button (Table 1, p. 8) appears in the upper left of the screen, as in Figure 6, p. 16. The icon on this button indicates the level of the most severe active alarm. Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 19: Reports

    Reports You can use the Tracer AdaptiView display to view a variety of reports and to create and edit a custom report. All reports contain live data that refreshes every 2–5 seconds. Viewing the Reports Screen Touch the Reports button in the main menu area (Figure 1, p.
  • Page 20: Viewing The Log Sheet

    “Appendix B: Reports, ” p. 62. The items included in the Log Sheet are those recommended by Trane. See current Trane service literature for more information. Notes: You can also access the Log Sheet by touching the Log Sheet button at the bottom of the home screen.
  • Page 21 Note: A page number appears in the lower right corner of the screen. If a screen contains more than one page, up/down arrows also appear for viewing the other pages, as in Figure Figure 9. Custom Report screen CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 22: Editing A Custom Report

    • Display Software Build • Unit Sales Order Number • Application Part Number • Display Boot Code • Unit Serial Number • Boot Part Number • Hardware Serial Number • Build Part Number Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 23: Viewing Chiller Operating Modes

    Note: You can also access the Chiller Operating Modes screen from the button in the upper left of the screen. In Figure 10, this button indicates that the chiller is running. Figure 10. Chiller Operating Mode screen CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 24 (IGV). Table 6. Chiller submodes Top-level mode Corresponding sub-level mode Stopped Local Stop Panic Stop Diagnostic Shutdown—Manual Reset Run Inhibit Ice Building Is Complete Tracer Inhibit External Source Inhibit Diagnostic Shutdown—Auto Reset Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 25 Free Cooling Opening Free Cooling Valves Closing Free Cooling Limit Preparing to Shutdown Closing IGV IGV Position % Shutting Down Post-Lubrication Time MIN:SEC Evaporator Pump Off Delay MIN:SEC Condenser Pump Off Delay MIN:SEC CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 26: Viewing Purge Operating Modes

    If less than 6 submodes are active, the submode rows that do not apply are blank. For detailed information about purge operating modes and submodes, see the EarthWise™ Purge System with Tracer AdaptiView™ Control Operation and Maintenance Guide (PRGD-SVX01A-EN). Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 27: Data Graphs

    Data Graphs You can use the Tracer AdaptiView display to view a variety of default data graphs and to create up to six custom data graphs. The data sample rate is 30 seconds, and the data storage duration is 48 hours. These rates cannot be adjusted.
  • Page 28: Viewing Data Graphs

    12-minute graph with 3 minutes between time labels • 40-minute graph with 10 minutes between time labels • 60-minute graph with 15 minutes between time labels • 4-hour graph with 1 hour between time labels Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 29 Figure 13. Set Axis Range screen 2. Touch the Manually set values button under either the Left Y-Axis or Right Y-Axis heading. Enter number buttons appear to the right of the minimum and maximum values. CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 30: Creating Custom Data Graphs

    1. Touch the Create Custom button at the top left of any default data graph screen (see Figure 12, p. 28, for example). The Data Graph Points screen appears (Figure 14). Figure 14. Data Graph Points screen Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 31 Touch Remove to move the selected item to the left box. • To remove all of the items in the right box to the left box, touch Remove All. A confirmation screen appears, asking you to verify your request. CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 32: Creating A Custom Data Graph With No Previously Defined Data Graph Points

    27). The Add/Remove screen appears (see Figure 15, p. 31), but with no data on the screen. 2. Continue by following steps 3 through 5 of “Creating a custom data graph from a default data graph, ” p. Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 33: Editing Custom Data Graphs

    3. Touch Save. The screen you were previously viewing appears with your changes reflected in the table. Figure 17. Edit Data Point screen Deleting a Custom Data Graph Touch the Delete button at the top of a custom graph screen to delete the custom graph. CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 34: Equipment Settings

    Equipment Settings You can use the Tracer AdaptiView display to monitor and change a variety of equipment settings. Viewing the Settings Screen Touch the Settings button in the main menu area (see “Main Menu Area, ” p. 13) to view the Settings screen.
  • Page 35: Viewing And Changing Equipment Settings

    Note: A page number appears in the lower right corner of the screen. If a screen contains more than one page, up/down arrows also appear for viewing the other pages, as Figure Figure 19. Example equipment settings screen (Chiller Settings shown) CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 36 20), touch the button that represents the setting you want. The button becomes shaded, and a Save button appears at the bottom of the screen. Figure 20. Example equipment settings screen with buttons for changing setting Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 37 “Manual Control Settings, ” p. 44. Touching Apply is the same as touching Save, except that you remain at the current screen after the change is communicated to the Tracer UC800 controller (Figure 24, p. 45). CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 38: Chiller Setting

    Valid numerical range appears on screen. Current Limit Control Softload Time Valid numerical range appears on screen. Current Limit Control Softload Start Point Valid numerical range appears on screen. Local Atmospheric Pressure Valid numerical range appears on screen. Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 39: Setpoint Sources

