3.16 Outdoor unit fan motor
3.16.1 Single phase outdoor unit
Checking procedures
To perform a mechanical check of the propeller fan blade assembly
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
b
a
a Fuse F1U
b Fuse F3U
Is the problem solved?
Yes
No
INFORMATION
It is recommended to perform the checks in the listed order.
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
1 If propeller fan blade touches the bellmounth, check if the fan motor is
correctly mounted on its base, see
2 Check the state of the propeller fan blade assembly for damage, deformations
and cracks.
Action
No further actions required.
Return to
"Checking
4
procedures" [
204] of the noise filter
PCB and continue with the next
procedure.
"3.17 Plate
4
"Repair
procedures" [
220].
3
Components
|
4
work" [
230].
Service manual
217