    • Set at the front panel (FP)—Refers to inputs that are entered by an operator using the Tracer AdaptiView display or by a technician using the Tracer TU service tool. Setpoint Source Arbitration The Tracer UC800 uses a process referred to as setpoint source arbitration to prioritize the selection of the setpoint source.
  • Page 40: Changing The Setpoint Source

    1. Touch the Settings button in the main menu area (Figure 1, p. 7). The Settings screen appears. 2. From the Settings screen, touch the Chiller Settings button. The Chiller Settings screen appears. Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 41 5. Touch the button the appropriate source button on the Setpoint Source screen. 6. Touch Save to complete the change. Note: The change applies to all arbitrated setpoints. Figure 23. Changing the setpoint source from an arbitrated setpoint screen CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 42: Feature Settings

    Valid numerical range appears on screen. Outdoor Reset Ratio Valid numerical range appears on screen. Outdoor Start Reset Valid numerical range appears on screen. Outdoor Maximum Reset Valid numerical range appears on screen. Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 43: Purge Settings

    Valid numerical range appears on screen. Disable Daily Pumpout Limit Valid numerical range appears on screen. Purge Liquid Temperature Inhibit • Enable • Disable Purge Liquid Temperature Limit Valid numerical range appears on screen. CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 44: Manual Control Settings

    Clear Restart Inhibit Timer XX:XX min:sec Clear Purge Exhaust Circuit Test Off/On • Auto Purge Rfgt Cprsr Suction Temp • On Purge Liquid Temp Purge Regen Cycle Off/On • Auto Carbon Tank Temp • On Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 45 Also, a Manual Override button appears in the upper left corner of the screen (see Figure 25, p. 46). • Touch Save. The change is communicated to the Tracer UC800 controller. The screen you were previously viewing appears. CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 46 Equipment Settings Figure 25. Manual Control Settings screen (Evaporator Pump Override shown) Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 47: Display Settings

    Display Settings You can use the Tracer AdaptiView display to change the format of the information that appears on the display, and to clean the touch screen. Viewing the Settings Screen Touch the Settings button in the main menu area (see “Main Menu Area, ”...
  • Page 48: Viewing And Changing Display Preferences

    (current value). Touch any of these buttons to view a screen where you can change the format (see Figure 28, p. 49 for an example). The button representing the format currently used is shaded (see the “MMDDYYYY” button in Figure 28). Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 49 2. Touch Save to confirm your selection and to return to the Display Preferences screen. Date Format You can use the Date Format screen to choose from the following date formats: • MMDDYYYY • YYYYMMDD • DDMMYYYY CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 50: Viewing And Changing The Language Preference

    Figure 29, p. 51): • Arabic (Gulf Regions) • Chinese—China • Chinese—Taiwan • Czech • Dutch • English • French • German • Greek • Hebrew • Hungarian • Italian • Japanese • Korean Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 51 Figure 29 as an example). To change the language: 1. Touch the button that shows that language you prefer. 2. Touch Save to confirm your selection and to return to the Settings screen. CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 52: Viewing And Changing Date And Time Preferences

    Above the center line, the following date and time attributes appear: • Month • • Year • Hour • Minute • AM/PM To change the date or time: 1. Touch the square presenting the attribute you want to change. The square becomes highlighted. Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 53: Cleaning The Display

    3. Touch Save to confirm your selection and return to the Settings screen. Cleaning the Display On the Settings screen, touch Clean Display to disable the Tracer AdaptiView display screen for 15 seconds so that you can clean the screen without it responding to touch.
  • Page 54: Security Settings

    Security Settings If security if enabled, the Tracer AdaptiView display requires that you log in with a four- digit security PIN to make certain setting changes. This prevents unauthorized personnel from doing so. Note: The default security PIN is 7123. A technician must use the Tracer TU service tool to define a different PIN, or to recall it if forgotten.
  • Page 55: Disabling/Enabling Security

    Security Settings Disabling/Enabling Security The Tracer AdaptiView display gives you the ability to disable or enable the security feature that allows a user to log in and log out. To disable security, you must be logged in: 1. From the Settings screen, touch the Security button. The Security screen appears (Figure 33).
  • Page 56: Logging In

    If the Log in screen appeared when you tried to change a setting, you return to that setting screen. Note: The PIN is valid until 30 minutes of inactivity pass, or until you log out. Figure 34. Log In Screen Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 57: Logging Out

    1. Touch the Log out button. A confirmation screen appears (Figure 35). 2. Touch Yes to confirm that you want to log out. The Settings screen appears with a Log in button on it. Figure 35. Log out confirmation screen CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 58: Troubleshooting

    Troubleshooting Table 13 contains information to help troubleshoot the Tracer AdaptiView displays. Table 13. Tracer AdaptiView display troubleshooting guide Issue Possible causes/Solutions The screen only partially displays; the Auto and The UC800 configuration is invalid. Stop buttons appear, but there is no text.
  • Page 59: Appendix A: Component Screen Data

    Appendix A: Component Screen Data The following list contains all of the settings and status points that are available for viewing on the Tracer AdaptiView display. Chiller configuration determines which ones appear on the display. Component Settings and status points...
  • Page 60 Starter Current L1 (A) Starter Current L2 (A) Starter Current L3 (A) Starter Voltage AB Starter Voltage BC Starter Voltage CA Motor Winding Temp #1 Motor Winding Temp #2 Motor Winding Temp #3 Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 61 Chiller On—7 Days Pumpout Chiller On—7 days Pumpout Chiller On—7 days Pumpout Chiller Off—7 days Time Until Next Purge Run Purge Rfgt Cprsr Suction Temp Purge Liquid Temp Pumpout—Life Purge Regen Cycle Carbon Tank Temp CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 62: Appendix B: Reports

    Oil Tank Pressure XXX.X PSI/kPa Oil Pump Discharge Pressure XXX.X PSI/kPa Oil Differential Pressure XXX.X PSI/kPa Oil Tank Temperature XXX.X °F/°C IGV1 Position XXX.X % IGV1 Position Steps IGV2 Position XXX.X % IGV2 Position Steps Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 63 XXX.X min Pumpout Chiller On—7 Days XXX.X min Pumpout Chiller Off—7 Days XXX.X min Pumpout—Life XXX.X min Purge Rfgt Cprsr Suction Temp XXX.X °F/°C Purge Liquid Temp XXX.X °F/°C Carbon Tank Temp XXX.X °F/°C CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 64 Outboard Bearing Temp XXX.X F°/C° Evap Entering Water Temp XXX.X °F/C° Evap Leaving Water Temp XXX.X °F/C° Evap Sat Rfgt Temp XXX.X °F/C° Evap Rfgt Pressure XXX.X PSI/kPaA Evap Approach Temp XXX.X °F/C° Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 65 XXX.X °F/C° Cond Water Flow Status: Flow/No Flow Cond Differential Wtr Press XXX.X PSID/kPaD Approx Cond Water Flow XXXX gpm/lpm Second Condenser Ent Wtr Temp XXX.X °F/C° Second Condenser Lvg Wtr Temp XXX.X °F/C° CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 66 Outboard Bearing Temperature Condenser Condenser Approach Temperature Condenser Entering Water Temperature Condenser Leaving Water Temperature Condenser Refrigerant Pressure Condenser Saturated Refrigerant Temperature Condenser Water Flow Switch Status Condenser Pump Override Time Remaining Condenser Pump Override Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 67 Starter Current L2 Starter Current L3 Starter Current L3 Starter Energy Consumption—Not Resettable Starter Energy Consumption—Resettable Time of Last Reset Starter Load Power Factor Starter Power Consumption Starter Power Demand Starter Voltage Phase AB CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 68 Pumpout Chiller Off—7 Days Pumpout Chiller On—7 Days Pumpout—Life Purge Carbon Tank Temp Purge Liquid Temperature Purge Refrigerant Compressor Suction Temp Time at Last Regeneration Time Until Next Purge Run MM:SS Purge Top Level Operating Mode Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 69: Appendix C: Data Graph Data Points

    Approach Temperature Graph data point Axis Evaporator Approach Temperature Left Y-axis Condenser Approach Temperature Left Y-axis Approximate Evaporator Water Flow Right Y-axis Approximate Condenser Water Flow Right Y-axis Average Line Current Right Y-axis CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 70 Graph data point Axis Active Hot Water Setpoint Left Y-axis Condenser Leaving Water Temperature Left Y-axis Condenser Entering Water Temperature Left Y-axis Condenser Saturated Refrigerant Temperature Left Y-axis Approximate Condenser Water Flow Right Y-axis Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 71 Left Y-axis Pumpout Chiller On—7 Days Left Y-axis Pumpout Chiller Off—7 Days Left Y-axis Purge Average Daily Pumpout—7 Days Right Y-axis Purge Refrigerant Compressor Suction Temperature Right Y-axis Purge Liquid Temperature Right Y-axis CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 72: Data Points Available To Include In Custom Data Graphs

    Outdoor Air Temperature Condenser Refrigerant Pressure Condenser Approach Temperature Approximate Condenser Water Flow Second Condenser Leaving Water Temperature Second Condenser Entering Water Temperature Compressor Chiller Control Signal Oil Tank Pressure Oil Pump Discharge Pressure Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 73 Average Phase Voltage Purge Generator Frequency Command Daily Pumpout—24 Hours Pumpout Chiller On—7 Days Pumpout Chiller Off—7 Days Purge Average Daily Pumpout—7 Days Purge Refrigerant Compressor Suction Temperature Purge Liquid Temperature Purge Carbon Tank Temperature CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide...
  • Page 74 Appendix C: Data Graph Data Points Tracer AdaptiView Display Operations Guide • CTV-SVU01B-EN...
  • Page 76 Supersedes CTV-SVU01A-EN January 2008 www.trane.com For more information, contact your local Trane Trane has a policy of continuous product and product data improvement and reserves the right to office or e-mail us at comfort@trane.com change design and specifications without notice.

Table of Contents